All the following functions can be programmed using the remote control DD-LCDHS-LR handset: 

1.

Detector Parameters (factory default in brackets):

1.1 

Time adjustment

  (20 min) 

10 seconds to 99 minutes time delay (select 0 for 10 second 
delay 

 use for commissioning only). 

1.2 

Sensitivity On

 (9) 

Sensitivity level when the detector is already operational 
adjustable between 1 (min.) and 9 (max.) 

1.3 

Sensitivity Off 

(9)

 

Sensitivity level for switching the detector on 

 adjustable 

between 1 (min.) and 9 (max.). 

1.4 

Range (m) 

(25)

 

Sensor range (in metres).  Can be set from 0-999, but only 
the values 5-30 are effective.  Other values are used for 
sensor testing and debugging. 

1.5 

Power Up On

 (Y) 

Select No for a 10 second delay on start up. If Yes is selected, 
there will be no delay on start up and the detector will always  
power up detecting. 

1.6 

Walk Test 

(N) 

LEDs behind the detector lens will illuminate to show   
movement has been detected (use for commissioning). 

1.7 

Disable Detector

 (N) 

Disables detection, leaving the relay output permanently off  
with the dimming output operational. This mode is used when 
the unit is for maintained illuminance only. 

1.8 

Factory Default 

Restores factory default settings.

 

2.

Modes (factory default in brackets):

2.1  Channel Modes 

2.1.1   Switch only

 

Usually used for absence detection - in this mode the dimming 
channel is not used. 

2.1.2

  

Switch and dim together 

(default) 

The detector will switch and dim the lighting together. 

2.1.3 

 

Switch and dim separate 

Relay and dimming channels are controlled separately. 

2.2     Switch Modes 

2.2.1

  

2 position switch together 

(default) A single centre-biased retractive switch will be used to 

control both channels together. 

2.2.2 

 

2 position switch separate

 

A single centre-biased retractive switch will be used to 
control only the dimming channel. 

2.2.3

  

1 position switch together 

A single-position retractive switch controls both channels 
together.  

2.2.4

  

1 position switch separate 

Two single-position retractive switches, controlling the 
channels separately.  

3.

Switching Channel 1 functions (factory default in brackets):

3.1

 

Presence detection 

Auto switch on with detection, auto off after movement ceases 

(default) 

and time delay ends.  

3.2

 

Absence detection

 

Manual switch on, auto off after movement ceases and time 
delay ends. 

3.3 

Switch level on 

(9)

 

Lux level setting to prevent the luminaires being switched on if 
the ambient light level is sufficient (adjustable between 1  
and 9). The luminaires will always be switched on at level 9. 

3.4 

Switch level off 

(9)

 

Lux level setting to switch the luminaires off during occupancy 
if the ambient light level goes above the setting (adjustable  
between 1 and 9). Level 9 will always keep the lights on.  

5. Programming

Содержание MWS7

Страница 1: ...grams 7 7 Detection patterns 10 8 Fault finding 12 9 Specification 12 10 Part numbers 12 80 60 40 20 0 90 10 30 50 70 90 10 30 50 70 80 60 40 20 80 60 40 20 0 90 10 30 50 70 90 10 30 50 70 80 60 40 20...

Страница 2: ...ion to be accurately set irrespective of whether the object is a person or a fork lift truck a common problem with other types of detector is that larger objects are picked up at longer distances maki...

Страница 3: ...s be placed near the centre of the corridor or aisle and angled correctly to provide maximum coverage of the desired area Note that the fully adjustable detection range of the MWS7 provides a well def...

Страница 4: ...he sensor s range is changed or the sensor is power cycled this step must be observed to ensure the proper operation of the sensor 7 Walk towards the sensor until the load comes on to find the detecti...

Страница 5: ...tch only Usually used for absence detection in this mode the dimming channel is not used 2 1 2 Switch and dim together default The detector will switch and dim the lighting together 2 1 3 Switch and d...

Страница 6: ...time adjustable between 0 and 99 4 12 Fade mins 0 This is the time period adjustable between 0 and 99 minutes that the luminaire will be held at the fade value before turning off A value of 0 disable...

Страница 7: ...BIASED RETRACTIVE GND EXT LUX GND SW UP SW DOWN GND SLAVE DSI DALI DSI DALI JUMPERS LIVE NEUTRAL NEUTRAL L OUT NOT USED EARTH LUMINAIRE NON DIMMING LUMINAIRE DSI DALI DIMMING NEUTRAL L OUT NOTE All in...

Страница 8: ...dimming output In this configuration the internal lux sensor needs to be disabled by setting Switch level on and Switch level off to maximum This configuration is used when a separate lux sensor is n...

Страница 9: ...ance when the area is un occupied generally for safety reasons DSI DALI does not allow multiple masters to generate the dimming signal hence the use of one master and multiple slaves It is important i...

Страница 10: ...shown in subsequent diagrams still applies however regardless of the type and size of object Several scenarios are given below Please contact our technical department for further information Example 1...

Страница 11: ...aisle using two sensors Note A minimum separation of 4m between sensors recommended Example 5 above 6 below Height 12m Range limits Setup 5 18m 18m 25m 50m coverage Setup 6 25m 18m 18m 25m 70m covera...

Страница 12: ...that the load turns on when powered Check the switch on lux level setting Increase the setting to allow the controller to turn on at a higher ambient natural light level Check the external lux sensor...

Отзывы: