114201I – System Installation Manual
24
Program Functions
All program functions are password protected. The password for user level is 1234. When
the
PROGRAM
Keypad is pressed, the display will prompt the user for the password. After
the password is entered (
1234
+
ENTER
key), the user can change the Date, Time, Month
Test Date, Month Test Time, Yearly Test Date and Yearly Test Time, Load Reduction Fault,
Low VAC Alarm, High VAC Alarm, Ambient Temp Alarm and Near Low Battery settings.
Time is always in the 24 hour standard. Example 4:00 PM is 16:00.
Table 7.3 Program Functions
Parameter
Format
Factory Default
Date MM/DD/YY
(Month, Date, Year)
Current Date
Time HH/MM
(Hours, Minutes)
Eastern Stand Time
Monthly Test Date DD (Date)
15
th
of the Month
Monthly Test Time HH/MM (Hours, Minutes)
5:00
Yearly Test Date MM (Month)
01
Yearly Test Time HH/MM (Hours, Minutes)
8:00
Load Reduction
AAAA (AMPS)
0.0A
Low VAC Alarm
VVVV (Volts)
1.0V
High VAC Alarm VVVV (Volts)
999.9V
Ambient Temp
Alarm
DDD (Degrees Centigrade)
70°C
Near Low Battery VVVV
(Volts)
See Table 7.4
Table 7.4 Near Low Battery Fault Chart
DC Voltage
Near Low Battery
240VDC
216VDC
The Day of the Automatic Tests
Table 7.5 shows the purpose of each parameter and its factory setting.
Table 7.5 Factory Setting for Automatic Test Parameter
Parameter
Determines...
Factory Default
Monthly Test The time and the day of the month for the monthly tests.
15
th
@ 5:00 AM
Yearly Test The time and the date for the yearly test.
(January) 1 @
8:00 AM
The Length of the Automatic Tests
Parameters Monthly Test and Yearly Test determine how long the battery test is. Table 7.6
shows the purpose of each parameter.
Table 7.6 Factory Setting for Automatic Test Parameters
Parameter
Purpose
Factory Default for 90 minute systems
Monthly Test Monthly battery test.
5 Minutes
Yearly Test Yearly battery test.
90 Minutes
The factory can only reprogram these parameters.