 SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 

WIRING THE TAMPER SWITCHES  
(REQUIRED FOR UL COMMERCIAL BURGLARY) 

Before installation and wiring, the tamper switches (part 

GEM-

Tamperkit

) are normally open devices; when placed into 

the circuit and into operation, they are normally closed devic-
es.   
 
Tamper switches protect against the opening of the radio cabi-
net door or the removal of the radio enclosure from the wall or 
other mounting surface.   
 
There are two places in the cabinet to mount tamper switches: 
(1) To prevent cabinet removal from the wall, located on the 
left side of the cabinet there is one knockout for the switch 
plunger and three mounting holes (in the enclosure sheet met-
al).  (2) To protect the cabinet door,  mount a tamper switch in 
the three mounting holes (in the enclosure sheet metal).  
When mounted, the switch button contacts the inside surface 
of the door.  

Note:  

Be sure to alert the user that opening the 

enclosure door will cause a tamper alarm.   
 
Wiring a normally closed sensor loop for tamper supervision, 
wire to a zone on the control panel. 

GEM-Tamperkit 

consists of 

Description 

QTY 

SC206LF 

Slotted Pan Head 6-32 x 3/4  

Machine Screw 

SW105 

Tamper Switch 

Tamper Switch Mounting Instructions 

Back T

a

m

p

er 

D

o

or

 Tam

p

er

 

VIEW OF TAMPER SWITCHES: 

(1) = ENCLOSURE BASE;  
(2-BACK) = TAMPER SWITCH TO PREVENT REMOVAL FROM WALL;  
(3-DOOR) = TAMPER SWITCH TO PROTECT THE ENCLOSURE 

DOOR 

NYCFD Conditions of Acceptability 

 

1.  Only radios Listed for UL 864 Commercial Fire are NYCFD approved. 

2.  All installations must be dual path (DACT and Radio) and DACT shall be primary. 

3.  Each path must be supervised not exceeding 24 hours. 

4.  Failure of either path shall be annunciated at the protected premises. 

5.  Failure of either path shall cause a trouble to be sent to the central station within 5 minutes on the other 

communications path. 

6.  When a remote antenna is used, the antenna transmission line shall be installed in rigid metal, intermediate metal, 

or electrical metallic tubing in accordance with NFPA70, NEC. 

7.  Interconnections between elements of transmitting equipment, including any antennas, shall be supervised either to 

cause an indication of failure at the protected premises or to transmit a trouble signal to the supervising station. 

8.  All UL requirements must be complied with. 

Содержание SLE-LTEV-CB

Страница 1: ...com Note Technical Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2018 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio c...

Страница 2: ...structions Note Antennas are not Listed by UL For LTE radios where an External Antenna needs to be in stalled outside of the room in which the radio is installed maximum 30 meters 98 feet in Resident...

Страница 3: ...c com Located at the bottom of the StarLink radio PC board the 17 terminals are described as follows TB1 PWR 12V Note Model SLE LTEV CFB is rat ed 12 24VDC input Refer to section STEP 4 APPLY POWER TB...

Страница 4: ...rent due to the application such as when 24 hour standby time is required for Fire or CO the SLE ULPS R Charger Module accessory must be used to charge an additional battery and to supply the power fo...

Страница 5: ...StarLink radio can also func tion as a backup to the existing telephone lines install jumper 3 in terminal block X5 When used as a backup communicator and when it senses telephone line trouble the Sta...

Страница 6: ...receivers via TCP IP STARLINK RADIO RELATED EVENT REPORT CODES Contact ID by default EVENT AREA CONTACT ID CODE ZONE IN 1 Fire 0 E110 990 1A IN 2 Panic 0 E120 992 22 IN 3 Trouble 0 E300 993 F3 Low Ba...

Страница 7: ...PGM activates the control panel zone and the panel generates a trouble that is sent to the central station All installations also require wiring an output from the control panel as follows With Gemin...

Страница 8: ...he transformer compartment knockouts Keep all non power limited wiring separate from all power limited wiring inside the housing by 1 4 In addition maintain a minimum 1 4 separation of all primary wir...

Страница 9: ...ng inside the housing by 1 4 Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the al...

Страница 10: ...ther the TRF12 T123 16 5V 20VA transformer or the chas sis mounted 16 5VAC 20VA transformer Transformer optional Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink t...

Страница 11: ...IP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional Transformer TELCO QUAD WIRE Optional When Power...

Страница 12: ...nstructions for the GEMC F8ZCPIM as a Monitor Zone Only When PGM1 is wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with a 560ohm 1 2 watt min EOL resistor Connect PGM1 to the negative...

Страница 13: ...Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer StarLink BATTERY RED BLACK Power Supply SLE ULP...

Страница 14: ...TERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RIN...

Страница 15: ...ring Diagram for PRIMARY Reporting Configuration GEM X255 GEM P9600 GEM P3200 Control Panels Use when telephone line is NOT available AUX POWER CONTROL PANEL HOUSING 13 14 15 16 17 18 19 20 21 22 26 2...

Страница 16: ...GRAY GRAY Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity GRN RED YELLOW BLACK StarLink BATTERY RED BLACK Refer to section S...

Страница 17: ...report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble Panel has alarm and Trouble Rel...

Страница 18: ...wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper...

Страница 19: ...3 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Ma...

Страница 20: ...ompromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provid...

Отзывы: