background image

IOM-TBN

Date: 12-2021 

Supersedes: NEW

Page 4 of 6

TBN BACnet Thermostat 

 General Configuration

To enter the Configuration submenu:

1. Hold the 

Menu

 button for five seconds.

The password field appears.
2. Use the down arrow key to decrease the display number until 

it matches the configured password.

By default, the password is 9995.
3. Press the 

Menu

 button to submit the password.

4. Once the password is accepted, press the 

Menu

 button again 

and SETPOINT will appear on the screen.

5.  Press  the  up  or  down  arrow  key  and  the  Bypass  Time  will 

appear. The default setting is 60 minutes. To change the default 

setting, use the arrow keys.

6. Press the 

Menu

 button again and the Setpoint Low Limit will 

appear. The default setting is 64

°

F. To change the default setting, 

use the arrow keys.

Nailor reserves the right to change any information concerning product or specification without notice or obligation.

Advanced 

Menu

and 

-

 Enters Advanced Menu, when held for 5 sec

- Navigates between parameters

- Submits a modified parameter

- Goes up one level, when held for 5 sec

- Cancels a modified parameter, when held for 5 sec

- Modifies a parameter

- Goes up one level when pressed in Exit screen

- Releases an override when both are pressed

- Enters into a submenu

Button Navigation Guide:

How to enter the Configuration submenu

7. Press the 

Menu

 button again and the Setpoint High Limit will 

appear. The default setting is 74

°

F. To change the default setting, 

use the arrow keys.

8. Press the 

Menu

 button again an Reheat Config will appear. The 

default setting is No Heat. To change the default setting, use the 

arrow keys.

9. Press the 

Menu

 button again and Min Position Heat will appear 

only if 1 or 2 stage heating or 0-10/2-10 volts was selected on 

the previous screen. The default setting is 10%. Use the arrow 

keys to change the default setting. This screen will be skipped if 

no reheat is selected and the next screen to appear will be Min 

Damper Position.

10.  Press  the 

Menu

  button  again  and  the  Minimum  Damper 

Position will appear. The default setting is 100%. To change the 

default setting, use the arrow keys.

11.  Press  the 

Menu

  button  again  and  the  Maximum  Damper 

Position will appear. The default setting is 100%. To change the 

default setting, use the arrow keys.

12. Press the 

Menu

 button again and the Unoccupied Damper 

Position will appear. The default setting is 10%. To change the 

default setting, use the arrow keys.

Screen timeout: none

Screen timeout: 15 sec

Screen timeout: 15 sec

Screen timeout: 30 sec

Screen timeout: 30 sec

Screen timeout: 30 sec

Screen timeout: 30 sec

Screen timeout: 30 sec

Screen timeout: 30 sec

Screen timeout: 30 sec

Screen timeout: 30 sec