Installation Instructions, Volume 3

 

SPECIFICATIONS AND RATINGS

 

* Must be reduced if an insufficient number of standby batteries are used.  Refer to Battery Standby chart.

 

Note:

  See individual accessory work instructions (WI's) for exceptions and 

other information. 

 

 

GEMC

-

255MB, GEMC

-

128MB, GEMC

-

96MB and GEMC

-

32MB Gemini C

-

Series Motherboards

 

 

Motherboard  Power  Supply  (GEMC

-

PS24V7A  and  GEMC

-

PS24V4A)  Input  Power:   

120AC 60Hz, 3A; maximum 15A dedicated 

branch circuit.

 

 

 

Motherboard  (GEMC

-

255MB,  GEMC

-

128MB,  GEMC

-

96MB  and 

GEMC

-

32MB) Input Power:  

24VDC, maximum 7A.  

 

 

 

Output Power:

 

 

Note:  

All outputs circuits are power

-

limited.

 

 

Note:   

The GEMC

-

96MB and GEMC

-

32MB provide two 2A NAC cir-

cuits (one 24V and one 12V or 24V selectable).  

 

 

NAC A, NAC B, NAC C:

  Regulated 24V NAC circuit; 2A maximum.  

When configured for 24V Auxiliary Power, it is a Special Application 
output only listed with the GEMC

-

24VR.  The GEMC

-

24VR output is 

Regulated 24VDC, 1A maximum.

 

 

NAC  D:    When  configured  for  24V:   

Regulated 24V NAC circuit; 

2A maximum.  When configured for 24V Auxiliary Power, it is a Spe-
cial Application output only listed with the GEMC

-

24VR.  The GEMC

-

24VR output is Regulated 24VDC, 1A maximum.

 

 

NAC  D:    When  configured  for  12V: 

 Regulated 12V NAC circuit, 

2A maximum or Regulated 12V Auxiliary Power, 1.4A maximum.  

 

 

Fire  Aux.  Relay  Output:

  Wet:  12V Regulated, 750mA max.; Dry:  

Remove  shunt  for  dry  contacts;  see  Wiring  Diagram;  dry  contact 
Form C relay rated 30VAC / VDC, 2.5A maximum.

 

 

Two  Active  low  programmable  outputs:   

(2A maximum).  

Note:  

Relies on 2A over

-

current protection of connected circuit.

 

 

Trouble Sounder Output:

  12V Regulated, 30mA.

 

 

E7  and  E8  Terminals:

  Active low open collector outputs; 0.1V, 2A 

(wire only to power limited circuits 30VDC or less).

 

 

Auxiliary  Power  Output:   

Output 12V Regulated @ 750mA maxi-

mum current.

 

 

Remote Bus Power Output:  

12V Regulated @ 750mA maximum 

current,  supporting  up  to  7  keypads,  zone  expansion  modules,  or 
wireless receivers, etc.

 

 

Auxiliary  Power  24V  Regulated:

    Can  only  be  supplied  through 

NAC A, NAC B, NAC C or NAC D (configured for 24V) programmed 
for  Reverse  Polarity  and  wired  to  GEMC

-

24VR.    1.0A*  Maximum 

(must reduce total combined standby and alarm current by 1.1 times 
24V Regulated current).

 

 

Maximum  Combined  12V  Regulated  standby  current:   

Remote 

Power + Auxiliary Power + NAC D 12V Output and programmed for 
Reverse Po AUX relay if shunt connector is installed:

 

 

plus

 

GEMC

-

BM

 total standby current plus 25mA; 

 

 

plus Fire Relay:

  35mA (when energized);

 

 

plus  GEMC

-

F8ZCPIM

  total  combined  standby  current  +120mA  = 

1.4A*.

 

 

If  additional  12V  current is required, use  the GEMC

-

12V2APS

-

CF  (for  Fire  applications)  and/or  GEMC

-

12V2APS

-

R  (for  non

-

Fire applications) Auxiliary Power supplies.

 

 

Maximum  Total  Combined  12V  Regulated  Standby  and  Alarm 
Current:   

Remote Power + Auxiliary Power + NAC D 12V Output 

and programmed for Reverse Po AUX relay if shunt connect-
or is ins NAC D  alarm current:

 

 

plus GEMC

-

BM

 total combined standby and alarm c 25mA;

 

 

plus GEMC

-

F8ZCPIM

 total standby and alarm current).

 

 

Maximum  Total  Combined  24V  Standby:   

(Total combined 12V 

standby plus alarm current times 0.6) + NAC A

-

D 24V standby cur-

rent:

 

 

plus (GEMC

-

BM

 total combined s 25mA) times 0.6; 

 

 

plus  (GEMC

-

F8ZCPIM 

total  combined  standby  +  120mA  )  times 

0.6;

 

 

plus GEMC

-

BM/PS

 total combined s 25mA;

 

 

plus GEMC

-

FW

-

SLC

 total combined 24V standby current;

 

 

plus GEMC

-

BSLC

 total combined 24V standby current = 1A*.

 

 

Maximum  Total  combined  24V  Standby  and  Alarm  Current:  

(Total combined 12V standby plus alarm current times 0.6) + NAC A

-

D 24V standby plus alarm current:

 

 

plus (GEMC

-

BM

 total combined standby and alarm c 25mA) 

times 0.6;

 

 

plus GEMC

-

BM/PS

 total 24V standby and alarm c 25mA;

 

 

plus  GEMC

-

FW

-

SLC

  total  combined  24V  standby  and  alarm  cur-

rent;

 

 

plus  GEMC

-

BSLC

 total combined 24V standby and alarm current 

=

 

6.8A  with  7A  supply  (GEMC

-

PS24V7A);  3.8A  with  4A  supply 

(GEMC

-

PS24V4A).

 

 

Maximum  Battery  Charging  Current:

    Refer  to  the  GEMC

-

PS24V7A  or  GEMC

-

PS24V4A  power  supply  specifications.    The 

maximum charging current (trickle charge and fast charge) and the 
maximum  ampere

-

hour  capacity  of  the  battery  that  the  product  is 

intended to charge:

 

 

Standby Time:  

See following charts.

 

 

Battery  Power: 

  See  tables  in  sections  "

GEMC

-

PS24V7A    7  AMP 

POWER  SUPPLY

"  and  "

GEMC

-

PS24V4A    4  AMP  POWER  SUP-

PLY

" (data also located in WI1646 and WI1702).

 

 

Loop Voltage:  

See zone expansion modules.

 

 

Loop Current:  

See zone expansion modules.

 

 

Loop Resistance:  

See zone expansion modules.

 

 

Operating Environment:  

0

-

49°C (32

-

120°F).

 

 
 
 

Modules  that  plug  into  the  GEMC

-

XXXMB 

Gemini C

-

Series Motherboards:

 

 

GEMC

-

BM / PS Burglary Module with Power Supply

 

 

Electrical Ratings

 

 

Input Power:

 24V, 25mA standby from motherboard plus 0.6 multiplied 

by the "

Total Combined Standby and Alarm Current

".

 

 

Output Power:

 

 

Burg Bell Power:  

10.8 

-

 12.5VDC, 2A maximum.

 

 

AUX Power:  

11.3 

-

 12.5VDC, 750mA maximum.

 

 

Burg  Bus  Power  ("Remote  Bus  Power"): 

 11.2 

-

 12.5VDC, 750mA 

maximum.

 

 

PGM1:

  Active low, 8.2 

-

 12.0V @ 150mA.

 

 

PGM2:

  Active low, 8.2 

-

 12.0V @ 150mA.

 

 

Aux  Relay:

  Wet 11.2 

-

 12.5VDC @ 750mA maximum (subtract from 

AUX Power); may be set to a dry form "c" relay contact upon removing 
or cutting the jumper "R"; output rated 30VAC/DC, 3A (Resistive Load 
Only)

 

 

Total Combined Standby Current 

(Auxiliary Power + Burg Bus power 

+ Aux Relay power):  750mA.

 

 

Total Combined Standby and Alarm Current 

(Auxiliary power + Burg 

Bus power + Aux Relay power + Bell power):  2.5A.

 

 

Battery Options:  

 

• 

One  12V  4AH  battery:    Maximum  standby  500mA  +  maximum 
alarm 1A = total 1.5A.  

 

• 

One 12V 7AH or 8AH battery:  Maximum standby 750mA + maxi-
mum alarm 1.75A = total 2.5A.  

 

 

Maximum Battery Charging Current:

  1A.

 

 

Note:

  Does not affect GEMC

-

XXXMB standby battery calculations, as 

all  standby  current  is  from  dedicated  battery.    Maximum  GEMC

-

XXXMB combined alarm and standby current must be reduced by 0.6 
times  the  combined  alarm  and  standby  current  of  the  GEMC

-

BM/PS 

plus 25mA.

 

 
 

GEMC

-

BM BURGLARY MODULE 

 

 

Electrical Ratings

 

 

Input  Power:   

12V  Regulated,  25mA  standby  plus  total  combined 

standby  and  alarm  current.    Must  reduce  GEMC

-

XXXMB  total  12V 

standby current by GEMC

-

MB total standby current plus 25mA. 

 

 

Note:

  GEMC

-

BM total standby and alarm current plus GEMC

-

XXXMB 

total 12V standby and 12V alarm current must not exceed 2.5A. 

 

Содержание GEMINI C Series

Страница 1: ...IAL GEMC 255 GEMC 128 GEMC 96 GEMC 32 CONTROL PANEL COMMUNICATOR Installing the GEMINI C Series Control Panels with the GEMC FK1 Keypad and the GEMC BK1 Keypad WIRELESS HARDWIRE GEMC FK1 Keypad GEMC B...

Страница 2: ...ws are registered trademarks of the Microsoft Corporation All other trademarks cited in this manual are for reference only and are the property of their respective owners Copyright 2021 by NAPCO Secur...

Страница 3: ...rammable Output Module 6 GEMC RECV Wireless RF Receiver 6 GEMC NACXX Supervised NAC Extender 6 GEMC FPRINT Parallel Printer Interface 6 GEMC 12V2APS CF Power Supply 6 GEMC 12V2APS R Power Supply 7 Fir...

Страница 4: ...ent 25mA plus GEMC F8ZCPIM total standby and alarm current Maximum Total Combined 24V Standby Total combined 12V standby plus alarm current times 0 6 NAC A D 24V standby cur rent plus GEMC BM total co...

Страница 5: ...ent must be reduced by GEMC BSLC current Operating Temperature 32 to 120 F 0 to 49 C Dimensions W x D x H 4 5 x 4 x 1 Modules Mounted Inside the C Series Motherboard Enclosure GEMC NL MOD Network Comm...

Страница 6: ...outputs are 24V Regulated Supervision AC fail supervision approximate 1 minute delay to prevent nui sance swingers Battery presence low battery supervision and battery charger volt age supervision com...

Страница 7: ...re Set Point 40 F 4 RATINGS Electrical Ratings Input Power 13 6 16 3VDC supplied by GEMC BSLC module 19mA Output Power not applicable Maximum Wiring Length 2000 feet 16 AWG Refer to GEMC BSLC document...

Страница 8: ...Glass types minimum size 10 7 8 x 10 7 8 280 mm x 280 mm 3 32 3 8 plate 1 8 3 8 tempered 1 8 9 16 laminated 1 4 wired 5 8 overall sealed insulated Note Coated glass with security films including film...

Страница 9: ...put Maximum charge current 1 96A 4 ampere continuous supply current at 24VDC Built in charger for sealed lead acid or gel type bat teries Automatic switch over to stand by battery when AC fails AC inp...

Страница 10: ...t Entry Trouble 55 R370 Burg Exit Entry Trouble Restore 56 E137 Burg Zone Tamper Alarm 57 R137 Burg Zone Tamper Restore 58 E370 Burg Zone Tamper Trouble 59 R370 Burg Zone Tamper Trouble Restore 60 E40...

Страница 11: ...Disable Restore 187 E342 Fire Monitor AC Fail 188 R342 Fire Monitor AC Fail Restore 189 E342 Fire Monitor AC Fail Trouble 190 R342 Fire Monitor AC Fail Trouble Restore 191 E338 Fire Monitor Bat Test...

Страница 12: ...CPIM Conventional 8 Fire Zone Expander Plug in Module see WI1651 GEMC FK1 Fire keypad see WI1649 OI341 GEMC FPRINT Print module for Fire Bus see WI1708 GEMC FW SLC Fire SLC Module see WI1647 GEMC HSKI...

Страница 13: ...ystem Kit As above but with 24V Panel 128 Points via commercial addressable wire less or conventional fire devices 4 on board NACs provid ing up to 6 5A notification power GEMC FW 32KT 32 Point GEM C...

Страница 14: ...ogy Motion Detector PIR and Microwave Range 40 x40 Fire Peripherals GEMC FK1 LCD Fire Keypad for GEMC Combo System Red GEMC WL SMK Wireless Commercial Fire Device Photoelectric Smoke De tector GEMC WL...

Страница 15: ...EMC NAC7S Remote NAC Extender Provides four 4 NAC Outputs for a combined output rating of 6 5A or a maximum of 2A on any one output Includes red enclosure 14 x16 must be connected to 120VAC source sup...

Страница 16: ...e system design is possible These Worksheets have been placed into a single Microsoft Excel file available online at the NAPCO website http www napcosecurity com Once at the NAPCO website click the li...

Страница 17: ...r lights indicating the Burglary Access Control portion of the sys tem is disabled 3 If the GEMC BM GEMC BM PS or GEMC BSLC module s are used The general idea is to unplug each of these Burglary modul...

Страница 18: ...B 7 NAC C 9 NAC D 14V 8V pulsing when active 21 REMOTE BUS YEL 20 REMOTE BUS GRN 10V 2 NAC A 4 NAC B 6 NAC C 8 NAC D Zero 0 Volts 3 NAC A 5 NAC B 7 NAC C 9 NAC D 19 REM PWR 23 AUX PWR 2 or 4 GEMC FW...

Страница 19: ...erences the Micro number either Micro 1 or Micro 2 for example ComboMicro1 hex Therefore for the Micro number referenced in the file name click the appro priate Browse button within either the Micro 1...

Страница 20: ...ower supervise the power with an end of line relay as shown below Connect the EOL relay to a conventional or SLC zone programmed as a Fire Monitor Zone Zone Programmed as Fire Monitor Zone POWER IN PO...

Страница 21: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 3 Installation Instructions Volume 3 Page 21 NOTES...

Страница 22: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 3 Page 22 Installation Instructions Volume 3 NOTES...

Страница 23: ...ons Commission helpful How to Identify and Resolve Radio TV Interference Problems This booklet is available from the U S Government Printing Office Washington DC 20402 Stock No 004 000 00345 4 CAUTION...

Страница 24: ...paired by others improperly installed improperly used abused altered damaged subjected to accident nuisance flood fire or acts of God or on which any serial numbers have been altered defaced or remove...

Отзывы: