6.0 Controls
(continued...)
07
KICKSPACE
®
500 DUO ECO
Installer’s Set-up Parameters
To access the installation parameters menu, press and hold
(OK)
for 10 seconds. Use
or
to highlight the parameter to be
adjusted then press
(OK)
to toggle the parameter setting, when
the value starts to blink, use
or
to adjust the value. Then
press
(OK)
to confirm. Once parameters are set, go to
<End>
parameter and press
(OK)
to go back to the main menu.
6.0
Parameter
Name
Default Setting
Description
Alternative Setting
Manually pair the thermostat to the receiver
rF ini
Press (OK) to begin pairing
Myson Smart Start (Adaptive Start) Thermostat will learn
to achieve temperature by time requested
At
No
Yes
Window open detection, product will switch off if a large
temperature drop is detected (usually caused by an open
window / door)
oP
No
Yes
Room temperature limiter (limits the maximum room
temperature set point)
Lt
20°C< TR MAX <30°C
30°C
Press OK
Automatic daylight saving time adjustment
No - manual
Yes - automatic
n/a
n/a
Ch
Reverts the control back to factory settings
CL
Version number
UE
Exit the installation menu
End
Fan Only Mode
If required, the unit can be used in summer for air circulation
without heat.
• Set the fan only/off/heating switch to fan only (blue dot)
• Adjust fan speed to required setting
KICKSPACE
®
may have poor performance/cycle if a low water
temperature/flow rate is supplied, please refer to your installer as
this could be from the following:
• Unit incorrectly sized for heat loss of room
• Lack of flow to KICKSPACE
®
from heating system
• Pipe sizes/pump sized incorrectly
• System incorrectly balanced
Fan not working in
heating mode
Possible Causes
Unit switched off
Room thermostat not calling for heat
Unit not switched on at fused spur
Fuse blown at fused spur
Unit isolating valves shut
Water temperature of
KICKSPACE
®
below 43°C
Problem
Remedy
Turn on
Turn up room thermostat
Switch on at spur
Replace fuse
Open valves
Ensure boiler, pump and other central
heating equipment is working correctly,
if not contact your installer
Note:
Operation of fan can be checked by
switching to fan only setting
If the fan convector is still faulty after checking the above, call your installer.
Once installed this fan convector becomes an integral part of
a complete heating system that includes boiler, pump, other
emitters such as radiators and fan convectors, and a number of
heating controls, dependent on system complexity. An apparent
problem with this unit may be the result of system controls being
incorrectly set and can be solved easily without calling out your
installer. Before calling your installer, please carry out the checks
listed below.
7.0 Troubleshooting
7.0
Press and hold OK for 10 seconds to reset