![NAPCO MAGNUM ALERT 1008e Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/napco/magnum-alert-1008e/magnum-alert-1008e_installation-instructions-manual_3339263004.webp)
MA1008e
/
1008eM
Installation Instructions
L
NAPCO Security Systems
Page 4
•
Sounder signals:
- Entry Delay in Progress
- Hold-Down Function Accessed
- Entry Door Opened while Disarmed (Chime)
- System Armed with a Zone in Trouble
- Day Zone in Trouble
- Fire Zone Alarm/Trouble
- Central-Station Ringback
- Failure-to-Communicate system trouble
- Exiting Dealer Program Mode
Communicator Features
•
Integral digital communicator with true dial tone detec-
tion, double-pole line seizure and anti-jam
•
Programmable abort delay time
•
Rotary or Touch-Tone
®
dialing available. Rotary dialing
available as backup to unsuccessful Touch-Tone
®
dial-
ing
•
Two telephone numbers and receiver/data formats can
be accessed
•
Two-digit event codes and 4-digit subscriber codes pro-
grammable for those receivers accepting these formats
•
Central-Station Ringback on closing or Auxiliary panic
Reporting Features
•
Report on Alarm
•
Opening and/or Closing Reporting by Individual User
•
Opening Report After Alarm
•
Day Zone Trouble; Fire Zone Trouble
•
Ambush; Panic; Keypad Auxiliary Panic
•
Test Timer; Reset Test Timer on Report
•
AC Failure; Low-Battery Report
•
Force-Arm Report; Force-Arm/Status Report .
•
Control-Panel Restore Report; Zone-Restore Report
•
Backup Reporting; Double Reporting; Split Reporting
Other Features
•
Supports NAPCO's Super Spectrum's Wireless System
•
Audible Bell-Test on Arming
•
Power-Up in Last State
•
Programmable Chime Duration
•
Chine/Display Chime Mode
•
No End-of Line Resistor
•
Watch Mode
•
Sensor Watch™
•
2- or 4-Wire Smoke Detector Compatibility on dedicated
Fire Zone
•
Electronic Dealer lockout prevents unauthorized access
SPECIFICATIONS
Operating Temperature: 0-49 °C (32-120 °F)
Input Power: 16VAC, Class 2 step-down transformer TRF12
(19.2VA) or TRF11* (40VA)
Loop Voltage: 10-13 VDC
Loop Current: 2.8mA (normal resistance)
Loop Resistance: 300
Ω
maximum series resistance
Alarm Output (Burg/Fire): Commercial, 12-12.5VDC, 1.2A
maximum; Residential, 10.9-12.5VDC, 125mA max.
(Dry) Contact Ratings: 24VDC, 2A (resistive)
Auxiliary Output: Commercial, 12VDC regulated; Residen-
tial, 10.6-12.5VDC
Combined Standby Current: (Remote Power + Aux. Output
+ Relay Output) 450mA maximum with standard TRF12;
500mA maximum with optional TRF11
Remote Station,
Current: 35mA typical
Maximum Number: 5
Recommended Battery: Rechargeable, sealed-acid,
(12VDC, 4AH) or (12VDC, 7AH)
Standby Time: See Wiring Diagram
Fuses,
Burglary/Fire Output: 3A, 1AG (F2)
Remote Power: 1A, 1AG (F3)
Battery: 3A, Over Current Protection
Housing Dimensions: MA1008e, 12.6 x 14.1 x 3.6" (32 x 36
x 9.1cm) HxWxD; MA1008eM, 13.3 x 13.3 x 3.8" (33.8 x
33.8 x 9.7cm) (HxWxD)
Shipping Weight: MA1008e, Approx. 14lb. (6.4kg);
MA1008eM, Approx. 11lb. (5.0kg)
*The TRF11 (40VA) Transformer and RBAT6 (7AH) Battery
are required for Mercantile installations.
ORDERING INFORMATION
Equipment Supplied
MA1008e - Residential 8 -zone (7 Burglary; 1 Fire; 3 Key-
pad Panics) 12-volt alarm control panel with integral com-
municator and siren driver, RP1054e keypad, 4AH and
TRF12 power transformer.
MA1008eM--As above, but for Mercantile installations. Less
keypad and battery, but with heavy-duty enclosure, Tam-
per Switch and TRF11 40VA power transformer.
Optional Peripherals and Accessories
RP1054e Designer-Style 4-Wire Keypad
RP1000eLCD Designer-Style Keypad with LCD display
RBAT-H1* Dual Battery Harness (not for UL installations)
TRF11 Transformer, 16VAC 40VA, Class 2 (UL Listed)
TRF12 Transformer, 16VAC, 19.2VA, Class 2 (UL Listed)
EOL2.2K End-of-Line Resistor Assembly, 2.2k
Ω
.
FT2200 End-of-Line Relay/Resistor Supervisory Module
PS3002 Power-Supply Module
MAV-15 Two-Way Voice/Listen In Module
GSM-400 Ground Start Module
LOCK-8 Lock & Key Set
PCI2000 Quickloader Interface and Software
PCL2000 Quickloader Local Download Cable
WL1 Wire with Lug Connector, 20"
*UL Listed Accessory
UL/cUL LISTINGS
Household Fire and Burglary Warning System Control Unit.
Combination Fire and Burglary (see Compatible UL Listed
Devices), Commercial Burglary (MA1008eM)
COMPATIBLE UL-LISTED DEVICES (See Note below)
For Residential control panels:
Smoke Detectors:
4-Wire:
System Sensor 1812, 2812TH, 1851B, 2851B, 2851BTH,
each with B102 Base
ESL 445AT*, 445C, 445CT, 445CR, 445CRT