TBN BACnet Thermostat
•
General Configuration
To enter the Configuration submenu:
1. Hold the
Menu
button for five seconds.
The password field appears.
2. Use the down arrow key to decrease the display number until
it matches the configured password.
By default, the password is 9995.
3. Press the
Menu
button to submit the password.
4. Once the password is accepted, press the
Menu
button again
and SETPOINT will appear on the screen.
5. Press the up or down arrow key and the Bypass Time will
appear. The default setting is 60 minutes. To change the default
setting, use the arrow keys.
6. Press the
Menu
button again and the Setpoint Low Limit will
appear. The default setting is 64
°
F. To change the default setting,
use the arrow keys.
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Advanced
Menu
and
-
Enters Advanced Menu, when held for 5 sec
- Navigates between parameters
- Submits a modified parameter
- Goes up one level, when held for 5 sec
- Cancels a modified parameter, when held for 5 sec
- Modifies a parameter
- Goes up one level when pressed in Exit screen
- Releases an override when both are pressed
- Enters into a submenu
Button Navigation Guide:
How to enter the Configuration submenu
7. Press the
Menu
button again and the Setpoint High Limit will
appear. The default setting is 74
°
F. To change the default setting,
use the arrow keys.
8. Press the
Menu
button again an Reheat Config will appear. The
default setting is No Heat. To change the default setting, use the
arrow keys.
9. Press the
Menu
button again and Min Position Heat will appear
only if 1 or 2 stage heating or 0-10/2-10 volts was selected on
the previous screen. The default setting is 10%. Use the arrow
keys to change the default setting. This screen will be skipped if
no reheat is selected and the next screen to appear will be Min
Damper Position.
10. Press the
Menu
button again and the Minimum Damper
Position will appear. The default setting is 100%. To change the
default setting, use the arrow keys.
11. Press the
Menu
button again and the Maximum Damper
Position will appear. The default setting is 100%. To change the
default setting, use the arrow keys.
12. Press the
Menu
button again and the Unoccupied Damper
Position will appear. The default setting is 10%. To change the
default setting, use the arrow keys.