![NAPCO MAGNUM ALERT 1008e Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/napco/magnum-alert-1008e/magnum-alert-1008e_installation-instructions-manual_3339263007.webp)
MA1008e
/
1008eM
Installation Instructions
L
NAPCO Security Systems
Page 7
Activate Fire & Aux. Panics
. Cut Jumper E to enable F/
P/A keypad panics.
Note:
This jumper must be cut to utilize
the three-keypad-panic feature of the MA1088e. Conversely,
if the jumper is cut,
Enable Keypad Fire Panic
or
Enable Key-
pad Auxiliary Panic
must be programmed or adverse opera-
tion will result.
Assembling the Keypad
. To reassemble the keypad af-
ter installation, hang the top of the front panel onto the hooks
in the rear case and push in firmly at the bottom until the re-
tainer tabs snap into place. (If difficulty is encountered, push
the retainer tabs up lightly using a screwdriver, as when re-
moving).
WIRING TO A MERCANTILE BELL
Refer to Fig. 1. Use an zone for a Tamper Zone and pro-
gram it for 24-Hour Protection. The Tamper Zone will super-
vise the cold-water pipe ground, door tamper and bell box.
UL installations require a tamper switch on the control panel
door. For this purpose, use the normally closed (when set)
tamper switch supplied with the MA1008eM in series with the
Tamper Zone.
TYPICAL FIRE INSTALLATION
(Where permitted by local
codes;
not
for use in Mercantile Installations).
At least one smoke detector should be installed directly
outside each sleeping area. If there is more than one floor,
additional smoke detectors should be installed on each level,
including the basement. The living-area and basement
smoke detectors should be installed near the stairway of the
next upper level.
For increased protection, additional detectors should be
installed in areas other than those required, such as dining
rooms, individual bedrooms, furnace rooms, utility rooms and
hallways. Heat detectors, rather than smoke detectors, are
recommended in garages, attics, and kitchens due to condi-
tions that may result in false alarms and improper operation.
Large areas and areas with partitions, ceiling beams, door-
ways, and open joists will require additional detectors. Refer
to NFPA Standard 74 (National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269) for additional infor-
mation, including proper mounting methods.
Fig. 1. Wiring to a Mercantile Bell.
COLD-WATER-GROUND PIPE
WITH GROUND CLAMPS MORE
THAN 1/4" APART.
EARTH GROUND
GROUND
SUPERVISION
WIRE
SPLICE
4700-OHM
END-OF-LINE
RESISTOR
NAPCO MA1008eM
―
BELL
+
TAMPER
ZONE
DOOR
TAMPER
UL INSTALLATIONS
REQUIRE RIGID CONDUIT
OR ELECTRICAL METALLIC
TUBING (EMT) FOR
ENTIRE LENGTH.
ADEMCO AB-12
BELL IN BOX
―
BELL
+
INTERNAL BELL
TAMPER
SWITCHES
4700-OHM
END-OF-LINE
RESISTOR
Fig. 2. Typical Fire Installation.
BEDROOM
HALL
BEDROOM
ATTIC
S
T
S
S
S
T
T
T
F
K
C
ATTIC
T
GARAGE
KITCHEN
RECREATION
ROOM
ATTIC
LIVING
ROOM
BASEMENT
CONTROL CENTER; FIRE ALARM SOUNDING DEVICE;
KEYPAD; SMOKE DETECTOR; HEAT DETECTOR
C
F
K
S
T