44
The data inside this manual are not binding and they can be modified by the manufacturer without notice.
All rights reserved.
NPC 280 - 400
ACF2
- Unit configured for the
ON/OFF or proportional
control of the
condensation without the
configuration of the
related probe (one probe
per circuit if separate
condensation, at least one
probe if single
condensation).
- If one of the following
rules is not respected in
the event of proportional
regulation:
(FA09
+
FA11
+
FA12
<
FA
10)
(**)
(FA12
<
FA13)
(**)
(FA07
<
FA15
<
FA08)
(**
)
- If one of the following
rules is not respected
when the proportional
regulation with pump is
enabled:
(FA18
+
FA21
+
FA20
<
FA
19)
(**)
(FA21
<
FA22)
(**)
(FA16
<
FA23
<
FA17)
(**
)
- If one of the following
rules is not respected in
the event of ON-OFF
regulation:
(FA09
<
FA10)
(**)
- If one of the following
rules is not respected
when the ON-OFF
regulation with pump is
enabled:
(FA18
<
FA19)
(**)
- If a condensation/
evaporation probe per
circuit is not present
when the pump and
defrost are enabled.
- When triac regulation is
enabled (
CF68
,
CF69
=2)
(**) and the continuous
power supply has been
selected (
CF83
=0)(**).
Incorrect programming
Correct programming
Auto.
E
Flashing
Alarm relay +
buzzer enabled.
ACF3
Two digital/analogue
inputs configured with
the same function or
without the necessary
resources (eg.
compressor 3 relay
configured but not
compressor 3)
Incorrect programming
Correct programming
Auto.
E
Flashing
Alarm relay +
buzzer enabled
ACF4 CF79
(*) and the non-
configured input or
CF79
(*) NTC probe not
configured as external air
temperature
Incorrect programming
Correct programming
Auto.
E
Flashing
Alarm relay +
buzzer enabled.
ACF5
If circuit 2 has been
configured and the
resources have been
configured (relay:
solenoid pump-down,
heaters, inversion valve,
condensing fan ON -
OFF, recovery, auxiliary)
Incorrect programming
Correct programming
Auto.
E
Flashing
Alarm relay +
buzzer enabled.
Code
Meaning
Cause
Reset
Restart
Icon
Action