Service Manual
PV1100 PLUS Series
(1200VA/1800VA/2400VA)
- 4 -
3. Maintenance
Note: When repairing, in order to avoid second damage caused by large current, you must
use DC power supply analog battery to connect to open the inverter, and make sure the
current is below 3A.
4. Fault Symptom
4.1 Inverter Failure in Starting
Possible Reasons as follows
A. Battery Reversely Connected or Battery Volt Abnormal
Check if battery input volt is normal:
B. Battery Reverse Protection Board Fuse Broken
Check if fuse is disconnected
(Figure 1.1)
C. Control Board Auxiliary Power Abnormal
Check if auxiliary power MOS and IC are broken.( Figure 1.7, less possibility, normally
occurs when inverter blast)
Position
Type
Normal Value
Failure Status
Battery input
terminal
Cable connection
terminal
10-14VDC
Beyond normal value
Position
Type
Normal Value
Failure Status
Battery reverse
protection board F1
Fuse
Direct connected, 0
ohm
Disconnected
Position
Type
Normal Value
Failure Status
Control board Q7
MOS
Boost reversely
between D-S 0.551
Short circuit or other
value