background image

User Set Up Menus

The following are the User Setup Menus for All TTDJ models:

SETUP.1

=  Class B1 Timer (0 – 5:00)

SETUP.2

=  Class B2 Timer (0 – 9:59)

*SETUP.3

=  Sensor 1-16 Type Setup

SETUP.4

=  Ignition Ground Delay (0 – 20 sec.) 

*SETUP.5

= Remote Setup 

0= No Remote Lockout or Reset, #29 is Class “A”
1= Remote Reset, No Remote Lockout, #29 is Class “A”
2= Remote Lockout, No Remote Reset #29 is Class “A”
3= Remote Reset, and Lockout, #29 is Class “A”
4= No Remote Reset or Lockout, #29 is Class “ESD”
5= Remote Reset, No Remote Lockout, #29 is Class “ESD”
6= Remote Lockout, No Remote Reset #29 is Class “ESD”
7= Remote Reset and Lockout, #29 is Class “ESD”

*SETUP.6

=  Hours Setup

The User Setup Menus shown below are also available for -T models:

*SETUP.7

= Pulses per revolution

SETUP.8

= Overspeed

SETUP.9

= Underspeed

The User Setup Menu shown below is for ALL -DC models:

SETUP.A

Modbus RTU node number 1-16 (-DC models)

*These Set Up Menus are code protected (for all models).

To Enter User Set Up Menus

(Must be in Manual Stop #52)

To enter the User Setup Menus the TTDJ unit Must be in the Manual
Stop (#52) condition. If a shutdown is present other than Manual Stop,
press the “Reset” key, then immediately Press and Hold Both the
Run/Stop and Up (Timer 0) keys. Now follow these steps:

1. Press and hold both the Run/Stop and Up (Timer 0) keys until the

LCD reads                                (HOLD).

2. Continue to hold both keys for 3 more seconds approximately. The

display reads                           (SETUP.0), you are now in the User
Setup Menu.

3. Use the Up key (Timer 0) and Down (Test) keys to select the desired

Setup Menu.

4. Press the Run/Stop key to enter the desired Setup Menu. 
NOTE: Some settings are password protected.
5. Use the Up and Down keys to preset the desired parameter. Press

Reset to zero the value. 

6. When the desired value is entered, press Run/Stop.
7. Repeat Steps 3-6 until all parameters are preset.
8. To exit User Setup, select SETUP.0 and press Run/Stop.

Code Protection

For Setup Menus that are code protected, the LCD will read “CODE.00”
prompting the user to enter a code before allowing setup. Use the Up
and Down keys to enter the code. If the code is entered incorrectly, the
LCD will read “Error”. After 3 incorrect entries, the Code Setup is exit-
ed. Once the correct Code is entered, the Setup Menu is accessed.

To Calibrate the Tachometer

(TTDJ-DC-T

and TTDJ-IGN-T models)

The TTDJ measures RPM based on the number of pulses per engine revo-
lution. To calibrate the tachometer first enter the User Set Up Menus, see
steps 1-3 from “To Enter User Set Up Menus” above. 

Select SETUP.7. Enter the code, then enter your number of pulses per
engine revolution (refer to Pulses/Revolution, above right).

Pulses/Revolution

TTDJ-IGN-T (Ignition Model)

For this model the number of pulses per revolution is determined by the num-
ber of cylinders and cycles of the engine, according to the following table:

TTDJ-DC-T (DC Model)

For TTDJ-DC-T models the pulses per revolution can come from a mag-
netic pickup. The number of pulses per revolution is simply the number
of teeth on the flywheel gear (32 to 360).

Sensor Input Set Up

Sensor inputs 1-16 are configurable. The following types are available:

Type 0 =

Class A, Shutdown

Type 1 =

Class B1, Shutdown

Type 2 =

Class B2, Shutdown

Type 3 =

Class C, Shutdown

Type 4 =

Class A, Alarm Before Shutdown

Type 5 =

Class B1, Alarm Before Shutdown

Type 6 =

Class B2, Alarm Before Shutdown

Type 7 =

Class C, Alarm Before Shutdown

To configure a Sensor Input:

1. Enter the SETUP.3 menu (enter the code). The Display will read:  

(3    00).

2. Use the Up and Down keys to select the input to be configured. 

For example if you select Input #1 the display reads:          
(3    01).

3. Press the Run/Stop key. Assuming you selected Input #1, and that

input is currently configured as a Class A, Shutdown, the display
will read                              (01    0).

4. Use the Up and Down keys to select the desired Sensor Input Type.
5. Press the Run/Stop key, the display reads:                            (3    01).
6. Repeat Steps 2-5 as necessary.
7. To Exit press Reset, the display shows:                            (3    00).

Then press the Run/Stop key. 

Elapsed Time Set / Reset

Enter the Elapsed Time Set Up. SETUP.6. First make sure the jumper
for Input #30 is installed. To Set the time do the following:

1. Enter the SETUP.6 menu (enter the code). The display will read the

elapsed time in hours, after the 6 (for example:                           
(6.00001) if the elapsed time is 1 hour).  

2. Set the desired time using the Up/Down keys. Press Reset to zero the time.
3. When the desired time is entered, press the Run/Stop key.
4. To exit User Setup, press Reset, the display will show:              

(SETUP 0) and press the Run/Stop key.

NOTE: Decimal fractional of the elapsed time is lost when the Elapsed
Time Setup is entered, and it can only be set to the nearest hours.

TTDJ USER CONFIGURATION AND SETUP

Cylinders

Cycles

Pulses

1

2

1

2

2

2

2

4

1

3

2

3

4

2

4

4

4

2

5

2

5

Cylinders

Cycles

Pulses

6

2

6

6

4

3

8

2

8

8

4

4

10

4

5

12

4

6

16

4

8

NOTE: 

Divide the number of cylinders by 2 for split capacitor ignitions.

Multiply the number of cylinders by 2 for throw away spark ignitions.

†Alarm Before Shutdown is a function that causes annunciation

and the alarm output, but will not cause a shutdown.

TTDJ-99062N page 7 of 8

Содержание TTDJ-DC-T

Страница 1: ...in the first two leftmost digits Hours display uses all the digits RPM display is shown in the rightmost digits with a Run Indicator in the first digit The Timer display shows the timer number in the...

Страница 2: ...he last 4 shutdown codes and any alarm present at shutdown as well as the elapsed time reading at which they occurred For instance if the unit is shutdown from sensor input 1 the display will show 01...

Страница 3: ...CATED WITHIN THE TTDJ MODULE THEREFORE EXTREME CAUTION MUST BE EXERCISED WHEN REPLACING IT FOR CLASS I DIVISION 2 HAZARDOUS AREAS INSTALLATIONS FIRST SHUTDOWN THE SYSTEM AND MAKE SURE THAT THE HAZARDO...

Страница 4: ...Sensors are normally open or normally closed mechanically actuated passive switches or Murphy certified non incendive or intrinsically safe products 2 Non incendive field circuits VOC 10 5 VDC ISC 1...

Страница 5: ...TTDJ 99062N page 5 of 8 STOP STOP STOP STOP STOP STOP STOP STOP TIMER 0 STOP STOP STOP RESET TIMER 0 SETUP TEST SETUP STOP TYPE SETUP TTDJ SENSOR SETUP MAP...

Страница 6: ...062N page 6 of 8 STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP STOP RESET SETUP STOP TEST SETUP TIMER 0 TTDJ SE...

Страница 7: ...ps 1 3 from To Enter User Set Up Menus above Select SETUP 7 Enter the code then enter your number of pulses per engine revolution refer to Pulses Revolution above right Pulses Revolution TTDJ IGN T Ig...

Страница 8: ...mode To manually shutdown the engine press the STOP RUN key The TTDJ will shutdown the system and the display will indicate 52 Manual Stop over rides the Test mode Upon reaching a shutdown condition...

Отзывы: