Installation Guide Modbus E5000 IAQ probe
page 5/6
3. Flush mounting
Use the multi material backbox provided or an airtight insulated backbox with a
waterproofing membrane through which the sheath passes. If the backbox passes
through the sealing plane, seal between the backbox and the partition with a
specific VOC free and silicone free sealant. If ordering the backbox separately:
Make sure that the backbox doesn’t contain Silicone.
The internal depth of the case must be at least 50mm.
The internal diameter (about 64mm) shall have a 40x40mm space free up to
the bottom)
The space between screws shall be 60mm
The height of the screws heads shall be 2mm max)
4. Wiring
Be careful, wiring must be sealed. Incoming air, even slight, would seriously jam the
temperature, humidity and air quality measures.
When the switchboard is located in the heated volume: caulk arrivals between cables
and ducts at the switchboard level.
When the switchboard is out of the heated volume, caulk between cables and ducts
before entering the heated volume. A sealing plug must also be placed between
duct and cable reaching the EP5000 probe to prevent air entry.
When the sealing of the duct is not possible, use a specific sealant without silicone
and VOC.
In case of use of electrical backbox, select an airtight case with sealing membrane
from which the duct passes through. If the case crosses through the sealing plane
(plasterboard), seal between the casing and panel with a special sealant without
silicone and VOC.
Connectors are specified for rigid cable 18 to 24 AWG (1 to 0.5mm dia.) or
twisted 20 to 22 AWG (0.8 to 0.65mm dia.)
The connectors accept two 0.8mm cables on the same terminal in order to chain
several sensors. Beware of line losses, a 0.8mm cable has a resistance of 21Ω
per Km.
5. Installation
It is recommended to install the probe at the end of the work (after painting and using
silicone-based products).
Connect the ModBus and the 24V DC Power Supply pair cables on the terminal
block on the back of the product. Pay attention to marking: Modbus A & B and
power supply polarity.
Just push the stripped ends (flexible or rigid) into the connector. In case of a multi-
strand cable, make sure to well twist them before inserting them. In case of
difficulty, push the release tab. Respect the polarity (non-destructive).
Make sure to respect the Up marking otherwise the temperature and humidity
measurement will be jammed.
Screw the plate on the backbox.
Plug the front panel onto the plate. Pay attention to the position of the connector in
the back of the front plate.
If well mounted, the transparent window of the light sensor shall be on top middle.
Ø 67/68