TOP POINTS TO REMEMBER

Master ( Engineer) Code is always stored in Slot 30.

User Codes are stored in Slots 01, 02, 03, 04..........26.

Relay no. 1 is controlled by the User Codes stored in Slots 01 - 13.

Relay no. 2 is controlled by the User Codes stored in Slots 14 - 26.

The code stored in Slot Number 27 activates Relay no. 1 & Relay no. 2 simultaneously.

The code stored in Slot Number 28 turns Latching Relay no. 3 “ON”.

The code stored in Slot Number 29 turns Latching Relay no. 3 “OFF”.

TIP - WHEN YOU ARE IN PROGRAMMING

Enter the numbers in quick succession after a beep. Do not wait more than 2-3 seconds in between entering numbers. If you have
correctly programmed, you will hear a rapid series of beeps.

SET-UP ON INSTALLATION

Wire up according to appropriate electrical schematic for your installation, then power up the keypad. Flick Programming Switch SW5
and wait for the keypad to start beeping every 3 seconds.

STEP 1

Decide Now......for how many seconds do you want the door to open:

After a beep enter

The 2no. digits shown as underlined set the door open time in seconds for relay no.1. The last 2no. digits set the door open time for
relay no.2. A rapid series of beeps indicates that you have programmed successfully.

You must set the relay/lock command time for relay no. 2 even if you are not using relay no. 2. If you have linked relays 1 &
2 together, you must set the same open times for both.

STEP 2

Now set the Master Code of your choice.

This is the code that allows you to access programming mode
without having to open up the keypad and flicking switch SW5.

The Master Code is always stored in Slot 30.

The Master Code can be any length of digits/characters/symbols -
minimum 3, maximum 8.

After a beep enter on the keypad:

if you want your Master Code to be 2901

A rapid series of beeps indicates that you have programmed successfully.

STEP 3

Turn off programming switch SW5.

STEP 4

PROGRAMMING/ADDING USER CODES

User codes can be any length of digits/characters/symbols - minimum 3, maximum 8.

User codes are stored in Slots 01-26. Example: 01, 02, 03… 26.

Enter the Master Code you set in STEP 2 and wait for the beeps.

After a beep enter on the keypad:

..............to program User Code 494 into Slot 01

A rapid series of beeps indicates that you have programmed successfully.

.............to program User Code 5519 into Slot 02

A rapid series of beeps indicates that you have programmed successfully.

Now press B or # to escape from programming.

02 4 5519

Length of Code

Slot No.

User Code

01 3 494

Length of Code

Slot No.

User Code

30 4 2901

Length of Code

Slot No.

Master Code
Itself

00 05 05

Relay No. 1

Set Timer

Command

Relay No. 2

05

Example

Seconds

This is an example only.
SET THE MASTER CODE OF
YOUR CHOICE

NOTE:
Relays can be programmed
between 01 – 99 seconds.

Содержание Noralsy MIHP/6

Страница 1: ...ure please contact Noralsy Standby for Audio Systems Simply add 12V battery to 12V DC power supply General Wire Diameter Guidlines per conductor Distance Call Speech Release Metres CA 2 1 9 6 mm 50 0 4 100 0 8 200 1 0 300 1 6 For greater distances please contact Noralsy for advice 1 2 3 1 2 4 5 6 3 1 2 3 1 2 4 3 1 2 3 1 2 4 5 3 1 2 3 1 2 3 View Side On PCB Facing Up View Side On PCB Facing Up View...

Страница 2: ...r INSTALLATION INSTRUCTIONS MIHP 6 SPEAKER Audio Entry Single Entrance Multiple Entrances with Automatic Switching With Fail Secure Locking Fail Safe Locking Automation Keypad Access Control NORALSY MASTERING ACCESS CONTROL ...

Страница 3: ... with a Keypad Fail Safe Locking 10 Volt Free Automation 11 Interfacing with a Keypad Volt Free Automation 11 Interfacing with Access Control Fail Secure 12 Interfacing with Access Control Fail Safe 12 Interfacing with Access Control Volt Free Automation 12 Programming instructions for 30 Code 1 Relay Keypad 13 Programming instructions for 30 Code 3 Relay Keypad 14 15 Cabling Specifications 16 2 A...

Страница 4: ...1 provides a normally closed contact once the keypad is secured to the wall AUTOMATIC TIME OUT whenever programming accessed via Master Code If you do not press B or to escape from programming the keypad will automatically revert to normal mode after 20 seconds 30 7 7767110 Length of Code Slot No Master Code Itself 01 6 700028 Length of Code Slot No User Code 17 A or Slot No Delete Command 01 A or...

Страница 5: ...e for relay no 2 even if you are not using relay no 2 If you have linked relays 1 2 together you must set the same open times for both STEP 2 Now set the Master Code of your choice This is the code that allows you to access programming mode without having to open up the keypad and flicking switch SW5 The Master Code is always stored in Slot 30 The Master Code can be any length of digits characters...

Страница 6: ...sting speech sound level down to the external panel P3 For adjusting speech sound level up to the handset s Speech Audio Settings ELEC INST 300 1 Turn P3 clockwise to zero No speech from panel to handset 2 Adjust P2 clockwise so that speech level at panel is at an acceptable level Do not increase beyond this point 3 Adjust P3 fractionally anti clockwise to turn on microphone J4 Prewired connected ...

Страница 7: ...electro magnet or electric release EMEX POWER SUPPLY 12v 0v Magnet or Fail Safe Release 1 2 J3 Varistor If your fail safe locking requires an Emergency Break Glass exit device ref EMEX normally closed contact in order to comply with relevant fire and safety regulations please fit as shown J3 1 2 J9 INV NOR J3 J9 1 2 INV NOR Fail Secure N O Fail Safe N C Jumper Settings J9 for Relay J3 ELEC INST 30...

Страница 8: ...After a beep enter on the keypad 01 3 A94 Slot Number Length of Code Code Itself 02 6 564B52 Slot Number Length of Code Code Itself NOTE CAREFULLY No codes into slot no 06 as this is for the Master Code Unless of course you want to change the Master Code Press B to escape from programming DELETING USER DOOR ENTRY CODES As all door entry codes are stored in slot numbers 01 05 and 07 30 it is easy t...

Страница 9: ... Set output time on speaker MIHP 6 via potentiometer P1 to slightly above minimum and program output time on ECP Door Controller to 01 seconds Program output time accordingly if more time is required to trigger automation system Relay J3 used as a N O Volt Free change over relay to trigger relay lock output of ECP Door Controller Door Controller Control Unit from 3rd party via standard internal ex...

Страница 10: ...9 Call Button 5 Call Button 4 Call Button 3 Call Button 2 Call Button 1 Speaker MIHP 6 Handset 2 Handset 1 Handset 3 Handset 4 Handset 5 To Handset 3 4 5 etc ie Terminal 1 of Handset ie Terminal CA of Handset 6 2 1 CA CA CA 12V Electric Release Varistor EX1 1 2 1 2 1 2 3 4 5 EX1 Door release button sited internally Normally open contact RS Release Signal INV NOR JUMPER SETTING For fail safe lockin...

Страница 11: ...6 Noralsy Speaker MIHP 6 Audio Entry 2 Entrances Automatic Switching ELEC INST 303 ...

Страница 12: ...em J1 J2 J3 Speaker MIHP 6 KEYPAD MODULE 30 Codes 1 Relay 1 2 3 4 5 6 J1 SW1 KEYPAD INV NOR INV NOR BUZZER JUMPER SETTING Common NOR 1 2 1 2 1 2 3 4 5 JUMPER SETTING Common NOR 12VDC 0V To Automation Control Set output time on speaker MIHP 6 via potentiometer P1 to slightly above minimum and program output time on keypad to 0 2 seconds Program keypad output time accordingly if more time is require...

Страница 13: ...SETTING J9 Common NOR P1 P3 P2 Fail Secure Locking MIHP 6 Speaker Audio System Keypad ELEC INST 305 ELEC INST 306 POWER SUPPLY 12V DC 1AMP KEYPAD MODULE 30 Codes 1 Relay 12v 0v L E N J1 J2 J3 12V DC Magnet or Fail Safe Release Varistor EX1 Speaker MIHP 6 1 2 3 4 5 6 J1 SW1 KEYPAD INV NOR BUZZER JUMPER SETTING Common INV JUMPER SETTING J9 Common NOR 1 2 1 2 1 2 3 4 5 EX1 Door release button sited i...

Страница 14: ...7 Noralsy Speaker MIHP 6 Audio Entry 3 or 4 Entrances Automatic Switching ELEC INST 304 NORALSY MASTERING ACCESS CONTROL ...

Страница 15: ...1 3 2 1 4 5 2 1 2 1 3 2 1 J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 6 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 5 3 2 1 Call Buttons MIHP 6 Panel 4 Call Buttons SU SD RS SU SD RS SU SD RS 6 3 9 12 0 SN2 4 1 7 SN1 5 2 11 8 C1 C2 6 3 9 12 0 SN2 4 1 7 SN1 6 3 9 12 DIP E 12 0 0 C1 C2 12 0 SN2 788 8 788 1 788 1 788 1 SU SD RS SU SD RS CALL LINE 2 CALL LINE 1 CALL LINE 3 CALL LINE 3 CALL ...

Страница 16: ...ttons SU SD RS 3 2 1 J3 J2 J1 3 2 1 4 5 2 1 2 1 3 2 1 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 7 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 6 3 2 1 Call Buttons J3 J2 J1 3 2 1 4 5 2 1 2 1 MIHP 6 Panel 5 3 2 1 Call Buttons MIHP 6 Panel 4 Call Buttons SU SD RS SU SD RS SU SD RS SU SD RS SU SD RS 6 3 9 12 0 SN2 4 1 7 SN1 5 2 11 8 C1 C2 6 3 9 SN2 4 1 7 SN1 5 2 11 8 C1...

Отзывы: