The 2
nd
Generation DC Series VRF Indoor Units
20
201806
Table 6.2: Wall mounted heating capacity (continued)
Capacity
(kW)
Outdoor air
temperature (°C)
Indoor air temperature (°C DB)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
WB
DB
kW
kW
kW
kW
kW
kW
8.0
-20
-19.8
5.04 5.04 5.04 5.04 5.04 5.04
-19
-18.8
5.40 5.40 5.40 5.40 5.40 5.40
-17
-16.7
5.67 5.67 5.67 5.67 5.67 5.67
-15
-14.7
5.85 5.85 5.85 5.85 5.85 5.85
-13.00
-12.60
6.03 6.03 6.03 6.03 6.03 6.03
-11.00
-10.50
6.30 6.30 6.30 6.30 6.30 6.30
-10.00
-9.50
6.57 6.57 6.57 6.57 6.57 6.57
-9.10
-8.50
6.75 6.75 6.75 6.75 6.75 6.75
-7.60
-7.00
6.84 6.84 6.84 6.84 6.84 6.84
-5.60
-5.00
7.11 7.11 7.11 7.11 7.11 7.11
-3.70
-3.00
7.47 7.47 7.47 7.47 7.47 7.47
-0.70
0.00
8.01 8.01 8.01 8.01 8.01 7.56
2.20
3.00
8.46 8.46 8.46 8.46 8.28 7.56
4.10
5.00
8.73 8.73 8.73 8.73 8.28 7.56
6.00 7.00 9.00
9.00
9.00
8.73 8.28 7.56
7.90
9.00
9.27 9.27 9.00 8.73 8.28 7.56
9.80
11.00
9.54 9.54 9.00 8.73 8.28 7.56
11.80
13.00
9.90 9.72 9.00 8.73 8.28 7.56
13.70
15.00
10.17 9.72 9.00 8.73 8.28 7.56
9.0
-20
-19.8
5.60 5.04 5.60 5.60 5.60 5.60
-19
-18.8
6.00 5.40 6.00 6.00 6.00 6.00
-17
-16.7
6.30 6.30 6.30 6.30 6.30 6.30
-15
-14.7
6.50 6.50 6.50 6.50 6.50 6.50
-13.00
-12.60
6.70 6.70 6.70 6.70 6.70 6.70
-11.00
-10.50
7.00 7.00 7.00 7.00 7.00 7.00
-10.00
-9.50
7.30 7.30 7.30 7.30 7.30 7.30
-9.10
-8.50
7.50 7.50 7.50 7.50 7.50 7.50
-7.60
-7.00
7.60 7.60 7.60 7.60 7.60 7.60
-5.60
-5.00
7.90 7.90 7.90 7.90 7.90 7.90
-3.70
-3.00
8.30 8.30 8.30 8.30 8.30 8.30
-0.70
0.00
8.90 8.90 8.90 8.90 8.90 8.40
2.20
3.00
9.40 9.40 9.40 9.40 9.20 8.40
4.10
5.00
9.70 9.70 9.70 9.70 9.20 8.40
6.00 7.00 10.00
10.00
10.00
9.70 9.20 8.40
7.90
9.00
10.30 10.30 10.00 9.70 9.20 8.40
9.80
11.00
10.60 10.60 10.00 9.70 9.20 8.40
11.80
13.00
11.00 10.80 10.00 9.70 9.20 8.40
13.70
15.00
11.30 10.80 10.00 9.70 9.20 8.40
Abbreviations:
TC: Total capacity
Notes:
1.
Shaded cells indicate rating condition.