Installation and Operations Manual

 
 

 

 

 

4. PREVENTATIVE MAINTENANCE PROCEDURES 
 

WIRE CONNECTIONS 

All power wire connections should be inspected for tightness one (1) month after 
commissioning and every six (6) months thereafter. 

 

CAPACITOR CELLS 

Capacitor cells should be visually checked for distorted tops one (1) month after 
commissioning and every six (6) months thereafter. 

 

INDICATION LIGHTS 

 

Blown fuse indication lights may be checked daily. 

 
 

CLEANLINESS  

Every six (6) months the fan filters should be inspected and cleaned or replaced 
and the unit should be clean of all contaminants. Note: DO NOT USE HIGH 
PRESSURE LIQUID TO CLEAN UNITS. 
 

 

CONTACTORS  

Remove covers and visually check contacts for signs of wear and excessive arcing 
every six (6) months. Energize each contactor with the controller in "manual" mode 
to ensure proper operation.  
 

How to Check Fuses: 

 

Trouble: Fuse light is illuminated. 

 

This indicates that a fuse is blown. Typically, power surges or a bad capacitor 
causes a fuse to blow. 

 

Disconnect power

 from the capacitor unit and wait one minute after the 

power has been disconnected to allow the capacitors to discharge. 

 

Check affected capacitor following steps below: 

How to Test a Capacitor Cell

 

Replace affected fuse. 

 

How to Test a Capacitor Cell: 

 

With a Capacitance Meter

 

Capacitor cells are rated in microfarad and voltage. The easiest way to test a cell 
is to measure the microfarads with a capacitance meter. 

 

Disconnect power 

from the capacitor unit and wait one minute after the 

power has been disconnected to allow the capacitors to discharge. 

 

Measure microfarads using a capacitance meter. The microfarads should be 
equal to the microfarad rating or up to 5% over the rating. 

 

If microfarads are below the minimum, the cell is going bad. 

 

Replace bad capacitor cells. 

 

Visual Inspection of Cell

 

If a capacitor meter is not readily available, the status of a cell can sometimes be 
determined visually. 

 

If the cell can is "bulged out" or "pouched up" on the top, it is definitely bad. 

 

Disconnect power 

from the capacitor unit and wait one minute after the 

power has been disconnected to allow the capacitors to discharge. 

 

Replace bad capacitor cells. 

 
 
 

Содержание CALTRAP

Страница 1: ...CALTRAP INSTALLATION AND OPERATIONS MANUAL...

Страница 2: ...otton clothing etc as required by local code and safety procedures Warnings and Cautions Failure to read these instructions and failure to install the equipment per instructions may cause equipment da...

Страница 3: ...SOURCE 2 2 1 Voltage 2 2 2 Conductor Wire Size 2 2 3 Disconnect Devices and Ratings 2 2 4 Connections to Power Source 2 2 5 Equipment Ground 2 3 REMOTE CONTROL 3 4 PREVENTATIVE MAINTENANCE PROCEDURES...

Страница 4: ...he unit cannot be placed into service reasonably soon after its receipt it should be stored in a clean dry and ventilated building free from temperature extremes Acceptable storage temperatures are fr...

Страница 5: ...do you keep harmonic currents from the drive cables you also have a means to disconnect the Caltrap from the drive circuit This will allow maintenance if needed to the Caltrap while keeping the motor...

Страница 6: ...50 200 45 6 75 100 36 6 60 60 40 96 2 0 175 200 48 4 80 100 38 4 6 65 100 42 5 102 2 0 175 200 51 4 90 100 40 8 6 70 100 45 108 3 0 200 200 54 4 90 100 43 2 6 75 100 50 120 3 0 200 200 60 2 100 100 48...

Страница 7: ...a fuse to blow Disconnect power from the capacitor unit and wait one minute after the power has been disconnected to allow the capacitors to discharge Check affected capacitor following steps below H...

Страница 8: ...2009 Myron Zucker Inc All Rights Reserved...

Отзывы: