Service Manual
PV1100 PLUS Series
(1200VA/1800VA/2400VA)
- 5 -
D. Main Board MOS Broken when Boosting
(Figure 1.2)
Position
Type
Normal Value
Failure Status
Main board Q1-Q7
MOS
Boost reversely
between D-S 0.248
Short circuit or other
value
Note: If confirmed MOS broken, need to check if relative drive resistor is burned, broken
resistor value is larger than normal one.
E. Main Board Invert MOS Broken
(Figure 1.3)
Position
Type
Normal Value
Failure Status
Main board Q8-Q16
MOS
Boost reversely
between D-S 0.515
Short circuit or other
value
Note: If confirmed MOS broken, need to check if relative drive resistor is burned, broken
resistor value is larger than normal one.
F. Cables Not to Connect Well
Position
Type
Normal Value
Failure Status
Connection cable
between control board
and button board
Connection
cable
Connected well
Disconnected
4.2 PV Failure in Charging
Possible Reasons as follows
A. PV Cables Connected Reversely or PV Volt Abnormal
Position
Type
Normal Value
Failure Status
PV cable connection
terminal
Cable connection
terminal
Connected well &
PV volt between
15-30VDC
Poor connect, PV volt
is beyond normal
value
B. In AC Priority Mode
Position
Type
Normal Value
Failure Status
Setting option No.6
Charger priority
setting
CSO/OSO
Others