HAZARDOUS AREAS INSTALLATION 

MODE

RESET

CANCEL

ENTER

SERIES 1400 MICROCONTROLLER

Sensor Input Ribbon Cable

INTRINSICALLY SAFE 

EQUIPMENT

NON INTRINSICALLY SAFE 

EQUIPMENT

S1400 

Power Supply

Enclosure

(explosion-proof)

with IS barrier

Explosion-proof 

Conduit Seal

(provided by user)

Power from 

120 VAC, 12 or 24 VDC

Sensor Input 

Ribbon Cable

Seals MUST be

within 18 inches

(457 mm) of 

power supply

Optional for non intrinsically safe 
Normally Open sensors inputs.
Each LCDT-ISB provides for 
(2) two channels.  

LCDT-ISB

Barrier

(explosion-

proof)

Sensor Input Terminal Block 

  Sensor Inputs

(such as Murphy

SWICHGAGE

®

 

control instruments) 

Wiring to Terminal Block.

Power and

Control Cable

Explosion-proof 

Conduit Seal(s)

(provided by user)

IMPORTANT: An approved isolation barrier such as the LCDT-ISB
barrier for normally open sensors or a thermocouple type barrier 
for normally closed sensors MUST be used between the sensor 
switch and input terminals if the sensor output comes from any
energy storing device such as a relay or transistor.

S1400 Module

Green to ground

Black to sensor input 
terminal block(for one channel)

White to sensor input
terminal block (one channel)

WARNING: For hazardous application requirements, the S1400 complete system must be installed in accordance with the

National Electrical Code (NEC) Class 

I

, Division 1, Group D (article 504) specifications, and per Murphy drawing HC12046.