For 10 controllers:
o
~1200 meter (~4000 feet): 9600 Baud
o
~1800 meter (~6000 feet): 4800 Baud
o
~2400 meter (~7870 feet): 2400 Baud
NOTE:
Baud rate depends on cable length and on the number of controllers.
4.3
Completing the Installation
The following section summarizes the steps needed to complete the installation. Refer to the relevant
sections in the manual for further details.
•
Configuring the communication to outside devices
•
Communicator / Comm-Box Connectivity
4.3.1
C
ONFIGURING THE COMMUNICATION TO OUTSIDE DEVICES
1. Set the baud rate to the controllers (refer to Configuring the channel settings, page 34).
2. Test the connection to each controller (refer to Displaying the controllers, page 35).
3. Test the communication channel to each controller (refer to Channel/Signal tests, page 35).
4. Set the baud rate to the local computer (refer to Defining the communication speed with the local
PC, page 37).
4.3.2
C
OMMUNICATOR
/
C
OMM
-B
OX
C
ONNECTIVITY
NOTE:
Users having an Ethernet card – refer to Appendix C: Ethernet Card/RotemNet Setup, page
59.
•
Communicator Software Version 3.07.01 supports the Comm-Box. Download the software from the
Munters web site.
•
Connect the Comm-Box to a Munters Communicator using RJ11 cable and the D9-RJ11 adapter
(supplied by Munters). Communicator units require the Communicator Serial Card
(P/N: C-COMM-SERIAL / 904-99-00038) to support the Comm-Box.
WARNING!
Disconnect the power before beginning.