MYRON ZUCKER CALTRAP Скачать руководство пользователя страница 6

CALTRAP

  

Installation and Operations Manual

 
 

 

 

3. REMOTE CONTROL

 

The Caltrap

 is shipped with a terminal block. For remote control, remove jumper 

at terminals and install your isolated contact in its place to turn unit on and off. 
Refer to drawings for terminal location. 

 

TABLE 1 

RECOMMENDED WIRE SIZES, SWITCHES AND FUSES FOR 3-PHASE, 60Hz CAPACITORS 

(These wire sizes are based on 135% of rated current in accordance with the National Electrical Code, Article 460.) 

 

240 VOLTS 

480 VOLTS 

600 VOLTS 

KVAR 

Current* 

(Amps) 

Wire Size 

90°C-Type 

THHN 

XHHW* or 

Equiv. † 

Fuse 

(Amps) 

C.B. or 

Switch 

(Amps) 

Current* 

(Amps) 

Wire Size 

90°C-Type 

THHN 

XHHW* or 

Equiv. † 

Fuse 

(Amps) 

C.B. or 

Switch 

(Amps) 

Current* 

(Amps) 

Wire Size 

90°C-Type 

THHN 

XHHW* or 

Equiv. † 

Fuse 

(Amps) 

C.B. or 

Switch 

(Amps) 

2.4 

14 

30 

1.2 

14 

30 

1.0 

14 

30 

1.5 

3.6 

14 

30 

1.8 

14 

30 

1.4 

14 

30 

4.8 

14 

10 

30 

2.4 

14 

30 

1.9 

14 

30 

2.5 

14 

10 

30 

14 

30 

2.4 

14 

30 

7.2 

14 

15 

30 

3.6 

14 

30 

2.9 

14 

30 

9.6 

12 

20 

30 

4.8 

14 

10 

30 

3.8 

14 

30 

12 

12 

20 

30 

14 

10 

30 

4.8 

14 

10 

30 

14.4 

10 

25 

30 

7.2 

14 

15 

30 

5.8 

14 

10 

30 

7.5 

18 

10 

30 

30 

14 

15 

30 

7.2 

14 

15 

30 

10 

24 

40 

60 

12 

12 

20 

30 

9.6 

12 

20 

30 

12.5 

30 

50 

60 

15 

10 

25 

30 

12 

12 

20 

30 

15 

36 

60 

60 

18 

10 

30 

30 

14.4 

10 

25 

30 

17.5 

42 

70 

100 

21 

35 

60 

16.8 

10 

30 

30 

20 

48 

80 

100 

24 

40 

60 

19.2 

35 

60 

22.5 

54 

90 

100 

27 

50 

60 

21.6 

35 

60 

25 

60 

100 

100 

30 

50 

60 

24 

40 

60 

27.5 

66 

125 

200 

33 

60 

60 

26.4 

45 

60 

30 

72 

125 

200 

36 

60 

60 

28.8 

50 

60 

32.5 

78 

1/0 

150 

200 

39 

65 

100 

31.2 

50 

60 

35 

84 

1/0 

150 

200 

42 

70 

100 

33.6 

60 

60 

37.5 

90 

1/0 

150 

200 

45 

75 

100 

36 

60 

60 

40 

96 

2/0 

175 

200 

48 

80 

100 

38.4 

65 

100 

42.5 

102 

2/0 

175 

200 

51 

90 

100 

40.8 

70 

100 

45 

108 

3/0 

200 

200 

54 

90 

100 

43.2 

75 

100 

50 

120 

3/0 

200 

200 

60 

100 

100 

48 

80 

100 

52.5 

126 

3/0 

200 

200 

63 

110 

200 

50.4 

80 

100 

55 

132 

4/0 

250 

400 

66 

125 

200 

52.8 

90 

100 

60 

144 

4/0 

250 

400 

72 

125 

200 

57.6 

100 

100 

65 

156 

4/0 

250 

400 

78 

1/0 

150 

200 

62.4 

110 

200 

70 

168 

300M 

300 

400 

84 

1/0 

150 

200 

67.2 

125 

200 

75 

180 

300M 

300 

400 

90 

1/0 

150 

200 

72 

125 

200 

80 

192 

350M 

350 

400 

96 

2/0 

175 

200 

76.8 

1/0 

150 

200 

90 

216 

500M 

400 

400 

108 

3/0 

200 

200 

86.4 

1/0 

150 

200 

100 

240 

500M 

400 

400 

120 

3/0 

200 

200 

96 

2/0 

175 

200 

125 

300 

(2)4/0 

500 

600 

150 

4/0 

250 

400 

120 

3/0 

200 

200 

150 

360 

(2)300M 

600 

600 

180 

300M 

300 

400 

144 

4/0 

250 

400 

200 

480 

(2)500M 

800 

800 

240 

500M 

400 

400 

192 

350M 

350 

400 

225 

540 

(3)300M 

900 

1200 

270 

(2)4/0 

500 

600 

216 

500M 

400 

400 

250 

600 

(3)350M 

1000 

1200 

300 

(2)4/0 

500 

600 

240 

500M 

400 

400 

300 

720 

(3)500M 

1200 

1200 

360 

(2)300M 

600 

600 

288 

(2)4/0 

500 

600 

350 

  

  

  

  

420 

(2)350M 

700 

800 

336 

(2)300M 

600 

600 

400 

  

  

  

  

480 

(2)500M 

800 

800 

384 

(2)350M 

700 

800 

450 

  

  

  

  

540 

(3)300M 

900 

1200 

432 

(2)400M 

750 

800 

500 

  

  

  

  

600 

(3)350M 

1000 

1200 

480 

(2)500M 

800 

800 

550 

  

  

  

  

660 

(3)500M 

1100 

1200 

528 

(3)300M 

900 

1200 

600 

  

  

  

  

720 

(3)500M 

1200 

1200 

576 

(3)350M 

1000 

1200 

* Rated current based on operation at rated voltage, frequency, and KVAR. 
†Consult National Electrical Code for other wire types.  Above size based on 35°C Ambient Operation. (Refer to NEC table 310-16) 

Note: 

Fuses furnished within Capacitor Assembly may be rated at higher value than shown in this table.  The table is correct for field 
installations and reflects the manufacture's suggested rating for overcurrent protection and disconnect means in compliance with the 
National Electrical Code. 

 

 

 

Содержание CALTRAP

Страница 1: ...CALTRAP INSTALLATION AND OPERATIONS MANUAL...

Страница 2: ...otton clothing etc as required by local code and safety procedures Warnings and Cautions Failure to read these instructions and failure to install the equipment per instructions may cause equipment da...

Страница 3: ...SOURCE 2 2 1 Voltage 2 2 2 Conductor Wire Size 2 2 3 Disconnect Devices and Ratings 2 2 4 Connections to Power Source 2 2 5 Equipment Ground 2 3 REMOTE CONTROL 3 4 PREVENTATIVE MAINTENANCE PROCEDURES...

Страница 4: ...he unit cannot be placed into service reasonably soon after its receipt it should be stored in a clean dry and ventilated building free from temperature extremes Acceptable storage temperatures are fr...

Страница 5: ...do you keep harmonic currents from the drive cables you also have a means to disconnect the Caltrap from the drive circuit This will allow maintenance if needed to the Caltrap while keeping the motor...

Страница 6: ...50 200 45 6 75 100 36 6 60 60 40 96 2 0 175 200 48 4 80 100 38 4 6 65 100 42 5 102 2 0 175 200 51 4 90 100 40 8 6 70 100 45 108 3 0 200 200 54 4 90 100 43 2 6 75 100 50 120 3 0 200 200 60 2 100 100 48...

Страница 7: ...a fuse to blow Disconnect power from the capacitor unit and wait one minute after the power has been disconnected to allow the capacitors to discharge Check affected capacitor following steps below H...

Страница 8: ...2009 Myron Zucker Inc All Rights Reserved...

Отзывы: