background image

14

WI1370 XP-400 Installation Instructions  

[21]Keypad Features 2 

(1) Audible Panic

 - Keypad Panic will not 

turn the Bell on unless this option is 
programmed. 

(2) Exit/Entry with Urgency

 - select to give 

an audible indication of Exit and Entry times.  
During the last 10 seconds of entry and exit 
time, the keypad sounds a distinct sound to 
indicate the premises must be left or the 
panel must be disarmed. 

(3) Display Bypassed (Armed)

 - Select to 

display bypassed zones while the panel is 
armed. 

(4) Disable Code Entry Beeps - 

Program 

to disable keypad beeping on valid code and 
function entries. 

 

[22]Miscellaneous Features 1 

(1) Abort Delay

 - Program to allow a 15 

second Delay (except  

24 Hour Zones

) after 

a zone trip before reporting.  Disarm the 
system within 15 seconds to prevent 
reporting. 

(2) Easy Exit/Easy Arm

 - Enables 

A0

 

command.  While the system is armed, 
entering this command allows 3 minutes to 
Exit through 

Exit/Entry 

and 

Exit/Entry 

Follower Zones

.  Enabling this option also 

enables Easy Arm,  enter 

a0

 to arm 

the system. 

(3) Swinger Shutdown

 - Automatically 

disables armed zones with excessive alarm/
restores (swingers).  Non-24-Hour 
Protection zones: allows only 3 alarms and 
2 restores per zone per arming before the 
zone is disabled. 

(4) Bell on Line Cut

 (Armed) - Program to 

turn the Bell Output on if the telephone line 
has been cut while the panel is armed. 

 
[23]Programmable Output  Features 1 

(1) Audio Verification

 - Program to activate 

the PGM during reporting.  Select specific 
zones for audio verification by programming 
the required zones in 

PGM Output

  [08],   

PGM Features 2

 [24] and 

PGM Features 3 

[25].  Connect the PGM to the Veriphone

TM

 

trigger low input.   

(2) Access Output

 - Activates the PGM 

output for 5 seconds using the 

A3

 

command.  

(3) Follow Keypad Sounder

 - The following 

keypad sounds will activate the PGM output:  
Entry Sounder, Keypad Pulsing Sounder,  
Keypad Output on Alarm, Chime, Fault Find. 
(

4) Keyfob/Keyswitch Chirp

 - Program to 

chirp the PGM Output (1) one time when the 
panel is armed or (2) two times when the 
panel is disarmed.  Wire as shown in Figure 
6. 

 
 
 
 
 
 

 
 
 
 
[24]Programmable Output

 

 Features 2 

(1) Reserved

 

(2) AUX

 - Program to activate the PGM on a 

AUX alarm. 

 N/O 

 N/C 

COM

BLK 

RED 

+AUX

 

Siren Driver  
Steady Input 

PGM

+AUX

K1 

FIGURE

 

6

  K

EYFOB

/K

EYSWITCH

 C

HIRP

 

Содержание RPXP4GT

Страница 1: ...XP 400 RPXP4GT keypad Control Panel Communicator Installation Instructions WI1370 1 05 NAPCO 2005...

Страница 2: ...Cut Detection Answering Machine Override Second Call Communicator 2 Telephone Numbers Backup Reporting Pager Format Point ID Format Individually Report 4 Users Opening after Alarm Report Cancel Code C...

Страница 3: ...12V 4 AH Rechargeable Change Battery every 5 years or as required Maximum Charging Current 165 mA Maximum Input Current 2 58 A Loop Characteristics Loop Voltage 5 Volts Loop Current Zones 1 2 0 9 mA...

Страница 4: ...ification HARMONIZED STANDARDS EN50081 1 and EN50082 1 EC DIRECTIVES 89 336 EEC Electromagnetic Compatibility Directive Optional Accessories Wireless Receiver Window Door Transmitter Key Fob Transmitt...

Страница 5: ...ng PCPreset For Site Initiated Downloaded see Auto Download ID Number 93 Local Downloading Wire as shown in Figure 1 Use the power up or A6 method of establishing a connection The power up method is r...

Страница 6: ...as shown in the wiring diagram in the back of this manual WARNING The FCC restricts the use of this equipment on certain telephone lines Read the FCC statement on the back of this manual to ensure co...

Страница 7: ...ode when the Bell or PGM is ON Bell and PGM will turn OFF Keypad LEDs W ARMED LED DEFINITION Armed ON Instant Mode Rapid Flash Zone in Alarm Flashing X READY LED DEFINITION Ready to be Armed ON Zone f...

Страница 8: ...entering the premises through an Exit Entry Zone the keypad will sound the Entry Delay Tone Enter a valid Arm Disarm code If a valid Arm Disarm code is entered the keypad will beep 6 times indicating...

Страница 9: ...sing a zone Disarmed only Press the C key then the number of the zone to be unbypassed Group Bypass Press C C to Bypass all Exit Entry Follower Zones 02 or Home Away Zones 01 only if the system is pro...

Страница 10: ...command to bypass all Exit Entry Follower Zones or Home Away Zones only if the system is programmed exclusively for Home Away with Delay zones A4 Instant Enter this command before or after arming to...

Страница 11: ...eypad will sound a short beep for transmitters with signal strengths of 3 or less Zone Features 00 Exit Entry Zones Delay allows exit and entry through an Exit Entry Zone after the system is armed wit...

Страница 12: ...s restored while the control panel is still armed the zone will automatically be unbypassed and any subsequent violations of the zone will cause an alarm condition 04 24 Hour Protection A zone that pr...

Страница 13: ...am the interval in days between Test Timer reports Test Timer Interval may be programmed from 1 to 255 days 15 Line Cut Time to Fail Enable this feature by programming the delay time required to decla...

Страница 14: ...winger Shutdown Automatically disables armed zones with excessive alarm restores swingers Non 24 Hour Protection zones allows only 3 alarms and 2 restores per zone per arming before the zone is disabl...

Страница 15: ...ion is not permitted for UL installations Telephone Number 1 Programming 30 Subscriber ID Number For 4 2 format enter a 4 digit number If 3 1 format is required enter a 3 digit number then press the i...

Страница 16: ...ager Format Selected Pager PIN Number Program if a PIN number is required by the paging system The digits in Telephone Number 2 will be added on to telephone number 1 and or telephone number 3 allowin...

Страница 17: ...ne detection can be disabled by programming No Dial Tone Detection 46 1 To program any additional delay enter a D where required in the phone number 42 Receiver Format Telco 2 Select the format that w...

Страница 18: ...tore code is the zone number of the restored zone For example if the Zone Restore Code 62 is programmed to E the restore code for that zone would be E4 4 2 format 62 2 Trouble Code Conditional Closing...

Страница 19: ...al Closing Telco 3 see 67 1 3 Reserved 4 Reserved Wireless Up to two receivers can be wired to the XP 400 Each wireless transmitter can be mapped to a zone Only 1 wireless device is permitted per zone...

Страница 20: ...c alarm when the M or N buttons on the Keyfob are pressed Additional programming required Keypad Panic GG 20 3 Panic Report to Telco 1 36 2 and or Telco 3 56 3 Audible Panic Optional 21 1 2 AUX Progra...

Страница 21: ...t 91 2 Answering Machine Override Using the downloading computer call the panel When the operator has determined that the panel has received 1 2 rings pressing the u key will cause the downloading com...

Страница 22: ...nnot be programmed from User Program Mode 96 Dealer Options 1 1 Dealer Code Lockout Program to prevent the Dealer Code from changing with a panel default 2 User 1 Code Lockout If programmed the User 1...

Страница 23: ...will beep once every 10 seconds The keypad will continue to beep until the reset button is pressed or the trouble has been acknowledged by pressing the i key System Trouble Reporting The following sys...

Страница 24: ...EOL2 2K resistor must be installed 3 Rcvr Fail to Respond Rcvr Tamper The receiver is not responding to the panel The red LED on the receiver should be flashing refer to WI848 The cover is off the rec...

Страница 25: ...t loop current flowing through the Bell circuit for supervision To eliminate this cut resistor R26 which is located directly above Terminal 9 just below the heat sink 5 Where are the fuses The control...

Страница 26: ...1 and point 2 is jumped out If using internal reed make sure J1 is cut and both Point 1 and Point 2 terminals are jumped out 10 Keypad LEDs Flicker The Keypad is not receiving a POLL from the Panel Ch...

Страница 27: ...esistors AUX POWER OUTPUT 10 12 5 VDC XP 400 WIRING DIAGRAM REFER TO INSTALLATION INSTRUCTIONS WI1371 RESIDENTIAL BURG 4 HOUR STANDBY COMBINED STANDBY 350 mA BELL 2 0 AMP 1 Z NOT USED Normally Open Zo...

Страница 28: ...sting and due to but not limited to any or all of the following criminal tampering electrical or communications disruption it is possible for the system to fail to perform as expected NAPCO does not r...

Отзывы: