Current Limiting
The Guardian battery charger is current limited and will only output the rated current of the
charger.
Guardian Current Ratings
Model
Rating
BCEG-12-10 10A
BCEG-24-10 10A
BCEG-24-20 20A
Battery Charged Condition
When charged, the battery will only accept a charge to replace the losses within the battery
(approximately 1mA per AH of battery). If there is a standing load (the panel controller, etc.)
the charger will output the standing load plus the losses to the battery. If a standing load of 1A
is present with 50AH Vented Lead Acid batteries then the charger will supply 1.05 amps.
A charged battery with open circuit terminals (no load connected) will always be higher than
nominal battery voltage (12.6 on a 12V lead acid battery).
Dimensions
Model
W
D
H
Weight
BCEG-12-10 10.83”
(275mm)
4.92”
(125mm)
11”
(280mm)
22 lbs.
(10.0Kg)
BCEG-24-10 10.9”
(278mm)
4.7”
(120mm)
11”
(280mm)
22 lbs.
(10.0Kg)
BCEG-24-20 13.19”
(335mm)
7.71”
(145mm)
12.20”
(310mm)
38.5 lbs.
(17.5Kg)