Supervised Alarm / Relay / Power Expansion Unit 10
CONFIGURATION
If the additional Battery-Backed Power is not needed, a CICP1300ENCL Expansion Unit may be installed with a
CICP1300IOBD Alarm/Relay Board. The wire harness provided with the CICP1300ENCL Expansion Unit allows
it to be powered by an adjacent CICP1300IOCOMBO Expansion Unit or Access Control Panel, but be mindful of
the 500mA load that must be met by the 12 Volt power source for each Alarm/Relay Board.
Note:
The maximum total length of modular cable to be used to connect the three Alarm/Relay Boards to the Access
Control Panel is 9 feet (2.74 meters).
Additional Configurations
A Second CICP1300IOBD Alarm/Relay Board may be installed as described on page 22. Then, a second
CICP1300IOCOMBO may be added to bring the total number of Alarm/Relay Boards to three (shown below).
Figure 4 - Second CICP1300IOBD Alarm/Relay Board