background image

BEFORE BEGINNING INSTALLATION OF THIS PRODUCT

Disconnect all electrical power to the machine
Make sure the machine cannot operate during installation
Follow all safety warnings of the machine manufacturer
Read and follow all installation instructions

WARNING

General 

The Keystart 9620 series provides manual start/stop and automatic 
fault shutdown protection for generators, pumps and other engine-
driven applications. 

Keystart features a 3 way keyswitch for operator control of the engine, 
with 6 LEDs for indication of status and faults - see ‘front view’ diagram 
for details. Electrical connection and configuration options are at the rear 
- see ‘Rear view, connection and settings’ diagram. 

For each Keystart ordered, the following is supplied: 

 

1 x Keystart module, fitted with 2 x panel mounting clips 

 

2 x keys 

 

these instructions 

Panel installation 

Keystart is designed for front-of-panel mounting in a DIN standard  
92 x 92 mm (3.6 x 3.6 in.) cut-out. Allow 75mm (3.0 in.) behind the 
panel for the case depth, keyswitch and cable connection. 

Secure the case to the panel with the two ratcheted mounting clips: 

1. 2. 

3. 

Remove the plastic 
mounting clips from 
the Keystart case: 
release each clip’s 
ratchet mechanism by 
pulling outwards (A), 
then slide the clip 
back and off the  
case (B).

 

At the front of the 
panel, insert the 
Keystart (without 
clips) into the panel 
cut-out (C).

 

At the rear of the panel, 
refit the two mounting 
clips into the slots on  
the Keystart case (D). 
Slide each clip forward 
until the arms (E) are 
secured behind the 
panel face. Ratchet 
mechanism (F) prevents 
the clip from moving 
backwards.

 

 

 

Keystart 9620 series 

Engine & Generator Controls

 

Installation Instructions 

00-02-0657

revision A, 22

nd

 September 2008

catalogue section 40 & 75

Please read the following information before installing.

 A visual inspection of this product for damage during 

shipping is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical 
technicians install this product. If in doubt, please contact your local Murphy representative. 

GENERAL INFORMATION

 

Product specifications  

power supply: 

 

 

operating voltage:   
   steady state 
   brown out / cranking 

 

7 – 30 VDC 

5 VDC 

current consumption 

< 100mA 

inputs: 

 

fault switch inputs: 

close to negative DC during fault 

–ve input defined as: 

–1V to +1V w.r.t. – ve DC supply 

speed sensing input: 

  generator AC (J2+J3 on) 
 

  mag. pickup (J2+J3 off) 
 

(model 9621 only) 

70 – 270 VAC rms,  

<50 to >60 Hz. nominal 

10 – 60 VAC peak,  

<2000 to >6500 Hz. nominal 

outputs: 

(all ratings non-reactive) 

run, preheat 

positive DC, switched NO relay contact,

10 A max. @ 24VDC 

start (crank) 

positive DC via keyswitch contacts, 

10 A max. @ 24V DC 

alarm 

negative DC (open collector  

NPN transistor), 250mA max. 

calibration/tacho 

to suit 0 – 1 mA, 75 Ohm meter 

output = 0.75mA at rated engine speed 

adjustable settings: 

 

preheat timer 

0 or 10 secs (link J1),  

default = 0 secs 

fault override timer 

2 to 20 secs (VR1),  

default = 10 secs 

overspeed trip level 

100 to 130 % (VR3) of  

nominal speed calibration (VR2),  

default = 110% (of 50 or 60 Hz) 

general: 

 

overall dimensions (w x h x d)  

96 x 96 x 95 mm / 3.8 x 3.8 x 3.7 in. 

panel cut-out size 

DIN 92 x 92 mm / 3.6 x 3.6 in. 

weight 

approx. 300 g / 0.7 lb 

operating temperature  

–35°C to +55°C / –31°F to 131°F 

Model options 

Отзывы: