NAPCO SLE-LTEV-CB Скачать руководство пользователя страница 17

StarLink

 SLE-LTE Commercial Series Alarm Communicators -- Installation Instructions 

17 

Option

 

Application 

Armed 

Disarmed 

Resend 

TBL every 

24 Hrs.  

NOC Inputs 

"Function" 

Selection 

Comments  

Cut 

Wire* 

Open 

Short 

Cut 

Wire*  Open  Short 

FACP 

with

 DACT 

Use IN2 or IN3 only for 

trouble.  Panel reports via 

dialer capture, but Linecut 

for DACT interconnection 

wiring to the radio reports via 

an input on radio.   

TBL 

TBL 

TBL 

Yes 

Supervised Fire 

Trouble (Linecut) 

Requires two EOLRs.  Radio reports in CID 

(use jumpers 4/5)  

-- 

-- 

-- 

Yes 

User Defined 

Unsupervised Fire 

Trouble (Linecut) 

Non-supervised (use conduit max 20 feet 

Commercial Fire or 3 feet Residential Fire) 

(remove jumpers 4/5).   

FACP 

with

 DACT 

Use IN1 (not supervised) 

either for trouble 

or

 alarm.  

Panel has trouble (or alarm) 

relay that closes on the 

condition. 

TBL  

(or 

ALARM) 

Yes 

Un-Supervised Fire 

Trouble (use 'User 

Defined' selection 

for Alarms) 

Non-supervised (use conduit activation 

re12V or 12/24V) 

FACP 

without

 DACT 

Use IN2 or IN3 for both 

Alarm and Trouble on one 

input.  Panel has alarm and 

trouble relay outputs. 

TBL 

TBL 

ALARM 

Yes 

Supervised Fire 

Alarm/Trouble 

Requires two EOLRs.  The Trouble relay 

N.O. contact (de-energized opens) is put in 

series with one EOLR.  Alarm relay put 

across both EOLR and trouble relay.   

BURG 

with

 DACT 

Use IN2 or IN3 for only 

trouble reporting.  Panel 

reports via dialer capture but 

Linecut for DACT intercon-

nection wiring to the radio 

reports via an input on radio. 

ALARM 

ALARM 

ALARM 

TBL 

TBL 

TBL 

No 

Supervised Burg-

Linecut 

Requires two EOLRs.  Program panel to 

report Open/Close (radio remembers last 

state of panel for Napco panels when used 

with local download cable).   

BURG 

without

 DACT 

Use IN2 or IN3 for both 

Alarm and Trouble. Panel 

has alarm and Trouble 

Relay/PGM outputs. Two 

EOLRs are needed since for 

UL Burg it is required to 

detect both wire breaks and 

shorts. 

ALARM 

TBL 

ALARM 

TBL 

TBL 

TBL 

No 

Supervised Burg 

Alarm/Trouble 

Requires two 10K EOLRs.  Three off nor-

mal conditions can be detected, namely, 

cut wire, shorted loop and one of the 

EOLR's having a closed contact in series.  

The Trouble relay N.O. contact (de-

energized opens) is put in series with one 

EOLR.  The Alarm relay N.O. contact is put 

across both EOLRs and trouble relay. The 

panel Armed or Disarmed state is deter-

mined by a separate input (see Option 6 in 

this table below for armed status opera-

tion). (

Note: 

 The Alarm relay should NOT 

activate on 24hr zones.) 

BURG

 without

 DACT: 

Armed Status

 

Use IN2 or IN3 for Armed 
Status input. Two EOLRs 

are needed since for UL 

Burg it's required to super-

vise for both wire breaks and 

shorts. 

TAMPER 

ALARM 

N/A 

ALARM 

TBL 

N/A 

TBL 

No 

Supervised Arm/

Disarm Status 

Requires two 10K EOLRs. A relay or PGM 

for Arm/Disarm status goes in series with 

one EOLR where open is disarmed and 

closed is armed. The other EOLR is across 

the series combination (relay for Arm/

Disarm and first EOLR) to provide the loop 

supervision. 

1  

Input Configuration Options 

*

Note:

  On line cut, PGM1 will activate. 

REN

 = 0.  The 

Ringer Equivalence Number

  (

REN

) indicates the maximum number 

of devices allowed to be connected to a telephone interface.  The termination of an 
interface may consist of any combination of devices subject only to the requirement that 
the sum of the 

REN

s of all the devices not exceed five (5). 

Содержание SLE-LTEV-CB

Страница 1: ...com Note Technical Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2018 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio c...

Страница 2: ...structions Note Antennas are not Listed by UL For LTE radios where an External Antenna needs to be in stalled outside of the room in which the radio is installed maximum 30 meters 98 feet in Resident...

Страница 3: ...c com Located at the bottom of the StarLink radio PC board the 17 terminals are described as follows TB1 PWR 12V Note Model SLE LTEV CFB is rat ed 12 24VDC input Refer to section STEP 4 APPLY POWER TB...

Страница 4: ...rent due to the application such as when 24 hour standby time is required for Fire or CO the SLE ULPS R Charger Module accessory must be used to charge an additional battery and to supply the power fo...

Страница 5: ...StarLink radio can also func tion as a backup to the existing telephone lines install jumper 3 in terminal block X5 When used as a backup communicator and when it senses telephone line trouble the Sta...

Страница 6: ...receivers via TCP IP STARLINK RADIO RELATED EVENT REPORT CODES Contact ID by default EVENT AREA CONTACT ID CODE ZONE IN 1 Fire 0 E110 990 1A IN 2 Panic 0 E120 992 22 IN 3 Trouble 0 E300 993 F3 Low Ba...

Страница 7: ...PGM activates the control panel zone and the panel generates a trouble that is sent to the central station All installations also require wiring an output from the control panel as follows With Gemin...

Страница 8: ...he transformer compartment knockouts Keep all non power limited wiring separate from all power limited wiring inside the housing by 1 4 In addition maintain a minimum 1 4 separation of all primary wir...

Страница 9: ...ng inside the housing by 1 4 Remove shunt J2 to isolate relay common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the al...

Страница 10: ...ther the TRF12 T123 16 5V 20VA transformer or the chas sis mounted 16 5VAC 20VA transformer Transformer optional Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink t...

Страница 11: ...IP STARLINK RADIO HOUSING Power Supply SLE ULPS R Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer optional Transformer TELCO QUAD WIRE Optional When Power...

Страница 12: ...nstructions for the GEMC F8ZCPIM as a Monitor Zone Only When PGM1 is wired to a GEMC F8ZCPIM zone replace the 2 2k ohm EOL resistor with a 560ohm 1 2 watt min EOL resistor Connect PGM1 to the negative...

Страница 13: ...Radio Terminals PANEL RING PANEL TIP STARLINK RADIO HOUSING Either the TRF12 T123 16 5V 20VA transformer or the chassis mounted 16 5VAC 20VA transformer StarLink BATTERY RED BLACK Power Supply SLE ULP...

Страница 14: ...TERY RED BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PANEL RIN...

Страница 15: ...ring Diagram for PRIMARY Reporting Configuration GEM X255 GEM P9600 GEM P3200 Control Panels Use when telephone line is NOT available AUX POWER CONTROL PANEL HOUSING 13 14 15 16 17 18 19 20 21 22 26 2...

Страница 16: ...GRAY GRAY Optional When Power Supply SLE ULPS R is not used connect Panel Aux Power to StarLink terminals 1 and 2 observing polarity GRN RED YELLOW BLACK StarLink BATTERY RED BLACK Refer to section S...

Страница 17: ...report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble Panel has alarm and Trouble Rel...

Страница 18: ...wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper...

Страница 19: ...3 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Ma...

Страница 20: ...ompromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provid...

Отзывы: