ALTERNATOR SAFETY RULES
DANGER !
During operation, do not stand in front of the air outlet
guards, in case anything is ejected from them. Do not
allow bystanders or children to stay near the air inlet &
outlet guards.
HANDLING
CAUTION !
The alternator is coming already fitted onto the engine.
The following applies only when alternator has to be
removed for major service.
Fat-sized lifting eyes are for handling the alternator
only. They must not be used to lift the genset. The
choice of lifting hooks or handles should be determined
by the shape of the lifting eyes. Choose a lifting system
in accordance with the integrity and the environment of
the machine.
CAUTION !
Because of the alternator offset center of gravity, keep
the sling horizontal. Do not allow anyone to stand under
the load during operation.
CONNECTIONS CHECKS
CAUTION !
Electrical installations must comply with the current
legislation in force in the country of use. Check that :
- The residual circuit-breaker conforms to legislation on
protection of personnel, in force in the country of use,
and has been correctly installed on the alternator power
output as close as possible to the alternator. (In this
case, disconnect the wire of the interference suppression
module linking the neutral).
- Protection devices in place are on trip position.
- If there is an external AVR, the connections between
the alternator and the cabinet are made in accordance
with the connection picture.
- There is no short-circuit phase-phase or phase-
neutral between the alternator output terminals and
the generator set control cabinet (part of the circuit not
protected by circuitbreakers or relays in the cabinet).
- The machine should be connected with the busbar
separating the terminals as shown in the terminal
connection picture.
- The alternator earth terminal inside the terminal box is
connected to the electrical earth circuit.
- The earth terminal is connected to the frame. The
connections inside the terminal box must never be
subjected to stress due to cables connected by the user.
HOW TO SECURE CABLES
Thightening torque for M10 bolts is : 20 Nm +/-3.
S09
ALTERNATOR
Содержание QLS 65T
Страница 1: ...GENSETS NANNI USER MANUAL Ref DGBXXT09047 MODEL QLS 65T ...
Страница 2: ......
Страница 4: ......
Страница 34: ...34 S06 COMPONENTS ENGINE VIEWS QLS65T 14 1 5 6 4 9 4 10 8 7 9 13 12 ...
Страница 35: ...35 S06 COMPONENTS ENGINE VIEWS QLS65T 2 9 10 11 1 12 ...
Страница 62: ...62 ENGINE ELECTRICAL WIRING S08 MAINTENANCE ...
Страница 63: ...63 S08 MAINTENANCE ...
Страница 72: ...72 Electrical faults S09 ALTERNATOR ...
Страница 79: ......