FRONT PANEL DESCRIPTION
Along with each description, an attempt has been made
to clarify output and input connections according to their
functions and terminals or wire color. 

A. Description of LED Callouts
1. IGNITION 
The ignition LED will come on when the system receives
a signal to start.  If the alarm before start is used, this
ignition LED will NOT come on until the 5 second alarm
goes off. 

2. PICKUP PRESENT
When the engine is cranking or running and the pickup is
connected properly with sufficient output voltage (2 volt
rms) this LED will come on.  IMPORTANT - This LED
must come on or the unit will not operate properly. 

Note: this LED will NOT be on if a mechanical switch is
used as a crank disconnect sensor. 

3. CRANK
The crank LED is on when the engine is cranking and is
used to show that the crank circuitry is functioning
properly. 
The crank solenoid will be connected to terminal 1 of the
A88-F or the white/brown wire of the A88, if the solenoid
is connected to positive to operate. 
If the crank solenoid is grounded to operate, connect it to
terminal 2 of the A88-F or connect it to the white/red wire of
the A88. 

4. CRANK DISCONNECT
This LED comes on when the crank disconnect
adjustment is adjusted to disengage the starter.  When
this LED comes on, the crank LED goes out. (See item B-
2 for control setting adjustments)

5.  CHOKE 
This LED will come on for approximately 3-4 seconds at
the beginning of each crank cycle and then go out.  If a
choke or compression release solenoid is connected from
battery positive to Terminal 3 (A88-F)or the violet wire
(A88) it will be energized when the LED comes on. 

6. OVERCRANK 
If the engine is called on to start and fails after 5 tries, this
LED will come on and stay on to indicate cause of
shutdown. 

7. OIL PRESSURE
The oil pressure LED will come on if oil pressure is lost
during operation and remain on to indicate cause of
shutdown.  Terminal 11 of the A88-F or the black/white
wire of the A88 are connected to the oil pressure switch.

8. ENGINE TEMPERATURE 
If the unit is shutdown because of high engine temperature,
this LED will be on.  The temperature sensor is connected to
Terminal 12 of the A88-F or the blue/white wire of the A88. 

9. SPARE 
This LED comes on to indicate cause of shutdown if the
spare is used.  Connect the monitor to Terminal 13 of the
A88-F and the yellow/white wire of the A88. 

Note: the overcrank, oil pressure, engine temperature
and spare circuits are locked out for 30 seconds during
start up.  They require normally open sensors (close to
operate).  A summary output is available (Terminal 20 on
the A88-F and the brown wire of the A88.) for remote
indication when a shutdown occurs. 

B. Description of AOT Switch, Crank Disconnect

Control & Rest/Crank Time Control

1. AUTO-OFF-TEST 

a.  OFF
When a shutdown occurs, this unit must be removed
from power to reset.  The Auto-Off-Test switch removes
power when placed in the off position.  The green LED
will go off.  The unit should be left off 8-10 seconds
to allow the circuitry to discharge and stabilize. 
b.  TEST 
This position is used after all connections have been
made or for periodic checks that should be a part of a
preventive maintenance program.  The start and stop
inputs are by-passed when this switch is placed in the
test position. The unit will automatically initiate the
crank cycle.

c.  AUTO 
For normal operation and after the system has been
tested, Place the switch in this position.  It indicates
the controller will take over starting and stopping the
engine. 

Note: these units may have a 4-5 second alarm before start.
The A88-F comes with the alarm hooked up by connection
of terminals 16 and 17.  The A88 comes without the alarm
hooked up; if alarm is needed, ground the red/white wire.
Although it is an optional hook up, it is recommended that
this alarm be used to alert personnel of a start. 

2. CRANK DISCONNECT CONTROL 
Adjust this control to make the crank circuit disengage the
starter when the engine starts.  Rotating it counter-
clockwise makes the starter drop out at lower RPM. 

3. REST AND CRANK TIME 
By placing this switch in one of the 4 positions, the rest
and crank time is selected.  If the switch is placed in the
10 seconds position, the system will crank the engine for
10 seconds, then rest for 10 seconds. 

Note: if the engine starts momentarily, then dies, it will go
into a 25-30 second rest period before it attempts another
crank.  This is regardless of what position the crank and
rest switch is in. 

When the system is called on to crank the first crank cycle
will be typically 50% longer than the remaining four tries.
This feature will aid in starting a cold engine. 

3

Содержание Automatic Engine Controller A88

Страница 1: ...AUTOMATIC ENGINE CONTROLLERS MODELS A88 AND A88 F INSTALLATION MANUAL A88 8916N Revised 01 97 Section 40 00 02 0196 A...

Страница 2: ...W Murphy Southern Division P O Box 1819 Rosenberg Texas 77471 USA tel 281 342 0297 fax 281 341 6006 e mail murphysd intertex net Since 1939 Frank W Murphy Ltd Church Rd Laverstock Salisbury SP1 1QZ U...

Страница 3: ...TION OF THIS MURPHY PRODUCT Disconnect all electrical power to the machine Make sure the machine cannot operate during installation Follow all safety warnings of the machine manufacturer Read and foll...

Страница 4: ...age 8 30 VDC negative ground 2 Current 12 volts less load current a standby 10 ma b crank 140 ma c shutdown 32 ma 3 Maximum fuse size 4 amp slow blow B Input Requirements 1 Start stop control switch a...

Страница 5: ...ECT OVER CRANK ENGINE TEMP CHOKE OIL PRESSURE AUTO OFF TEST CRANK AND REST TIME IGNITION ON PICK UP PRESENT CRANK CRANK DISCONNECT CRANK DISCONNECT 20s 15s 10s 5s CHOKE OVER CRANK OIL PRESSURE ENGINE...

Страница 6: ...LED comes on to indicate cause of shutdown if the spare is used Connect the monitor to Terminal 13 of the A88 F and the yellow white wire of the A88 Note the overcrank oil pressure engine temperature...

Страница 7: ...as below After the engine has been running for approximately 30 seconds the indicator will be energized 5 WARM UP If it is desirable to have a warm up period or a 90 second delay after the engine has...

Страница 8: ...e blank space Step No 7 Time Delay This system has a 60 second built in time delay for customer use If the appropriate inputs are grounded it times out after the crank disconnect light comes on Step N...

Страница 9: ...One 1 amp max Remote Annunciator Connection 1 amp max Engine Running Shutdown Summary Pickup Signal Source Connection Use Only One Electronic or Breaker Type Ignition Tach O P ALT Magnetic Pickup A88...

Страница 10: ...1 wire Ong Wht Connect 10 for alarm Pin 12 wire Black Battery negative Pin 13 wire Red Battery positive Pin 14 wire Brn Wht Stop I P Pin 15 wire Grey Wht Connect to 14 for close to run open to stop op...

Страница 11: ...1 amp max Use Continuous Duty Solenoid Remote Annunciator Connection 1 amp max Engine Running Shutdown Summary Pickup Signal Source Connection Use Only One Electronic or Breaker Type Ignition Tach O...

Страница 12: ...al 26 Positive Terminal 7 Alternator I P Terminal 8 Vacuum switch I P Terminal 9 Ground for time delay I P Terminal 10 No connection Terminal 11 Oil pressure I P Terminal 12 Water temperature I P Term...

Страница 13: ...n Grey White Brown White Stop White Yellow White Brown Black Blue Red Black White White Red White Ignition N C Green White A88 White Orange 16 17 22 1 25 7 26 11 23 15 4 21 or A88 F Blue Grey Charging...

Страница 14: ...26 1 16 11 4 12 15 21 or A88 F E IG BAT LO ST Combination Switch Brown White Grey White Red White 17 To Yellow Red OIL To Yellow Grn TEMP Closed to Start Open to Stop Connect Black Red White Black Bla...