12 of 32
Opus Control Wiring and Programming Installation Manual
www.NabcoEntrances.com
P/N C-00139
Rev 10-20-17
Optional Settings
Parameter
Range
Default
Description
Stop Force Adjustment
0 - 7
3
Determines how the door reacts to a continuous safety signal:
Slow Open, Stop, or Slow Close
Sim Pair Setting
Single Door
Single
Door
Select type of Door
Normal Sim Pair
If selected; before returning to last screen, option to copy
settings to other Control is given.
Double Egress
The Activation signal (only) is shared between doors. All other
signals are independent.
Overlap Sim Pair
X
Overlap Sim Pair is for an Astragal Application.
X
Opus Control connected to door that must open first must:
3. Have activation signals connected to it
4. Be set to “Overlap Sim Pair”
X
The delayed control will be set to “Normal Sim Pair”
X
Latch Check range is wider than normal setting.
X
If selected; before returning to last screen, the option to
copy settings to the other Control is given
Output Settings
Parameter
Terminal
Range
Default
Description
Output 1
Terminal 7
X
Fully Opened Position
X
Fully Closed Position
X
Closing Status
X
Opening Status
X
Full Opened Position
X
Error State Output
X
Recycle happened
X
Electric Strike Lock
X
Electric Magnetic Lock
X
Air lock
X
Breakout Pass through
X
Door Sequencing
X
Sensor Monitoring (N.O.)
X
Sensor Monitoring (N.C.)
X
BEA Bodyguard Output
Full Open
X
Output doesn’t change state
X
Output changes when fully closed
X
Output changes when door is closing
X
Output changes when door is opening
X
Output changes when fully open
X
Output changes when error detected
X
Output changes when recycle occurs
X
Set for electric strike functionality
X
Set for Mag lock functionality
X
Set for Air lock functionality
X
Output changes when breakout occurs
X
Provision for door sequencing
X
Normally open contacts for Monitoring
X
Normally closed contacts for Monitoring
X
For BEA Bodyguard
Output 2
Terminal 13
Full Closed
Relay Output 3
Electric Lock
Terminals
— —
Open Delay Timer
N/A
X
0.1, 0.4, 1.5 sec
X
After Unlock Input
0.4
X
Delay time after activation to allow lock to
unlock before the door starts moving.
X
Only functional if Electric Lock is selected
Sequence
Delay Timer
N/A
0-10, 12, 15, 20, 25, 30
0
Amount of Hold Open time after deactivation
in seconds
Lock Condition
N/A
X
Every Fully Closed
X
One way/Night Only
Every Fully
Closed
Determines when the electric lock engages
Input Settings
Parameter
Terminal
Range
Default
Input 62
Terminal 4
— —
Exterior
Activation
No input
All Activation Mode
Activates in all modes but OFF
Interior Activation
Activation on interior for One Way mode
Exterior Activation
Activation on exterior
Beam Sensor
Beam input
LE Approach Sensor
LE door mounted sensor
Unlock Input
Receives unlocked signal from elec Lock
Spring Close Only
Turns off power close and hold close