PM 600 PLUS Line Interactive Schuko
Startup manual V.1.0
6. Important Safety Warning
This manual contains important instructions that should be followed
during installation and maintenance of the UPS and batteries.
CAUTION!
To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area free of conductive
contaminants. (See the specs for the acceptable temp. and
humidity range.)
CAUTION!
With the installation of this equipment, it should be
prevented that the sum of the leakage current of the UPS to the
connected consumer exceeds 3.5mA.
Attention hazardous through electric shock. Also with disconnection
of this unit from the mains, hazardous voltage still may be
accessible through supply from battery. The battery supply should
be therefore disconnected in the plus and minus pole at the quick
connectors of the battery when maintenance or service work inside
the UPS is necessary.
7. Battery Replacement
Simple steps to replace the battery:
TURN the unit over and
Remove the screws located on
the bottom of the UPS to open
the battery cover.
LIFT the battery out of the
compartment and disconnect
the two wires connecting it to the
UPS. Replace the same type of
batteries.
Slide the battery compartment
cover back to the battery
housing.
CAUTION!
Servicing of batteries should be performed or
supervised by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away from
batteries.
CAUTION!
When replacing the batteries, use the same number
and type of batteries.
CAUTION!
Internal battery voltage is 12Vdc. Sealed, lead-acid,6
cells battery.
CAUTION!
Do not dispose of batteries in a fire. The battery may
explode. Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to the skin and eyes.
CAUTION!
A battery can present a risk of electric shock and high
short circuit current. The following precaution should be observed
before replacing batteries:
1)
Remove watches, rings, or other metal objects.
2)
Use tools with insulated handles.
3)
Wear rubber gloves and boots.
4)
Do not lay tools or metal parts on top of batteries.
5)
Disconnect charging source prior to connecting or
disconnecting batteries terminal.
8. Specification
MODEL
PM 600 PLUS Line Interactive Schuko
INPUT
Capacity
625VA/375W
Voltage
220/230/240VAC
Voltage Range
170-280VAC
OUTPUT
Voltage Regulation
±10% (Batt. Mode)
Transfer Time
Typical 2-6ms, 10ms max.
Waveform
Simulated Sine Wave (Batt. Mode)
BATTERY
Type & Number
12V/7AH x 1
Recharge Time
4 hours recover to 90% capacity
PHYSICAL
Dimension,
DXWXH
292 x 199 x 91 (mm) (foot included)
Net Weight (kgs)
5.3
ENVIRONMENT
Humidity
0-90% RH @ 0- 40°C (non-condensing)
Noise Level
Less than 40dB
INTERFACE
USB Port
Supports Windows® 2000/2003/XP, Windows®
Vista/2008/7, Linux, Unix and MAC
9. Trouble Shooting
Problem
Probable Cause
Solution
The UPS will not turn on.
Battery is disconnected or utility power is
not available at the wall outlet.
Connect the battery and ensure power is
available at the wall outlet.
Yellow LED is flashing, and alarm
is heard intermittently. But mains
is normal.
UPS is not connected properly to the
mains.
Connect the UPS according to the installation
guide.
Line breaker protected.
Press the breaker.
UPS shutdown after a few
seconds and circuit breaker
protected.
UPS output is short-circuited, possibly due
to defective computer.
Disconnect your computer from the UPS and then
press the breaker.
Inadequate runtime
Battery is not fully charged.
Charge the unit at least 4 hours.
Battery is near the end of useful life.
As a battery ages, the amount of runtime
available will decrease. You can replace the
battery by following the steps above.