User Set Up Menus
The following are the User Setup Menus for All TTDJ models:
SETUP.1
= Class B1 Timer (0 – 5:00)
SETUP.2
= Class B2 Timer (0 – 9:59)
*SETUP.3
= Sensor 1-16 Type Setup
SETUP.4
= Ignition Ground Delay (0 – 20 sec.)
*SETUP.5
= Remote Setup
0= No Remote Lockout or Reset, #29 is Class “A”
1= Remote Reset, No Remote Lockout, #29 is Class “A”
2= Remote Lockout, No Remote Reset #29 is Class “A”
3= Remote Reset, and Lockout, #29 is Class “A”
4= No Remote Reset or Lockout, #29 is Class “ESD”
5= Remote Reset, No Remote Lockout, #29 is Class “ESD”
6= Remote Lockout, No Remote Reset #29 is Class “ESD”
7= Remote Reset and Lockout, #29 is Class “ESD”
*SETUP.6
= Hours Setup
The User Setup Menus shown below are also available for -T models:
*SETUP.7
= Pulses per revolution
SETUP.8
= Overspeed
SETUP.9
= Underspeed
The User Setup Menu shown below is for ALL -DC models:
SETUP.A
=
Modbus RTU node number 1-16 (-DC models)
*These Set Up Menus are code protected (for all models).
To Enter User Set Up Menus
(Must be in Manual Stop #52)
To enter the User Setup Menus the TTDJ unit Must be in the Manual
Stop (#52) condition. If a shutdown is present other than Manual Stop,
press the “Reset” key, then immediately Press and Hold Both the
Run/Stop and Up (Timer 0) keys. Now follow these steps:
1. Press and hold both the Run/Stop and Up (Timer 0) keys until the
LCD reads (HOLD).
2. Continue to hold both keys for 3 more seconds approximately. The
display reads (SETUP.0), you are now in the User
Setup Menu.
3. Use the Up key (Timer 0) and Down (Test) keys to select the desired
Setup Menu.
4. Press the Run/Stop key to enter the desired Setup Menu.
NOTE: Some settings are password protected.
5. Use the Up and Down keys to preset the desired parameter. Press
Reset to zero the value.
6. When the desired value is entered, press Run/Stop.
7. Repeat Steps 3-6 until all parameters are preset.
8. To exit User Setup, select SETUP.0 and press Run/Stop.
Code Protection
For Setup Menus that are code protected, the LCD will read “CODE.00”
prompting the user to enter a code before allowing setup. Use the Up
and Down keys to enter the code. If the code is entered incorrectly, the
LCD will read “Error”. After 3 incorrect entries, the Code Setup is exit-
ed. Once the correct Code is entered, the Setup Menu is accessed.
To Calibrate the Tachometer
(TTDJ-DC-T
and TTDJ-IGN-T models)
The TTDJ measures RPM based on the number of pulses per engine revo-
lution. To calibrate the tachometer first enter the User Set Up Menus, see
steps 1-3 from “To Enter User Set Up Menus” above.
Select SETUP.7. Enter the code, then enter your number of pulses per
engine revolution (refer to Pulses/Revolution, above right).
Pulses/Revolution
TTDJ-IGN-T (Ignition Model)
For this model the number of pulses per revolution is determined by the num-
ber of cylinders and cycles of the engine, according to the following table:
TTDJ-DC-T (DC Model)
For TTDJ-DC-T models the pulses per revolution can come from a mag-
netic pickup. The number of pulses per revolution is simply the number
of teeth on the flywheel gear (32 to 360).
Sensor Input Set Up
Sensor inputs 1-16 are configurable. The following types are available:
Type 0 =
Class A, Shutdown
Type 1 =
Class B1, Shutdown
Type 2 =
Class B2, Shutdown
Type 3 =
Class C, Shutdown
Type 4 =
Class A, Alarm Before Shutdown
†
Type 5 =
Class B1, Alarm Before Shutdown
†
Type 6 =
Class B2, Alarm Before Shutdown
†
Type 7 =
Class C, Alarm Before Shutdown
†
To configure a Sensor Input:
1. Enter the SETUP.3 menu (enter the code). The Display will read:
(3 00).
2. Use the Up and Down keys to select the input to be configured.
For example if you select Input #1 the display reads:
(3 01).
3. Press the Run/Stop key. Assuming you selected Input #1, and that
input is currently configured as a Class A, Shutdown, the display
will read (01 0).
4. Use the Up and Down keys to select the desired Sensor Input Type.
5. Press the Run/Stop key, the display reads: (3 01).
6. Repeat Steps 2-5 as necessary.
7. To Exit press Reset, the display shows: (3 00).
Then press the Run/Stop key.
Elapsed Time Set / Reset
Enter the Elapsed Time Set Up. SETUP.6. First make sure the jumper
for Input #30 is installed. To Set the time do the following:
1. Enter the SETUP.6 menu (enter the code). The display will read the
elapsed time in hours, after the 6 (for example:
(6.00001) if the elapsed time is 1 hour).
2. Set the desired time using the Up/Down keys. Press Reset to zero the time.
3. When the desired time is entered, press the Run/Stop key.
4. To exit User Setup, press Reset, the display will show:
(SETUP 0) and press the Run/Stop key.
NOTE: Decimal fractional of the elapsed time is lost when the Elapsed
Time Setup is entered, and it can only be set to the nearest hours.
TTDJ USER CONFIGURATION AND SETUP
Cylinders
Cycles
Pulses
1
2
1
2
2
2
2
4
1
3
2
3
4
2
4
4
4
2
5
2
5
Cylinders
Cycles
Pulses
6
2
6
6
4
3
8
2
8
8
4
4
10
4
5
12
4
6
16
4
8
NOTE:
Divide the number of cylinders by 2 for split capacitor ignitions.
Multiply the number of cylinders by 2 for throw away spark ignitions.
†Alarm Before Shutdown is a function that causes annunciation
and the alarm output, but will not cause a shutdown.
TTDJ-99062N page 7 of 8