StarLink™ Connect SLE-LTEV-C / SLE-LTEV-Z Alarm Communicators -- Installation Instructions
7
NOC Originated
Alarms
Contact ID
Event Data
Sent
Pulse Format
Event Code
Sent
Initiated By
Comments
Supervisory Fail
E356 A00 Zn000
99
Automatically by NOC if fail to receive
any signal from StarLink radio within
Supervisory Timeout duration.
For Auto Enroll, uses captured telephone
number, Sub ID and format. For Dealer
Programmed, uses entered telephone
number, Sub ID and format.
Press to Send
Test Signal
E601 A00 Zn000
98
Manually by dealer from the Manage-
ment Center
Signal Log
screen (located
at
http://NapcoNoc2.com
). Sends test
into CS receiver.
Same comment as above.
Press to Send
Radio Test
Not Applicable
Nothing sent to
CS receiver
Not Applicable
Manually by dealer from the Manage-
ment Center
Checkins
screen (located at
http://NapcoNoc2.com
). Sends a com-
mand to the StarLink radio to force a
check-in to the NOC.
----
S I G N A L S O R I G I N AT E D A T T H E N O C
STARLINK RADIO RELATED EVENT
REPORT CODES
(Contact ID by default)
EVENT
AREA
CONTACT ID
PULSE
4/2
CODE
ZONE #
IN 1 Fire
0
E110
990
1A
IN 2 Panic
0
E120
992
22
IN 3 Trouble
0
E300
993
F3
Low Battery/Voltage
0
E302
994
F4
Tamper Trouble
0
E341
995
F5
Reboot
0
E625
997
F7
IN 1 CO (Carbon Monoxide)
0
E162
998
18
Panic Alarm*
E123
Holdup Alarm*
E122
Medical Alarm*
E100
24 hour Aux. Alarm*
E150
24 hour Aux. Restore*
R150
Burg Perimeter Alarm*
E131
Burg Interior Alarm*
E132
Keypad Holdup Alarm (ambush)*
E121
Keypad Panic Alarm*
E123
Keypad Emergency Alarm*
E140
Opening*
E401
Closing*
R401
A.C. Trouble*
E301
Tel 1 Fail*
E351
Fire Polling Report
E780
999
F9
Supv Failure Report
E788
000
D1 or D2
Tip/Ring Wiring Fault Report
E789
000
F2
Path Test Report
E602
890
77
*Not generated by the StarLink radio.
COVER TAMPER SWITCH
The SLE series radios in the plastic housings are
provided with a front tamper switch.
Note:
The tamper
switch on the radio PC board is always functional and
requires no programming.
JUMPER DESCRIPTIONS
Jumper block labeled "
X5
"; from top to bottom, as
detailed in the following table.
Note:
Contact ID is
always available in response to a Contact ID
handshake.
The SLE series radios are compatible with 4/2 Pulse
Dialing formats with 10pps, 20pps, and 40pps with and
without checksum, either 1400Hz or 2300Hz
handshake / kissoff. See WI2336LF for table of
formats.
Refer to WI2140 for selecting the required handshake /
kissoff frequency in the NOC (
http://NapcoNoc2.com
)
setup screens (as required by the control panel).
Jumper Block "X5" Options
Jumper block labeled "X5" contains 5 jumper terminals; from top
(labeled "1") to bottom (labeled "5") as follows:
Jumper ON
Jumper
Number
Jumper OFF
Not used; do NOT install jumper
1
Not used; do NOT install jumper
4/2 with Checksum Pulse Format
2
Contact ID or 4/2 format without
sum check
Not used; do NOT install jumper
3
Not used; do NOT install jumper
Supervised inputs. EOLR(s)
required, see page 3
4 and 5
Not permitted by UL1610