A.  The Automatic Engine Controller, Model A88 and
A88-F 
is designed to automatically start, monitor and stop
electric start engines.  The A88 comes in an all-weather
case with a 5 foot cable and a plug for connection.  The
A88-F is the same system, but housed in a panel-mount
case with terminals on back for connecting. 

B.  Features

1. Has a self-contained Auto-Off-Test Switch. 
2. Rest and crank time selected by a single switch. 
3. Adjustable crank  disconnect speed switch. 
4. Close a switch to run; open to stop feature. 
5. Engine starts and runs when a contact closes and

stops when a separate set of contacts close. 

6. Goes into a rest period in the event of a false start. 
7. Alarm before start to alert personnel. 

8. Crank disconnect circuitry accepts the following inputs:

a.  breaker or electronic type ignition 
b.  magnetic pickup 
c.  alternator tach 
d.  flywheel alternator 
e.  mechanical switch 

9. Has a built-in one minute time delay for customer use. 
10. Five fixed crank attempts before shutdown. 

SECTION I: INTRODUCTION

A.  Power Requirements:

1.  Voltage 8-30 VDC, negative ground. 
2.  Current @ 12 volts less load current.

a.  standby

10 ma

b.  crank

140 ma

c.  shutdown

32 ma

3.  Maximum fuse size, 4 amp, slow blow. 

B.  Input Requirements:

1.  Start-stop control switch 

a. SPST N.O. dry contact; close to run, open to stop 

b. SPDT dry contact 

c. Two SPST N.O. dry contacts; one, momentary

close to run; one momentary close to stop 

2.  Magnetic pickup or alternator tach requirements: 

a.  voltage  2 volts, rms minimum 
b.  25 to 2000 hz crank disconnect 
c.  maximum 100 volts Pk Pk 

C.  Output Ratings: Source = switch to battery 

Sink = switch to ground 

1.  Ignition or run relay; SPDT dry relay contacts

rated 10 amp @ 30 VDC resistive, 6 amp @ 30
VDC inductive. 

2.  Crank output 

a.  transistor

1 amp source

b.  transistor

1 amp sink

3.  Choke 

a.  transistor

1 amp sink

4.  Time delay 

a.  transistor

1 amp sink

5.  Summary 

a.  transistor

1/2 amp sink

11.  An output to indicate that the engine is running

to be used as remote indication or in warm up
operation. 

12.  Has a summary of shutdown output. 

13.  Monitors the following engine functions and will

shut the engine down in event of a failure: 

a.  Overcrank 
b.  Oil Pressure 
c.  Engine Temperature 
d.  Spare 

14.  Has 30 second lockout feature for start up. 
15.  Output for choke actuator. 

SECTION II: SPECIFICATIONS  

1

Содержание Automatic Engine Controller A88

Страница 1: ...AUTOMATIC ENGINE CONTROLLERS MODELS A88 AND A88 F INSTALLATION MANUAL A88 8916N Revised 01 97 Section 40 00 02 0196 A...

Страница 2: ...W Murphy Southern Division P O Box 1819 Rosenberg Texas 77471 USA tel 281 342 0297 fax 281 341 6006 e mail murphysd intertex net Since 1939 Frank W Murphy Ltd Church Rd Laverstock Salisbury SP1 1QZ U...

Страница 3: ...TION OF THIS MURPHY PRODUCT Disconnect all electrical power to the machine Make sure the machine cannot operate during installation Follow all safety warnings of the machine manufacturer Read and foll...

Страница 4: ...age 8 30 VDC negative ground 2 Current 12 volts less load current a standby 10 ma b crank 140 ma c shutdown 32 ma 3 Maximum fuse size 4 amp slow blow B Input Requirements 1 Start stop control switch a...

Страница 5: ...ECT OVER CRANK ENGINE TEMP CHOKE OIL PRESSURE AUTO OFF TEST CRANK AND REST TIME IGNITION ON PICK UP PRESENT CRANK CRANK DISCONNECT CRANK DISCONNECT 20s 15s 10s 5s CHOKE OVER CRANK OIL PRESSURE ENGINE...

Страница 6: ...LED comes on to indicate cause of shutdown if the spare is used Connect the monitor to Terminal 13 of the A88 F and the yellow white wire of the A88 Note the overcrank oil pressure engine temperature...

Страница 7: ...as below After the engine has been running for approximately 30 seconds the indicator will be energized 5 WARM UP If it is desirable to have a warm up period or a 90 second delay after the engine has...

Страница 8: ...e blank space Step No 7 Time Delay This system has a 60 second built in time delay for customer use If the appropriate inputs are grounded it times out after the crank disconnect light comes on Step N...

Страница 9: ...One 1 amp max Remote Annunciator Connection 1 amp max Engine Running Shutdown Summary Pickup Signal Source Connection Use Only One Electronic or Breaker Type Ignition Tach O P ALT Magnetic Pickup A88...

Страница 10: ...1 wire Ong Wht Connect 10 for alarm Pin 12 wire Black Battery negative Pin 13 wire Red Battery positive Pin 14 wire Brn Wht Stop I P Pin 15 wire Grey Wht Connect to 14 for close to run open to stop op...

Страница 11: ...1 amp max Use Continuous Duty Solenoid Remote Annunciator Connection 1 amp max Engine Running Shutdown Summary Pickup Signal Source Connection Use Only One Electronic or Breaker Type Ignition Tach O...

Страница 12: ...al 26 Positive Terminal 7 Alternator I P Terminal 8 Vacuum switch I P Terminal 9 Ground for time delay I P Terminal 10 No connection Terminal 11 Oil pressure I P Terminal 12 Water temperature I P Term...

Страница 13: ...n Grey White Brown White Stop White Yellow White Brown Black Blue Red Black White White Red White Ignition N C Green White A88 White Orange 16 17 22 1 25 7 26 11 23 15 4 21 or A88 F Blue Grey Charging...

Страница 14: ...26 1 16 11 4 12 15 21 or A88 F E IG BAT LO ST Combination Switch Brown White Grey White Red White 17 To Yellow Red OIL To Yellow Grn TEMP Closed to Start Open to Stop Connect Black Red White Black Bla...

Отзывы: