ATEX Installation Requirements
1.
The conductor size of the phase conductor must be in the range of 16-28AWG (0.08mm²-1.31mm²).
2.
Field wiring must be suitable for a minimum of 110°C.
3.
Ethernet Switches are intended for mounting in an ATEX-Certified IP54 enclosure in a pollution degree
2 environment as defined by IEC 60664-1.
II 3 G
4.
Temperature testing of the Ethernet Switches was conducted on the switch itself in an 85°C air-
circulating oven and resulted in a Temperature Code of T4. However, end-product temperature testing
shall be considered.
5.
The end user shall provide bonding means as necessary. All bonding equipment (components) shall be
evaluated according to EN 60079-15:2010 and covered by a component certificate for the actual use.
When installing bonding components that will pass through an enclosure wall, they must have a
minimum of IP54 rating equal to the enclosure. All electrical clearances must be maintained per the
manufacturer’s instructions of the bonding component or per EN 60079-15:2010.
6.
Ethernet Switch requires protection against transients. The end-product shall provide a suitable form of
protection that removes the risk of or limits transients to no more than 42V.
7.
Products are evaluated to EN 60079-0:2012 and EN 60079-15:2010.