HI-LINE Super RC

1.0  General Information

2.0  Heating System Design

l

This MYSON HI-LINE Super RC fan convector is designed for 
wall-mounted installation with a maximum installation height
of 3m to the underside of the unit. 

l

The minimum installation height is 1.8m to the underside of
the unit.

l

The minimum clearance between the top of the unit and the
ceiling should be 20mm for rear pipe connection or 100mm
for connection from above.

l

The minimum side clearance is 150mm.

l

The HI-LINE Super RC should only be used on closed 
circulation, two pipe, pump assisted central heating systems.

l

Before proceeding with the installation, the heating system
design must be considered and the unit correctly sized to
meet the heat loss requirements of the room at normal fan
speed. 

l

This unit is supplied with an infra red remote control system
and has 3 operating modes - 

Automatic – the desired room temperature is programmed in
to the unit and the fan speed is automatically adjusted until
the desired room temperature is achieved.

Fan only – allows user selection of any of the 3 available fan
speeds irrespective of room temperature or water temperature
in the coil.

Fan only with water temperature control – allows the user to
select any of the available fan speeds, which will operate only
if the water temperature in the coil is above 32C. This enables
control of the unit via an externally mounted room thermostat
if desired.

l

This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental 
capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.

Children should be supervised to ensure they do not play with
the appliance.

This fan convector must be fitted on a two pipe, pumped 
circulation heating system.

For optimum fan convector heating performance the system
must be capable of providing sufficient hot water through the
heat exchanger. This means that:

1. The minimum pipe size from boiler to fan convector must be

at least 22mm.

2. This unit is not suitable for use on microbore pipework.

3. Where the unit is fitted on to a system with other emitters a

separate circuit for the fan convector should be considered
to provide adequate water flow.

4. The system water must be above 32°C for heating mode. 

5. For heat pump applications - see Commissioning Procedure.

6. This unit is NOT suitable for one-pipe systems.

7. Optimum performance will require effective balancing of

the whole system.

8. This unit should NOT be used to replace a radiator in an 

existing system unless an adequate flow of water can be 
guaranteed.

3.0  Unit Selection/Sizing

Heat output performance is given in the Technical Data section
of this manual. Outputs are shown for the 3 fan speeds,
however, it is important to size the unit to match the calculated
heat loss requirements of the room with the unit operating on

the low fan speed. The higher fan speeds are used in automatic
mode when the room temperature is significantly lower than the
preset temperature.

4.0  Location

l

This HI-LINE Super RC unit may be fitted to any convenient
wall at a height from floor level that suits the application, 
providing an unimpeded flow of warm air into the area to be
heated.

l

The maximum distance from the underside of the unit to floor
level is 3m.

l

The minimum distance to the underside of the unit is 1.8m.

l

This unit should not be installed in locations with ceiling
heights greater than 3.5m.

l

The unit should be mounted on a flat wall, and stud or 
partition walls should be avoided to minimise the possibility
of noise transmission.

1.0

2.0

3.0

4.0

This unit MUST NOT be installed in a bathroom or other similar high humidity area.

23674 HiLine Super RC manual  27/06/2011  09:24  Page 4

Содержание 25-18

Страница 1: ...erating Maintenance and After Sales Manual Product Serial Number Please leave this manual with the end user Part Number 1370065 Issue 4 heatingthroughinnovation HI LINE Super RC Models 25 18 29 20 01...

Страница 2: ...t Selection Sizing 03 4 0 Location 03 5 0 Preparation 04 6 0 Fixing 04 7 0 Water Connections 05 8 0 Electrical Connection 06 9 0 Commissioning Procedure 07 10 0 Technical Data 08 11 0 Operating Instru...

Страница 3: ...appliance This fan convector must be fitted on a two pipe pumped circulation heating system For optimum fan convector heating performance the system must be capable of providing sufficient hot water t...

Страница 4: ...lace on screws with adhesive side towards the point l Tighten the screws into the wall leaving about 9mm projecting l Press adhesive washers to the wall Remove the outer casing as follows l Remove the...

Страница 5: ...st practice and a suitable inhibitor is added to the system as necessary l Open valves fully check pipe connections for leaks and vent the heat exchanger see Commissioning Procedure Fig 4 Fig 3 5 0 6...

Страница 6: ...e unit should be made through the hole provided at the top left hand side of the unit using the cable gland provided l Connect live and neutral wires to the power board terminal connections and the ea...

Страница 7: ...is means low outlet air temperatures from the unit are avoided when the room temperature is low in relation to the set temperature This facility can be switched on or off by following the instructions...

Страница 8: ...orrection Factors 455 ltr h 100 gal h multiply by 1 03 227 ltr h 50 gal h multiply by 0 98 113 ltr h 25 gal h multiply by 0 85 Model Air Flow m3 h Air Flow ft3 h 29 20 390 470 540 13772 16597 19069 25...

Страница 9: ...n manual mode with water temperature control any of the 3 fan speeds can be selected and the fan will operate when the water temperature in the coil is greater than 32 C This means that heating perfor...

Страница 10: ...seconds until the horizontal bars disappear 10 HI LINE Super RC 12 0 Troubleshooting Once installed this fan convector becomes part of a complete heating system that generally will include boiler pum...

Страница 11: ...crease temperature set point Switch on at spur Replace fuse Open valves Check boiler Programmer ON Boiler ON and set to high with central heating pump running Note Operation of fan convector can be ch...

Страница 12: ...482 713927 F 01482 789056 service convectors myson co uk Spare parts and technical help on all Convector products are available from MYSON Service MYSON Eastern Avenue Team Valley Gateshead Tyne Wear...

Отзывы: