16

Cabling Audio Systems

1)

Cabling should be Star Configuration (Topology). ie. Each Handset cable should go back
to a junction box or central cabinet and NOT looped from one Handset to the next. This is
purely for maintenance reasons.

2)

It is recommended that 1mm diameter conductors are used from the power supply to the
(+) POSITIVE and (-) NEGATIVE of the speaker unit.

3)

It is recommended that 1mm (preferably 1.5mm) diameter conductors are used for the
lock circuit.

4)

Standard BT telephone cable is recommended (0.4mm per conductor) for reasons of
higher quality audio reproduction and because the pairs are twisted thereby providing a
powerful defence against interference.

5)

Standard alarm cable can also be used although there is a greater risk of interference.
Special care must be taken to ensure clean and neat terminations.

6)

All low voltage cabling must be run totally separated from high/mains voltage cables.

Please note that far better results are achieved using thicker conductors than combinations of
thinner conductors.

Power

Power the MIHP/6 Speaker using a 12V DC power source.

Amperage draw is dependent upon consumption characteristics of the locking used, the lengths of cable runs, the number of
handsets required to switch on simultaneously etc. As a general guide, allow 1 Amp per door. If unsure, please contact Noralsy.

Standby for Audio Systems

Simply add 12V battery to 12V DC power supply.

General Wire Diameter Guidlines – per conductor

Distance

Call/Speech/Release

Metres

CA, 2, 1, 9, 6

mm

50

0.4

100

0.8

200

1.0

300

1.6

For greater distances, please contact Noralsy for advice.

1 2 3

1

2

4

5

6

3

1

2

3

1

2

4

3

1

2

3

1
2

4
5

3

1
2
3

1

2

3

View Side-On

PCB Facing Up

View Side-On

PCB Facing Up

View Side-On

PCB Facing Up

View Side-On

PCB Facing Up

1 2

1 2 3

1 2

4

3

1 2

4 5

3

1 2

4 5 6

3

1 2

4 5 6 7

3

1 2

4 5 6 7 8

3

Direction of View

1 2

1 2

4 5 6

3

Any Noralsy

Control Unit

Door Controller

Speaker Unit

Access Pass Reader/Receiver

Keypad

Call Decoder

Module

Standardisation of
Terminal Numbering

Place Noralsy unit on a flat surface with
PCB facing skywards. View terminal blocks
from the outside looking in. Terminal No. 1
is always the first on the left of every
terminal block strip.

General Information

Our policy is one of continuous product improvement, we reserve the right to change specifications and prices without notice. All information is given in good faith. No responsibility can be accepted for errors, omissions or
incorrect assumptions. Picture reproduction of products are within the limitations of both colour and black and white printing and are intended as a guide only.

Star
Topology

N.A.C.D. LIMITED

UNIT 10, AVEBURY COURT, MARK ROAD, HEMEL HEMPSTEAD, HERTS HP2 7TA     

TEL:

01442 211848

FAX:

01442 212776

EMAIL:

[email protected]

WEB:

http//:www.nacd.co.uk

NORALSY

MASTERING ACCESS CONTROL

Содержание Noralsy MIHP/6

Страница 1: ...ure please contact Noralsy Standby for Audio Systems Simply add 12V battery to 12V DC power supply General Wire Diameter Guidlines per conductor Distance Call Speech Release Metres CA 2 1 9 6 mm 50 0 4 100 0 8 200 1 0 300 1 6 For greater distances please contact Noralsy for advice 1 2 3 1 2 4 5 6 3 1 2 3 1 2 4 3 1 2 3 1 2 4 5 3 1 2 3 1 2 3 View Side On PCB Facing Up View Side On PCB Facing Up View...

Страница 2: ...r INSTALLATION INSTRUCTIONS MIHP 6 SPEAKER Audio Entry Single Entrance Multiple Entrances with Automatic Switching With Fail Secure Locking Fail Safe Locking Automation Keypad Access Control NORALSY MASTERING ACCESS CONTROL ...

Страница 3: ... with a Keypad Fail Safe Locking 10 Volt Free Automation 11 Interfacing with a Keypad Volt Free Automation 11 Interfacing with Access Control Fail Secure 12 Interfacing with Access Control Fail Safe 12 Interfacing with Access Control Volt Free Automation 12 Programming instructions for 30 Code 1 Relay Keypad 13 Programming instructions for 30 Code 3 Relay Keypad 14 15 Cabling Specifications 16 2 A...

Страница 4: ...1 provides a normally closed contact once the keypad is secured to the wall AUTOMATIC TIME OUT whenever programming accessed via Master Code If you do not press B or to escape from programming the keypad will automatically revert to normal mode after 20 seconds 30 7 7767110 Length of Code Slot No Master Code Itself 01 6 700028 Length of Code Slot No User Code 17 A or Slot No Delete Command 01 A or...

Страница 5: ...e for relay no 2 even if you are not using relay no 2 If you have linked relays 1 2 together you must set the same open times for both STEP 2 Now set the Master Code of your choice This is the code that allows you to access programming mode without having to open up the keypad and flicking switch SW5 The Master Code is always stored in Slot 30 The Master Code can be any length of digits characters...

Страница 6: ...sting speech sound level down to the external panel P3 For adjusting speech sound level up to the handset s Speech Audio Settings ELEC INST 300 1 Turn P3 clockwise to zero No speech from panel to handset 2 Adjust P2 clockwise so that speech level at panel is at an acceptable level Do not increase beyond this point 3 Adjust P3 fractionally anti clockwise to turn on microphone J4 Prewired connected ...

Страница 7: ...electro magnet or electric release EMEX POWER SUPPLY 12v 0v Magnet or Fail Safe Release 1 2 J3 Varistor If your fail safe locking requires an Emergency Break Glass exit device ref EMEX normally closed contact in order to comply with relevant fire and safety regulations please fit as shown J3 1 2 J9 INV NOR J3 J9 1 2 INV NOR Fail Secure N O Fail Safe N C Jumper Settings J9 for Relay J3 ELEC INST 30...

Страница 8: ...After a beep enter on the keypad 01 3 A94 Slot Number Length of Code Code Itself 02 6 564B52 Slot Number Length of Code Code Itself NOTE CAREFULLY No codes into slot no 06 as this is for the Master Code Unless of course you want to change the Master Code Press B to escape from programming DELETING USER DOOR ENTRY CODES As all door entry codes are stored in slot numbers 01 05 and 07 30 it is easy t...

Страница 9: ... Set output time on speaker MIHP 6 via potentiometer P1 to slightly above minimum and program output time on ECP Door Controller to 01 seconds Program output time accordingly if more time is required to trigger automation system Relay J3 used as a N O Volt Free change over relay to trigger relay lock output of ECP Door Controller Door Controller Control Unit from 3rd party via standard internal ex...

Страница 10: ...9 Call Button 5 Call Button 4 Call Button 3 Call Button 2 Call Button 1 Speaker MIHP 6 Handset 2 Handset 1 Handset 3 Handset 4 Handset 5 To Handset 3 4 5 etc ie Terminal 1 of Handset ie Terminal CA of Handset 6 2 1 CA CA CA 12V Electric Release Varistor EX1 1 2 1 2 1 2 3 4 5 EX1 Door release button sited internally Normally open contact RS Release Signal INV NOR JUMPER SETTING For fail safe lockin...

Страница 11: ...6 Noralsy Speaker MIHP 6 Audio Entry 2 Entrances Automatic Switching ELEC INST 303 ...

Страница 12: ...em J1 J2 J3 Speaker MIHP 6 KEYPAD MODULE 30 Codes 1 Relay 1 2 3 4 5 6 J1 SW1 KEYPAD INV NOR INV NOR BUZZER JUMPER SETTING Common NOR 1 2 1 2 1 2 3 4 5 JUMPER SETTING Common NOR 12VDC 0V To Automation Control Set output time on speaker MIHP 6 via potentiometer P1 to slightly above minimum and program output time on keypad to 0 2 seconds Program keypad output time accordingly if more time is require...

Страница 13: ...SETTING J9 Common NOR P1 P3 P2 Fail Secure Locking MIHP 6 Speaker Audio System Keypad ELEC INST 305 ELEC INST 306 POWER SUPPLY 12V DC 1AMP KEYPAD MODULE 30 Codes 1 Relay 12v 0v L E N J1 J2 J3 12V DC Magnet or Fail Safe Release Varistor EX1 Speaker MIHP 6 1 2 3 4 5 6 J1 SW1 KEYPAD INV NOR BUZZER JUMPER SETTING Common INV JUMPER SETTING J9 Common NOR 1 2 1 2 1 2 3 4 5 EX1 Door release button sited i...

Страница 14: ...7 Noralsy Speaker MIHP 6 Audio Entry 3 or 4 Entrances Automatic Switching ELEC INST 304 NORALSY MASTERING ACCESS CONTROL ...

Страница 15: ...1 3 2 1 4 5 2 1 2 1 3 2 1 J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 6 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 5 3 2 1 Call Buttons MIHP 6 Panel 4 Call Buttons SU SD RS SU SD RS SU SD RS 6 3 9 12 0 SN2 4 1 7 SN1 5 2 11 8 C1 C2 6 3 9 12 0 SN2 4 1 7 SN1 6 3 9 12 DIP E 12 0 0 C1 C2 12 0 SN2 788 8 788 1 788 1 788 1 SU SD RS SU SD RS CALL LINE 2 CALL LINE 1 CALL LINE 3 CALL LINE 3 CALL ...

Страница 16: ...ttons SU SD RS 3 2 1 J3 J2 J1 3 2 1 4 5 2 1 2 1 3 2 1 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 7 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 6 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 5 3 2 1 Call Buttons MIHP 6 Panel 4 Call Buttons SU SD RS SU SD RS SU SD RS SU SD RS SU SD RS 6 3 9 12 0 SN2 4 1 7 SN1 5 2 11 8 C1 C2 6 3 9 SN2 4 1 7 SN1 5 2 11 8 C1...

Отзывы: