–300 to 900  

 

–312 to 1000  

 

–312 to 1000  

 

DC current and voltage inputs 

If the PV exceeds Indication range high limit value, the PV display blinks “

”, and   

if the PV exceeds the Indication range low limit value, the PV display blinks “

”. 

Indication ran

: [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value 

ge 

 

+ Scaling span x 10%] 

 

However, if the input value exceeds the range –1999 to 9999, the PV   

 

display blinks “

” or “

”. 

Control range 

: [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value 

u

 

+ Scaling span x 10%] 

DC input burno t 

: When DC input is burnt out, PV display blinks “

” for 4 to 20mA DC   

 

and 1 to 5V DC inputs, and “

” for 0 to 1V DC input. 

 

For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC inputs, the PV display   

 

indicates the corresponding value for which 0mA or 1V is inputted. 

[Burnout] 

When the thermocouple or RTD input is burnt out, OUT is turned off and PV display blinks 

” (for DC current output type, OUT low limit value). 

Accessories included

: Instruction manual 1 copy 

When the option Heater burnout alarm is added: Wire harness 3m, 1 length 
When the option Heater burnout alarm is added: 

For rating 5A, 10A, 20A     

CT (AKT4815) 

1 piece 

For rating 50A   

  CT (AKT4816)  1 piece 

Accessories sold separately

: For DC current input, 50  shunt 

resistor 

(AKT4811)  1 

piece 

 

10.2 Optional specifications 

Heater burnout alarm 

Watches the heater current with CT (Current transformer) and detects the burnout. 
When this option is added, this option shares common output with Alarm output and Loop break alarm. 
This option cannot be applied to DC current output type. 
Rating 

: 5A, 10A, 20A, 50A (Must be specified) 

Setting range 

: 5A, 0.0 to 5.0A (Off when set to 0.0) 

                 10A, 

0.0 

to 

10.0A 

(Off 

when 

set 

to 

0.0) 

                20A, 

0.0 

to 

20.0A 

(Off 

when 

set 

to 

0.0) 

                50A, 

0.0 

to 

50.0A 

(Off 

when 

set 

to 

0.0) 

Setting accuracy :

 

5% of the rated value 

Action   

: ON/OFF action 

Output 

: Open collector 

 

 

Control capacity, 24V DC    0.1A (Max.) 

11. Troubleshooting 

If any malfunctions occur, refer to the following items after checking the power supply to the controller. 

11.1 Indication 

Problem 

Presumed cause and solution 

” is blinking on the PV 

display. 

• 

Sensor (Thermocouple, RTD and DC voltage 0 to 1V DC 

  input) is burnt out. 

Change the sensor for new one. 

• 

Is the lead wire of the sensor (Thermocouple, RTD and DC 

voltage 0 to 1V DC input ) securely connected? 

  Connect it to the input terminal properly. 

The indication on the PV display 
does not change. 

• 

Check if the input signal source for DC voltage (0 to 10V DC)

  and DC current (0 to 20mA DC) is normal. 

• 

Is the input signal wire for the DC current (0 to 20mA DC) 

  and DC voltage 0 to 10V DC securely connected to the input

terminal of this controller? 

Connect the sensor lead wire securely to the input terminal 

of this controller. 

” is blinking on the PV 

display. 

• 

Check if the input signal source for sensor (DC current 

“4 to 20mA DC” and DC voltage “1 to 5V DC” input) is 
normal. 

• 

Is the input signal wire of DC current 4 to 20mA DC and 

  DC voltage1 to 5V DC securely connected to the terminal 

Содержание KT7

Страница 1: ...ed according to the specifications described in this manual If it is not used according to the specifications it may malfunction or cause fire Be sure to follow the warnings cautions and notice If not...

Страница 2: ...rease key Decreases the numeric value 8 Mode key Selects the setting mode or registers the setting value By pressing the Mode key the setting value can be registered 9 Sub mode key Brings up Auxiliary...

Страница 3: ...contact with the controller...

Страница 4: ...n DIN rail is mounted vertically be sure to use commercially available fastening plates at the end of KT7 series Mount the KT7 series to the DIN rail so that the KT7 series cannot move However if the...

Страница 5: ...nal screw with the specified torque If not it may damage the terminal screw and deform the case Use thermocouple and compensating lead wire that fit sensor input specification of this unit Use the 3 w...

Страница 6: ...ned on the sensor input characters and temperature unit are indicated on the PV display and the input range high limit value is indicated on the SV display for approx 3 seconds Table 5 1 If any other...

Страница 7: ...500 0 199 9 to 900 0 0 1 JPt100 200 to 500 300 to 900 1 4 to 20mA DC 1999 to 9999 1 2 1 0 to 20mA DC 1999 to 9999 1 2 1 0 to 1V DC 1999 to 9999 1 1 0 to 5V DC 1999 to 9999 1 1 1 to 5V DC 1999 to 9999...

Страница 8: ...e time setting Decimal point place selection ARW setting PV filter time constant setting OUT proportional cycle setting OUT high limit setting Manual reset setting OUT low limit setting Alarm setting...

Страница 9: ...d Approx 3s Press the for 3 seconds while the key is being pressed Approx 3s Press the for 3 seconds while the key is being pressed When setting a value or selecting an item in the setting modes use t...

Страница 10: ...tting the value to 0 disables the function This setting item is not indicated for ON OFF action Setting range 0 to 300 seconds 50 seconds Anti reset windup setting Sets anti reset windup Available onl...

Страница 11: ...larm action type Setting range High limit alarm Scaling span to scaling span Low limit alarm Scaling span to scaling span High Low limits alarm 0 to scaling span High Low limit range alarm 0 to scalin...

Страница 12: ...to 20mA 1999 to 9999 0 to 20mA 1999 to 9999 0 to 1V 1999 to 9999 0 to 5V 1999 to 9999 1 to 5V 1999 to 9999 0 to 10V 1999 to 9999 Scaling high limit setting Sets the scaling high limit value Setting ra...

Страница 13: ...Not available if No alarm action is selected in the Alarm action selection Energized Deenergized Energized Alarm HOLD function selection Selects whether alarm HOLD function is Used or Not used If ala...

Страница 14: ...ue In such a case the control can be set at the desired temperature by adjusting the input value of sensors Loop break alarm The alarm will be activated when the process variable PV does not rise to t...

Страница 15: ......

Страница 16: ...sensor type from Input type selection 5 Set the high limit of the value that is going to be converted during Scaling high limit setting 6 Set the low limit of the value that is going to be converted d...

Страница 17: ...DC Cycle action is performed according to deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Changes continuously according to deviation Unlit...

Страница 18: ...g side side side side SV setting A1 setting point A1 setting point A1 setting point SV setting A1 setting point SV setting A1 setting point A1 setting point A1 setting point SV setting A1 setting poin...

Страница 19: ...tant PID contatnt calculated Controlled by the PID constant set by auto tuning AT bias value 1 2 3 4 2 When the control is stable Fluctuation is applied at the setting value Temp Time AT 1 2 3 AT Auto...

Страница 20: ...Within 6 12 B input 0 to 300 0 to 600 Accuracy is not guaranteed K J E N input less than 0 32 Within 0 4 of input span 1 digit RTD Within 0 1 of input span 1 digit or within 1 2 whichever is greater D...

Страница 21: ...ical life 100 000 times Non contact voltage for SSR drive 12 V DC Max 40mA Short circuit protected DC current 4 to 20mA DC Load resistance Max 550 Output accuracy Within 0 3 of output span Resolution...

Страница 22: ...ed Deenergized can be selected Energized Deenergized Red EVT LED Lights Lights EVT output ON OFF Alarm HOLD function selection Once the alarm is activated alarm output is held until the power is turne...

Страница 23: ...OFF for DC current output type OUT low limit value However for manual control it outputs the preset manipulated variable Input Input range Indication range Control range 199 9 to 400 0 199 9 to 450 0...

Страница 24: ...s the burnout When this option is added this option shares common output with Alarm output and Loop break alarm This option cannot be applied to DC current output type Rating 5A 10A 20A 50A Must be sp...

Страница 25: ...ured object is indicated on the PV display Internal memory is defective Contact our agency or us 11 2 Key operation Problem Presumed cause and solution Setting values do not change even if the or key...

Страница 26: ...Matsushita Electric Works Ltd Tatsuno Matsushita Electric Works Ltd Mail address 300 Katayama Tatsuno cho Tatsuno city Hyogo pref Japan Telephone 81 791 63 0511 No KT71E1 2002 03...

Отзывы: