Connect SLE-LTEV-C / SLE-LTEV-Z Alarm Communicators -- Installation Instructions
To report the radio trouble to the central station:
1. Program the SLE-LTEV-C/Z (select "
Y
") for the "Tip/Ring
Wiring Fault Report" feature located in the
Advanced
Features
screen of the Napco " NOC" (at
http://
NapcoNoc2.com
).
2. Install a UL Listed 10K EOLR across the control panel
terminals normally intended to be wired to the home tele-
phone if Telco service was used (shown in the wiring
diagram examples).
Note:
Some control panels may require a different dura-
tion than the default time of 3 minutes. See also the alter-
nate supervision method described below, "
Telco Line to
Alarm Panel Supervision (For Primary Mode Only)
".
Supervision Time Schedule Considerations
If a status change (alarm trouble, etc.) is transmitted, the ra-
dio supervision timer is restarted.
For example, if a status change is sent, the next regular su-
pervision transmission will occur at the interval determined
by your rate plan.
For radio models powered by the control panel Aux Power
terminals, wire the radio directly to the PGM1 output of the
control panel (program the radio to report all troubles on
PGM1).
You can also wire to the positive terminal of the dedicated
zone on a GEMC-EZM8. Thus when a radio trouble is de-
tected, the radio PGM activates the control panel zone, and
the control panel generates a trouble.
StarLink Panel / Radio Supervision of Tip/Ring Wiring
We recommend that the StarLink radio connection to the
control panel be supervised with local trouble annunciation
and report to the central station if the Tip/Ring wiring is cut or
shorted.
For local annunciation of radio troubles, the control panel
must be programmed for Telco line supervision that will pro-
duce a local trouble at the premises (refer to control panel
programming).