Procedure to set the Terminal Unit functions (continue)
PROCEDURE
STEPS
STE DISPLAY
2
Select the box settings display.
1. From the
CNFG
display, press the
∆
or buttons
to show the
BOX
display.
2. Press the button to select the
CNFG
options.
The display changes to
STPT
.
3. Press the
∆
or buttons to change the display to
BOX
.
4. Press the button to select
BOX
.
3
Set the primary VAV terminal unit
K factor.
Refer to the K-factor label on the controls enclosure
door of the terminal unit for appropriate value. You can
also refer to page 43, visit www.nailor.com or contact
your local Nailor Representative for more details.
1. Press the
∆
or buttons to set the primary K-factor.
2. Press the button to save the entry and advance to
the next function.
4
Set the secondary VAV terminal
unit K factor.
Not used in all models.
1. Press the
∆
or buttons to set the secondary
K-factor.
2. Press the button to save the entry and advance to
the next function.
5
Set the mode of reheat for the
terminal unit.
Not used in all models.
1. Press the
∆
or buttons to choose one of the
following reheat options.
None
—Reheat is not enabled.
Staged
—Enables staged reheat.
Modulating
—The analog reheat output varies from
0—10 volts DC.
Floating
—The reheat outputs control a tristate
actuator.
2. Press the button to save the reheat option and
advance to the next function.
6
Set the fan option.
Not used in all models.
1. Press the
∆
or buttons to choose one of the
following fan options.
None
—No fan is connected to the controller.
•
Models: 3001, 30RE and 30RW, 3600
Series
—The VAV unit includes a series fan.
•
Model Series: 35S(ST), 35SE(ST), 35SW(ST),
37S(ST), 37SE(ST) and 37SW(ST), 38S/SE/SW
Parallel
—The VAV unit includes a parallel fan.
•
Models: 35N, 37N, 35NE, 35NW, 37NE and 37NW
2. Press the button to save the fan option and
advance to the next function.
∆
∆
∆
∆
∆
∆