N-TRON SWITCH GROUNDING TECHNIQUES FOR 100 SERIES 

 
 

The grounding philosophy of any control system is an integral part of the design.  N-Tron switches are designed 
to  be  grounded,  but  the  user  has  been  given  the  flexibility  to  float  the  switch  when  required.    The  best  noise 
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via 
a  drain  wire.    Some  N-Tron  switches  have  metal  din-rail  brackets  that  can  ground  the  switch  if  the  din-rail  is 
grounded.  In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if 
isolation is required. 

 
Users may run a drain wire & lug from the screw provided on the back face of the 
enclosure.    In the  event the provided grounding screw has been lost, care should 
be taken to limit the penetration of the outer skin by less than 1/4".  Failure to do 
so may cause irreversible damage to the internal components of the switch.  
 
Note: Ensure the power supply is grounded properly before applying power to the 
grounded  switch.    This  may  be  verified  by  using  a  voltmeter  to  determine  that 
there is no voltage difference between the power supply’s negative output terminal 
and the chassis grounding point of the switch.   

 
 
As  an  alternative  grounding  method,  both  V-  legs  of  the  power  input 
connector are connected to chassis internally on the PCB.  Connecting 
a  drain  wire  to  earth  ground  from  one  of  the  V-  terminal  plugs  as 
shown  here  will  ground  the  switch  and  the  chassis.    The  power  leads 
from the power source should be limited to 3 meters or less in length. 

 
 

 
The  use  of  shielded  cables  between  devices  is  not  required  for  most  N-Tron  devices  (please  consult  the  user 
manuals  for  specific  details).    If  the  use  of  shielded  cables  is  required,  it  is  generally  recommended  to  only 
connect the shield at one end to prevent ground loops and interfere with low level signals (i.e. thermocouples, 
RTD, etc.).  Cat5e cables manufactured to EIA-568A or 568B specifications are required for use with N-Tron 
Switches.  
 

 

 
In  the  event  all  Cat5e  patch  cable  distances  are  small  (i.e.  All  Ethernet  devices  are  located  the  same  local 
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to 
chassis ground at both ends in systems void of low level analog signals. 
 
 

Содержание 100 Series

Страница 1: ...5 17 2007 1 100 Series Media Converter Industrial Ethernet Switches User Manual Installation Guide...

Страница 2: ...5 17 2007 2 Industrial Media Converter Installation Guide 102MC XX 102MCE XX YY 104TX 105TX 108TX Where XX ST or SC and YY 15 40 or 80...

Страница 3: ...n contained in this document is subject to change without notice N TRON Corp makes no warranty of any kind with regard to this material including but not limited to the implied warranties of merchanta...

Страница 4: ...it with the end plates removed as this could create a shock or fire hazard WARNING Do not operate the equipment in a manner not specified by this manual ENVIRONMENTAL SAFETY WARNINGS WARNING Disconnec...

Страница 5: ...replace the device unless power has been switched off or the area is known to be non hazardous 5 Use 60 75 C rated Copper wire 022Nm 2 inch lbs Tightening torque for field installed connectors 6 WARN...

Страница 6: ...seFX full duplex fiber The 104TX 105TX and 108TX are affordable and share a small footprint Each switch is capable of auto negotiating 10 100 Mb and half full duplex communications The 102MC utilizes...

Страница 7: ...e packaging and store the packaging in a safe place File any damage claims with the carrier CLEANING Clean only with a damp cloth INSTALLATION Read the following warning before beginning the installat...

Страница 8: ...remove the unit from the 35mm industrial DIN rail place a flat head screwdriver into the release clip found at the bottom of the unit and apply downward force on the clip until it disengages from the...

Страница 9: ...s two LED s located at the left side of the connector The top LED indicates Activity ACT and the lower LED indicates Link LNK status LED s The table below describes the operating modes LED Color Descr...

Страница 10: ...0 22 Nm 0 162 Pound Foot All LED s will flash ON Momentarily Verify the Power LED stays ON GREEN Note Either V1 or V2 can be connected to power for minimal operation For redundant power operation V1...

Страница 11: ...ay be verified by using a voltmeter to determine that there is no voltage difference between the power supply s negative output terminal and the chassis grounding point of the switch As an alternative...

Страница 12: ...RJ45 connector Connect the other end to the far end station Verify that the LNK LED s are ON once the connection has been completed To connect any other port to another Switch or Repeater use a standa...

Страница 13: ...harmful interference in which case the user will be required to correct the interference at his own expense INDUSTRY CANADA This Class A digital apparatus meets all requirements of the Canadian Inter...

Страница 14: ...I Div 2 Groups A B C and D UL Temperature Ratings 102MC MCE T5 104TX 105TX and 108TX T4A EMI EN61000 6 4 EN55011 Class A FCC Title 47 Part 15 Subpart B Class A ICES 003 Class A EMS EN61000 6 2 EN6100...

Страница 15: ...rature 40 C to 85 C Operating Humidity 10 to 90 Non Condensing Operating Altitude 0 to 10 000 ft Network Media 10BaseT Cat 3 Cable 100BaseT Cat 5 Cable 100BaseFX Multimode 50 62 5 125 m Fiber Singlemo...

Страница 16: ...4VDC Input Ripple Less than 100 mV Input Wire Size 16 28 AWG Environmental Operating Temperature 40 C to 80 C Storage Temperature 40 C to 85 C Operating Humidity 10 to 90 Non Condensing Operating Alti...

Страница 17: ...VDC Steady State Inrush Current 8 1 Amp 0 7ms max 24VDC Input Ripple Less than 100 mV Input Wire Size 16 28 AWG Environmental Operating Temperature 40 C to 70 C Storage Temperature 40 C to 85 C Operat...

Страница 18: ...ES EXCLUSIVE IF AN N TRON PRODUCT DOES NOT OPERATE AS WARRANTED ABOVE CUSTOMER S SOLE REMEDY FOR BREACH OF THAT WARRANTY SHALL BE REPAIR REPLACEMENT OR REFUND OF THE PURCHASE PRICE PAID AT N TRON S OP...

Отзывы: