background image

TTDJ-99062N page 8 of 8

System Start Up

Pr

ess the RESET key to clear any faulted sensor input and unground/enable

ignition for engine operation. Apply starting power to the engine.

The first thing displayed on versions with Tachometer is the engine speed.

While there is time remaining in either of the Class “B” timers, the display

will alternate between engine speed and the Class “B” timers (4 seconds

each). Once the Class “B1” timer expires, while there is time remaining in

the Class “B2” timer, the display will alternate between the engine speed and

the Class “B2” timer (4 seconds each). Once both Class “B” timers expire,

the engine speed is displayed continuously.

While there is time remaining in the Class “B1” timer, the display will alternate

between engine speed and the Class “B1” time remaining for example: “1 0:30”

(4 seconds each). All sensor inputs configured as Class “B1” are locked out at

this point. For non -T models the “B1” display will be steady. To zero this

timer, press TIMER “0”.

Once the Class “B1” timer expires while there is time remaining in the Class

“B2” timer, the display will alternate between engine speed and the Class “B2”

time remaining for example:  “2    0:30” (4 seconds each). All sensor inputs

configured as Class “B2” are locked out at this point. For non -T models the

“B2” display will be steady. To zero this timer press the TIMER “0” key, after

the Class “B2” timer has expired.

To display the run hours, press the “DisplayHours” key. The current Run hours will

be displayed for 5 seconds. NOTE: On all non tachometer models (non -T) the

RUN HOURS are displayed after the Class “B” Timers expire, instead of ENGINE

SPEED. The decimal point flashes to indicate the unit is running.

If any one of the sensor inputs configured as an ALARM-ONLY is faulted, the

Alarm Output will turn ON, and the sensor  number will be displayed in the first

two digits. Press the RESET key after the sensor input has cleared, to clear the dis-

play and to turn OFF the Alarm output. 

If the engine speed exceeds the Overspeed Set point the engine will shutdown,

bypassing the Ignition Ground Delay. The TTDJ-T models will display “50”.

Overspeed overrides the Test mode.

If after the Class “B1” Timer expires the engine speed falls below the

Underspeed  Setpoint,  the  engine  will  shutdown.  The  TTDJ  will

annunciate/display “51”. Underspeed overrides the Test mode. 

To manually shutdown the engine, press the STOP/RUN key. The TTDJ will

shutdown the system and the display will indicate “52”. Manual Stop over-

rides the Test mode.

Upon reaching a shutdown condition, the unit will trip the fuel valve, and, after

the delay expires, ground the ignition. This delay is bypassed on Overspeed

(50), Emergency Shutdown (32), and sensor input #29 if configured as Class

“ESD”.

TTDJ-IGN models annunciate/display “51” when ignition input is lost. 

The energy stored in the FV+ circuit will trip the fuel valve.

After the shutdown condition is cleared on the equipment, press RESET key.

The Test Timer is used to verify that sensors are wired properly and working

correctly. To perform a sensor test while running do the following: 

1.

Press the TEST key and verify that the Test Timer is shown with 

5 minutes: (3    5.00).

2.

Trip the first sensor to be tested and verify that the sensor number and

class type appear on the display (see displays below). The display will

alternate between the Sensor Number and the Test timer.

3.

Clear the sensor then press the RESET key. Verify that the sensor num-

ber is cleared from the display.

4.

Repeat Steps 2 and 3 for each sensor.

5.

To exit, press the TIMER “0” key or allow the Test Timer to expire.

NOTE: Any of the following conditions will override the Test Timer:

Emergency Shutdown (32), Overspeed Shutdown (50), Underspeed Shutdown

-T models (51), Loss of Ignition (51) non-T models, Manual Stop (52), and

sensor input #29, if configured as a Class “ESD”..

In Test, when a sensor is tripped, he sensor number and the Class type are

displayed, for example if sensor #1 (01) a Class “B1” shutdown is tripped in

the Test the LCD reads “01    t1”. The following are the Test Mode Displays:

(t0):  Class “A” Shutdown
(t1):  Class “B1” Shutdown
(t2):  Class “B2” Shutdown
(t3):  Class “C” Shutdown
(t4):  Class “A” Alarm
(t5):  Class “B1” Alarm
(t6):  Class “B2” Alarm
(t7):  Class “C” Alarm

SEQUENCE OF OPERATIONS

A limited warranty on materials and workmanship is given with this

FWMurphy product. 

A copy of the warranty may be viewed or printed by going to www.fwmur-

phy.com/warranty.asp.

R

EGISTERE

D

USA–ISO 9001:2000 FM 28221

UK–ISO 9001:2000 FM 29422

Printed in U.S.A.

Engine Speed (-T Models Only)

Class “B1” Timer

Class “B2” Timer

Ignition Ground Delay

Loss of Ignition

Resetting Shutdown Fault

Test Timer

Elapsed Time

Alarm Only Condition

Overspeed (-T Models Only)

Underspeed (-T Models Only)

Manual Stop

Test Mode Display

Warranty

M

ur

C

al

c

CALL MURCAL TO PLACE YOUR ORDER

P:(661)272-4700   

  

F:(661)947-7570

www.murcal.com         e-mail: [email protected]

Содержание TTDJ-DC-T

Страница 1: ...in the first two leftmost digits Hours display uses all the digits RPM display is shown in the rightmost digits with a Run Indicator in the first digit The Timer display shows the timer number in the...

Страница 2: ...he last 4 shutdown codes and any alarm present at shutdown as well as the elapsed time reading at which they occurred For instance if the unit is shutdown from sensor input 1 the display will show 01...

Страница 3: ...CATED WITHIN THE TTDJ MODULE THEREFORE EXTREME CAUTION MUST BE EXERCISED WHEN REPLACING IT FOR CLASS I DIVISION 2 HAZARDOUS AREAS INSTALLATIONS FIRST SHUTDOWN THE SYSTEM AND MAKE SURE THAT THE HAZARDO...

Страница 4: ...Sensors are normally open or normally closed mechanically actuated passive switches or Murphy certified non incendive or intrinsically safe products 2 Non incendive field circuits VOC 10 5 VDC ISC 1...

Страница 5: ...TTDJ 99062N page 5 of 8 STOP STOP STOP STOP STOP STOP STOP STOP TIMER 0 STOP STOP STOP RESET TIMER 0 SETUP TEST SETUP STOP TYPE SETUP TTDJ SENSOR SETUP MAP...

Страница 6: ...062N page 6 of 8 STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP RESET SETUP STOP TEST SETUP TIMER 0 TTDJ SE...

Страница 7: ...ps 1 3 from To Enter User Set Up Menus above Select SETUP 7 Enter the code then enter your number of pulses per engine revolution refer to Pulses Revolution above right Pulses Revolution TTDJ IGN T Ig...

Страница 8: ...mode To manually shutdown the engine press the STOP RUN key The TTDJ will shutdown the system and the display will indicate 52 Manual Stop over rides the Test mode Upon reaching a shutdown condition...

Отзывы: