V

1

HORIZONTAL TERMINATION

See graph to determine the re-
quired vertical rise V

T

 for the re-

quired horizontal run H

T

.

For vent configurations requiring more than one 45º and
90° elbow the following formulas apply:

Formula 1:  H

< 4.2 V

T

Formula 2: H

+ V

T

 < 24.75 feet

FIGURE 7

REQUIRED
VERTICAL
RISE IN
INCHES (V

T

)

HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)

when 

(H

T

)

 > 

(V

T

)

Simple venting configuration (only one 45º and 90° elbow)

Example 2:

V

1

= 4  ft

V

2

= 1.5 ft

V

T

=

V

V

= 4 ft + 1.5 ft = 5.5 ft

H

1

= 2  ft

H

2

= 1  ft

H

3

= 1  ft

H

4

= 1.5 ft

H

R

=

H

1

 + 

H

H

3

 + 

H

= 2 + 1 + 1 + 1. 5 = 5.5 ft

H

O

= .03(one 45º elbow + three 90º elbow -135º)
=.03(315-135)=5.4ft

H

T

=

H

R

 + 

H

= 5.5 +5.4 = 10.9 ft

H

+ V

T

= 10.9 + 5.5 = 16.4 ft

Formula 1:

H

< 4.2 V

T

4.2 V

= 4.2 x 5.5 = 23.1 ft

 

10.9 < 16.8

Formula 2:

H

+ V

T

 < 24.75 feet

16.4 < 24.75

Since both formulas are met, this vent configuration is ac-
ceptable.

H

4

90°

H

3

H

1

90°

H

2

90°

FIGURE 8

45°

The shaded area within the lines represents acceptable
values for H

T

 and V

T  

.

V

2

Содержание Arlington GDS20N

Страница 1: ...1 W415 0496 B 08 10 05 W415 0496 B 08 10 05...

Страница 2: ...2 W415 0496 B 08 10 05 WHAT TO DO IF YOU SMELL GAS WARNINGS SAFETY PRECAUTIONS...

Страница 3: ...nder water Immediately call a qualified service technician to inspect the stove and to replace any part of the control system and any gas control which has been under water Do not operate the stove wi...

Страница 4: ...ot covered Any labour related to warranty repair is not covered Any labour related to warranty repair is not covered Any labour related to warranty repair is not covered CONDITIONS AND LIMITATIONS NAP...

Страница 5: ...m with local codes In the absence of local codes install to the current standard for gas equipped mobile housing CAN CSA Z240 MH Series in Canada or the manufactured home construction and safety stand...

Страница 6: ...in the centre of a building thereby allowing the most efficient use of the heat created The location of windows doors and the traffic flow in the room where the stove is to be located should be consid...

Страница 7: ...bracket as shown using 2 of the screws supplied Connect the flagged leads to the terminals of the thermodisc Remove the knock out from the housing label 8 Install the variable speed switch rheostat in...

Страница 8: ...n Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the centerline of the terminal Clearance to unv...

Страница 9: ...venting included WALL TERMINAL KIT GD176 24 of vent ing included or 1 12 TO 7 12 PITCH ROOF TERMINAL KIT GD110 8 12 TO 12 12 ROOF TERMINAL KIT GD111 FLAT ROOF TERMINAL KIT GD112 or STOVE PERISCOPE KI...

Страница 10: ...bottom air slot is located a minimum of 12 inches above grade The maximum allow able vent length depends on the fireplace as illustrated FIGURES3a c FIGURE4 TYPICAL VENT INSTALLATIONS SPECIAL VENT IN...

Страница 11: ...in feet feet inches 1 0 03 0 5 15 0 45 6 0 30 0 9 11 0 45 1 35 16 0 90 2 7 32 0 the first 45 and 90 offset has a zero value and is shown in the formula as 45 and 90 respectively or 135 when combined F...

Страница 12: ...ET HT when HT VT Simple venting configuration only one 45 and 90 elbow Example 2 V1 4ft V2 1 5ft VT V1 V2 4 ft 1 5 ft 5 5 ft H1 2ft H2 1ft H3 1ft H4 1 5ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 one 45...

Страница 13: ...ce both formulas are met this vent configuration is ac ceptable when HT VT FIGURE9 REQUIRED VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSETS IN FEET HT FIGURE10 For vent configurations requir...

Страница 14: ...eptable Formula 2 HT VT 40 feet 15 9 40 Since only formula 2 is met this vent configuration is unac ceptable and a new fireplace location or vent configuration will need to be established to satisfy b...

Страница 15: ...in the ceiling and the roof to provide the minimum 1 inch clearance be tween the stove pipe and any combustible material Try to center the exhaust pipe location midway between two joist to prevent hav...

Страница 16: ...ng Slide the storm collar around the air terminal and down to the caulking Tighten to ensure that a weather tight seal between the air terminal and the collar is achieved Attach the other storm collar...

Страница 17: ...L copper tubing with a shut off valve to the stove 2 Seal and tighten the gas line securely to a flex connector DO NOT KINK FLEXIBLE CONNECTOR 3 Check for gas leaks by brushing on a soap and water so...

Страница 18: ...It is not necessary to remove the cast front in order to remove the door 1 Lift the top cast piece off of the unit 2 Unlatch the door latches from the door 3 Slide the door straight up to remove Follo...

Страница 19: ...shown onto the rear log support brackets Ensure the cutout on the left underside of the log fits over the pilot assembly Bend the bracket on the right side to help retain the rear log 2 Place the hol...

Страница 20: ...itch must be in the ON position to ignite the burner 10 Turn on all electric power to the fireplace When lighting and re lighting the gas knob cannot be turned from PILOT to OFF unless the knob is dep...

Страница 21: ...ermopile on one leg and reaches toward the burner on the other leg 5 Replace the cleaned logs 6 Check to see that the main burner ignites completely on all openings when the gas knob for the burner is...

Страница 22: ...ER 30 GD222 TERMINALASSEMBLY 31 BM67ADJ 30 TO 53 ADJUSTABLE PIPE 7 DIA 32 W500 0077 FIRESTOP WALL PLATE 33 W020 0032 HARDWARE 34 BRTC7 BRASS TRIM COLLAR 35 BM6724 24 STOVE PIPE 7 DIAMETER 36 W010 0300...

Страница 23: ...23 W415 0496 B 08 10 05 WARNING This is a fast acting thermocouple It is an integral safety component Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd...

Страница 24: ...s knob is on HI wall switch thermostat is on Main burner orifice is plugged Faulty thermopile Faulty themostat or switch remove stoppage in orifice replace connect a jumper wire across the wall switch...

Страница 25: ...led at all joints check that minimum rise per foot has been adhered to for any horizontal venting Air shutter has become blocked ensure air shutter opening is free of lint or other obstruc tions Flame...

Страница 26: ...26 W415 0496 B 08 10 05 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Страница 27: ...27 W415 0496 B 08 10 05 NOTES...

Страница 28: ...28 W415 0496 B 08 10 05 NOTES...

Отзывы: