background image

Fig.4-1

  

Ha nging screw bolts

Ce iling 

Timber over the beam

Ro of beam

Put the square timber traversely over the roof beam, then 
install the hanging screw bolts. (Refer to 

Fig.4-1

Wooden construction

New concrete bricks

Fig.4-2

Inlaying or embedding the screw bolts (Refer to 

Fig.4-2

)

  

Blade shape insertion

Slide insertion

Overhanging the indoor unit

Overhang the indoor unit onto the hanging screw bolts with 
block. 

Position the indoor unit in a flat level by using the level indicator, 
unless it may cause leakage.

Screw nut

Overhang part

washer

Hanging
screw bolt

Fig.4-5

Pipe Connection

The static pressure   outside the unit is 200Pa , the length of 
the air pipe attached is determined by this parameter.

The positioning of ceiling hole and indoor unit and hanging 
screw bolts 

Routine method of installation: the size of installation for indoor 
unit following 

Fig.4-9

Please install with Φ10 hanging screw bolts.

Carry out the pipe and line operation in the ceiling after finishing 
the installation of the main body. While choosing where to start 
the  operation, determine the direction of the position the 
refrigerant pipes, drain pipes, indoor & outdoor lines and line-
controlled lines to the connection places before. 

ķ

ĸ

Ĺ

Fig.4-7

Fig.4-8

For original concrete bricks

Steel roof beam structre

Fig.4-3

Fig.4-4

Steel bar

Embedding screw bolt

(Pipe hanging and embedding screw bolt)

Use embeding screw bold, crock and stick harmness (refer 
to 

Fig.4-3

)

  

 

 

 

 

 

Hanging screw bolt

Hanging bolts

Supporting

Install and use directly the supporting angle steel. (refer to 

Fig.4-4

)

  

angle  steel

Install the main body

Installing the dust proof net and canvas air passage

Open the air-in grill 
Anti-clockwise the bolts as indicated in follow figure 
sketch.Then pull down the air-in grill. 

ķ

Take out the air-in grill.

Dismantle the air filter

Clean the air filter (Vacuum cleaner or pure water may be 
used to clean the air filter. If the dust accumulation is too 
heavy , please use soft brush and mild  detergent to clean it 
and dry out in cool place).

The air-in side should face down when using water. 
(See 

 

Fig.4-7

)

ĸ

Ĺ

ĺ

Ļ

ļ

The air-in side should face up when using vacuum cleaner. 
(See

 

Fig.4-8

)

Fig.4-6

maintenance of motor

˖

0 1 2

F

3

E

4

D

5

C

6

B

7

A

89

Installation manual

3

High pressure duct

Содержание CL23904

Страница 1: ...CL23380 to CL23383 High Pressure Duct MVD DC Installation manual English www mundoclima com MVD...

Страница 2: ...car or in the cabin In the kitchen or a place full of oil steam There is strong electromagnetic wave CONTENTS PAGE INSTALLATION PRECAUTION 1 INSTALLATION PLACE 1 ACCESSORIES 2 INDOOR UNIT INSTALLATION...

Страница 3: ...out Especially in case there is a ceiling position the refrigerantpipes drainpipes indoor outdoorlinestotheconnec tion places before hanging up the machine The installation of hanging screw bolts Ins...

Страница 4: ...of the main body While choosing where to start the operation determine the direction of the position the refrigerant pipes drain pipes indoor outdoor lines and line controlled lines to the connection...

Страница 5: ...11 28 169 691 52 35 136 123 179 15 ELECTRICAL CONTROL BOX PLASTIC COVER 930 135 88 24 46 68 82 82 56 270 420 249 29 722 65 75 61 43 189 123 642 420 85 856 214 86 800 44 253 155 189 123 26 255 33 65 RE...

Страница 6: ...Fig 4 11 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arrow show in Fig 4 12 4 Clean th...

Страница 7: ...3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fan assembly 4 Refer to Fig 4 14 horizontal pushing the fan assembly until it cannot no...

Страница 8: ...ray and then take off the tray as figure showed in Fig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re install the unit follow the rever...

Страница 9: ...rding to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightly and take down to remove it 4 A...

Страница 10: ...lt A bolt C Installation manual 9 High pressure duct 1121 75 343 96 60 4 10 hanging screw configure on spot Air intake Air outlet Refrigerant pipe flared connection 16 5 8 Refrigerant pipe flared conn...

Страница 11: ...the part B and part C of indoor unit The part A and part B of indoor unit individual put into the positionsite then install the indoor unit following the reverse order of step 2 3 4 and 5 Maintenance...

Страница 12: ...00 1800 2200 2600 3000 3400 3800 4200 0 20 40 60 80 100 120 140 160 180 200 220 1400 1800 2200 2600 3000 3400 3800 4200 MVD 160T1 DHN1 B HIGH FAN SPEED MIDDLE FAN SPEED LOW FAN SPEED MVD 200T1 DHN1 B...

Страница 13: ...the outside frame tightly to the ceiling and fix it Fig 7 15 Hang up the outside frame until it sticks to the ceiling tightly Canvas air passage Ceiling Outside frame Air passage Main body Waist shape...

Страница 14: ...enable pipe The bending angle should not exceed 90 Bending position is preferably in the bendable pipe The larger the better it is Do not bend the pipe more than three times Bend the connecting pipe o...

Страница 15: ...NT PIPE CONNECTION 9 1 Expel The Air Fig 9 1 Flaring Cut a pipe with a pipe cutter Insert a flare nut into a pipe and flare the pipe 90 lean crude burr A 90 4 _ 4 5 2 _ Outside diameter A mm Max 8 7 6...

Страница 16: ...low zero Then fasten the nut When the pumping has finished close the Lo lever of the manifold valve completely and turn off the vacuum pump When you have pumped for over 15 minutes please confirm that...

Страница 17: ...se power of air condictioners The wiring of 71 to 160 indoor unit please refer to Fig 11 1 and Fig 11 2 is the communication wiring for 200 250 and 280 indoor unit The reserved function is indicated i...

Страница 18: ...P5 XS4 XP4 NEW DISPLAY BOARD WIRE CONTROLLER CN16 CN29 CN3 Y G CN23 FAN1 TA T1 T2 T2B C S EEV XP1 XP5 XS1 XS5 XT1 XT2 XT3 PUMP BD 1 BLACK For 200 250 280 models REACTOR CN13 T2 A XS1 XP1 T2B A T1 A XP...

Страница 19: ...c pressure range which means the airflow noise and dehumidification are all in the best state 81 120Pa 121 170Pa 171 200Pa 61 120Pa 121 170Pa 171 200Pa 2 3 4 ENC2 Table 12 2 6 definition 00 means shut...

Страница 20: ...01 means shutting down the unit to stop cold air at 20 unit to stop cold air at 24 unit to stop cold air at 26 6 definition 00 means the time of stopping TERMAL fan is 4 minutes 01 means the time of s...

Страница 21: ...Run LED flash or show E2 Run LED flash or show E3 Run LED flash or show E4 Timer LED flash slowly or show E6 Defrost LED flash slowly or show E7 Alarm LED flash slowly or show Ed Alarm LED flash or s...

Страница 22: ...er please refer to the manual of the outdoor unit you choose Fig 15 3 Fig 14 1 Bypass A Bypass B Gas pipe A Gas pipe B Liquid pipe A Liquid pipe B Liquid lines A and B are joined by a distributor The...

Страница 23: ...air conditioner under the mode of COOLING with the remote controller and check the following points per the Owner s Manual If there is any malfunction please resolve it through chapter Troubles And Ca...

Страница 24: ...ASK FOR MORE INFORMATION Phone 34 93 446 27 81 eMail info mundoclima com TECHNICAL ASSISTANCE Phone 34 93 652 53 57 www mundoclima com MVD...

Отзывы: