Install electronic controls in a separate ventilated control room that is protected from extreme
temperatures and dirty environments. Place the controls so that the operators can conveniently
use the control and read indicators and displays.
•
Keep low voltage wires separate from high voltage wires.
•
Use shielded wiring for low level signals. For buried wiring (building to building runs) use high
grade jell filled cables that are impervious to moisture.
•
Seal cable entry points and control boxes to prevent contamination and corrosion. If you use
silicon sealant with acetic acid cure, keep the control open and ventilated until cured.
Otherwise, the acetic acid will attack the metal parts, including circuitry.
3.1.2
W
HAT
C
OMES IN THE
P
ACKAGE
•
One Trio unit
•
One hanging bracket
•
Two screws
3.2
Mounting the Unit
•
•
3.2.1
K
NOCKOUTS
1. Using the supplied clips and screws, mount the Trio.
2. On the bottom the Trio are knockouts used to route the low and high voltage cables.
Figure 1: Trio
Knockouts and PG Size
o
Using a screwdriver and a hammer, gently apply pressure to the knockouts.
o
Only open the holes that you require.
o
Munters recommends removing the knockouts before mounting the unit.
o
16*: Use this knockout for the Ethernet cable.
3. Place the required cables through the cable holders at the bottom of the unit.
CAUTION
Run low voltage cables through one knockout and high voltage relay cables through a
separate knockout. Do not place them in the same knockout!
Содержание Rotem Trio 20
Страница 20: ... Munters AB 2020 20 Figure 6 Relay and port numbering ...
Страница 44: ... Munters AB 2020 44 ...
Страница 99: ... Munters AB 2020 99 Refer to Tunnel Ventilation page 123 for more details ...
Страница 110: ... Munters AB 2020 110 4 Click the fan in the upper right Both fans turn blue 5 Define fans as required ...
Страница 141: ... Munters AB 2020 141 If an outside temperature sensor is enabled map timers to it if required ...
Страница 160: ... Munters AB 2020 160 23 3 2TRIO 20 CONTAINER SPARE PARTS ...
Страница 162: ... Munters AB 2020 162 23 3 3TRIO 20 DOOR CARDS SPARE PARTS ...
Страница 164: ... Munters AB 2020 164 23 3 4TRIO 20 MAIN CONTAINER SPARE PARTS ...
Страница 170: ... Munters AB 2020 170 Card Description Munters Ordering Number TUBES AND FILTERS FOR RPS NO RPS CARD 999 99 00503 ...
Страница 186: ... Munters AB 2020 186 Figure 33 Relay and port numbering 26 2 3POWER Figure 34 Power ports ...
Страница 199: ... Munters AB 2020 199 2 Insert and secure the SMA connector ...
Страница 202: ... Munters AB 2020 202 example only ...