Technical Manual PD4-E-M (EtherCAT)
10 Description of the object dictionary
Object description
Index
2034
h
Object name
Upper Voltage Warning Level
Object Code
VARIABLE
Data type
UNSIGNED32
Savable
yes, category: application
Access
read / write
PDO mapping
no
Allowed values
Preset value
0000C92C
h
Firmware version
FIR-v1426
Change history
Description
If the input voltage of the controller exceeds this threshold value, the motor is switched off and an
error triggered. This error is reset automatically if the input voltage is less than (voltage of object 2034
h
minus 2 volts).
2035h Lower Voltage Warning Level
Function
This object contains the threshold value for the "Undervoltage" error in millivolts.
Object description
Index
2035
h
Object name
Lower Voltage Warning Level
Object Code
VARIABLE
Data type
UNSIGNED32
Savable
yes, category: application
Access
read / write
PDO mapping
no
Allowed values
Preset value
00002710
h
Firmware version
FIR-v1426
Change history
Description
If the input voltage of the controller falls below this threshold value, the motor is switched off and an
error triggered. The error is reset automatically if the input voltage exceeds the voltage of object 2035
h
plus 2 volts.