Section 80
6
1900003
2019-01-18
Loading Configurations with USB
There are two types of configuration files: configuration.gciBin, and configurationFull.gciBin. It
is recommended to use the larger Full file, which includes the application portion of the
configuration.
There are two methods for loading configurations using the USB port. If the configuration is
PowerVision 2.9 or later, there is a Load Configuration choice in the main menu. This is
referred to as the Local method in this manual. If the configuration is an older version, that
choice is not there, and the older method must be used.
MPC20 & MPC10 LOCAL METHOD
The file name can be customized for easy reference, but the file must have .gciBin as the
extension (i.e., perkins.gciBin, model42.gciBin, etc.).
If you load a file with the file name from PowerVision, you must use configurationFull.gciBin.
Configuration.gciBin will not load using the local method.
Step
Action
1
Go to the main menu and select Load Configuration.
2
Press Enter. The message No File Found will be displayed.
3
Install the Thumb drive, and select the correct file to be loaded. There can be
several files on the same USB Thumb Drive.
4
Press Enter and the display will prompt as follows: