DIN-Rail Mounting
Install the unit in a standard DIN rail. Recess the unit to allow at least 2” of horizontal clearance for CAT5e
cable bend radius.
To install the plastic clip units to 35mm
industrial DIN rail, place the top edge of the
included mounting bracket on the back of the
unit against the DIN rail at a 15° angle as shown.
Rotate the bottom of the unit to the back (away
from you) until it snaps into place.
To remove the plastic clip units from the
35mm industrial DIN rail, place a flat head
screwdriver into the release clip found at the
bottom of the unit, and apply downward force on
the clip until it disengages from the bottom of the
unit from the DIN rail. Rotate the bottom of the
unit towards you and up at an approximate 15°
upward angle to completely remove the unit.
To install the metal clip units to 35mm
industrial DIN rail, place the top edge of the
included mounting bracket on the back of the
unit against the DIN rail at a 15° angle as shown.
Rotate the bottom of the unit to the back (away
from you) until it snaps into place.
To remove the metal clip units from the 35mm
industrial DIN rail, pull forward on the unit until
it disengages from the bottom of the DIN rail.
Rotate the bottom of the unit towards you and up
at an approximate 15° upward angle to
completely remove the unit.