IMPORTANT INFORMATION FOR THE USED REFRIGERANT
A
I
This product has the fluorinated gas, it is forbidden to release to air.
{{|J?'
GWP=Global Warming Potential
Model
Refrigerant/kg
tonnes CO
2
equivalent
2.50
2.50
2.90
3.20
5.22
5.22
6.06
10kW
12kW
14kW
16kW
5kW
7kW
Factory charge
=
Frequency of Refrigerant Leak Checks
1) For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes of CO
2
equivalent or more,but of less than
50 tonnes of CO
2
equipment,at least every 12 months, or where
a leakage detection system is installed, at least every 24 months.
2) For equipment that contains fluorinated greenhouse gases in
quantities of 50 tonnes of CO
2
equivalent or more,but of less than
500 tonnes of CO
2
equipment,at least every six months, or where
a leakage detection system is installed, at least every 12 months.
3) For equipment that contains fluorinated greenhouse gases in
quantities of 500 tonnes of CO
2
equivalent or more,at least every
three months, or where a leakage detection system is installed,
at least every six months.
4) This air-conditioning unit is a hermetically sealed equipment that
contains fluorinated greenhouse gases.
5) Only certificated person is allowed to do installation, operation
and maintenance.