IOM-EZVAVINST
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Page 21 of 48
Installation and Operation Manual
●
EZvav Digital Controls
Procedure to set the airflow set points (continue)
Advanced Options
The advanced options set up passwords and special features in the controller.
•
Establish or change Password 1 and Password 2
•
Set timers for standby and override (optional)
•
Enable automatic occupancy (optional)
•
Enable discharge air temperature control (optional)
•
Calibrate the sensor
Setting the advance options requires entering Password 2 which is described in the topic Getting started with configuration on
page 14.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure to set the advanced options
PROCEDURE
STEPS
STE DISPLAY
9
Set the maximum limit for fan
speed.
Not used for all models.
1. Press the
∆
or buttons to set the maximum limit
for the fan speed. The set point will change in 1%
increments.
2. Press the button to save the set point and
advance to the next function.
10
Set the dual duct minimum
airflow.
Not used for all models.
1. This set point is for the minimum airflow when a Dual
duct system is at temperature set point.
1. Press the
∆
or buttons.
2. Press the button to save the set point and
advance to the next function.
11
Select a new configuration
function or exit.
1. Press the
∆
or buttons to select one of the
following:
•
STPT
,
BOX
,
ADVC
, or
RSTR
options
•
BACK
to choose another configuration function
EXIT
.
2. Press the button to select the next function.
∆
∆
PROCEDURE
STEPS
STE DISPLAY
1
Starting display
1. Start at the temperature display.
2. Press the
∆
and buttons together.
• If Password 2 is not required, the display changes
to
CNFG
.
• If required, enter Password 2. The display changes
to
CNFG
when Password 2 is correct.
∆
∆