2
incorrectly
used
(e.g
indoors
without
adequate air circulation) or not properly
working. CO poisoining may lead to death.
Early signs of CO poisoning are headache,
dizziness and/or nausea. If you have these
signs, get fresh air at once, shut off the
heater and check the heater operation and
installation. Call qualified service if needed.
Some people such as pregnant women,
persons with heart or lung diseases, or under
the influence of alcohol, or at high altitudes
are more affected by carbon monoxide than
others.
Connect the power cord female connector to the
male connector on the control panel (see Fig. 4).
3. Operation with portable generators:
If the heater is powered by a
portable generator, before use:
a. check and be sure that the generator is
properly grounded to earth. Refer to the
generator manual for grounding procedures.
b. check and be sure that the electrical ratings of
the generator are consistent with the electrical
ratings of the heater. Refer to data plates.
c. measure the actual output voltage from the
generator: the voltage must be 120 V +/- 10%
(108 V - 132V). Do not connect the heater to
the generator if the voltage is not within this
range.
The installation of the equipment shall be in
accordance
with
the
regulations
of
authorities having jurisdiction and CSA B139.
Do not connect the heater to
external fuel tanks.
6. Operation
1. Fill the fuel tank with clean 1-K Kerosene, Fuel
Oil (Diesel Fuel) No.1 or Fuel Oil (Diesel Fuel)
No.2.
JAZ 42/80/80W: the sightglass on the right side
of the tank allows the user to see when fuel level
is getting low (see Fig. 5)
JAZ 125/160: the fuel gauge on top of the tank
allows the user to see the fuel level during
operation (see Fig. 6)
3.
Turn
the
thermostat
knob
fully
counterclockwise.
4. Plug the heater into a 120V/60Hz, 1 Phase
GFCI protected grounded outlet.
The electrical connections
and grounding of the heater shall be in
compliance with the National Electrical Code,
ANSI/NFPA 70 or the CSA C22.1, Canadian
Electric Code, Part I.
Always check power cables
and extensions before use. Do not use the
heater if any cable is damaged.
IMPORTANT: extensions must be approved,
grounded, 3-wire cords of proper size.
Extension cord size requirements:
6-10 ft
18 AWG (0.75 mm²)
11-100 ft
16 AWG (1 mm²)
101-200 ft
14 AWG (1.5 mm²)
Fig. 5
Fig. 4
Fig. 6