Munchkin Gas-Fired Hot Water Boiler Скачать руководство пользователя страница 63

62

GAS-FIRED BOILER 

Boiler Manual

PART 14: TROUBLESHOOTING 

(CONTINUED)

Table 14-2: 925 Control Board FAULT Codes

Code

Description

Remedy

„

F00

High Limit Exceeded.

1. Check circulation pump operation
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the

return thermister to the supply thermister.

3. Check thermister reading on supply thermister. Replace switch if faulty.
4. If this is a new installation, disconnect the two light grey wires from the zone control, and twist the wires together. Depress the S4 reset

button. If the fault clears, the problem is outside the boiler

5. If this is an existing installation with glycol in it, check the condition of the water pressure switch. It may be necessary to jump out the water

pressure switch (temporarily only, as a trouble shooting aid) The 24 VAC signal, may have grounded through the glycol if the water pressure
switch is leaking.

„

F01

Vent Temperature Limit Exceeded. 

1. Push the red reset button on the switch.
2. Check the flue temperature during operation using a combustion analyzer.
3. Replace the vent limit switch if faulty.
4. Verify the combustion drain if clear and draining properly.
5. Visually inspect the target wall to see if it is intact. If not intact replace target wall.

„

F02

Interrupted or Shorted
Supply (Outlet) Thermister.

1. Check the electrical connection to the thermister on the outlet manifold. Verify 5 VDC by checking in Molex connector. Verify thermister

values by referencing chart in this manual.

2. Replace thermister if necessary.

„

F03

Interrupted or Shorted
Return (Inlet) Thermister.

1. Check the electrical connection to the thermister on the inlet manifold. Verify 5 VDC by checking in Molex connector. Verify thermister

values by referencing chart in this manual.

2. Replace thermister if necessary.

„

F05

Supply (Outlet)
Temperature exceeds 230°F.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the

return thermister to the supply thermister.

„

F06

Return (Inlet) Temperature
Exceeded 230°F.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the

return thermister to the supply thermister.

3. Check direction of flow on boiler circulator. (See Piping Details in this manual.)

„

F09

No flame detected – The boiler will
make three attempts at ignition
before the control goes into this
lockout condition. *See spark
electrode detail.

1. Watch the igniter through the observation window provided.
2. If there is no spark, check the spark electrode for the proper ¼” gap. Use 2 quarters together as a gauge to hold ignitor against to check

gap distance.

3. Remove any corrosion from the spark electrode and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the boiler.
5. If there is a flame, check the flame sensor.
6. Check any flue blockage or condensate blocks.

„

F10

Loss of Flame Signal – The boiler
will relight 4 times before the control
goes into this lockout condition.

1. Monitor the gas pressure to the unit while in operation.
2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the boiler is running.
4. If the green light doesn’t come on or goes off during operation check the flame signal on the status menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
6. If the flame rectifier probe continues to read low, replace it.
7. Check the stability of the flame rectification signal. If the signal is unstable, you may need to replace the burner gasket.

„

F11

False Flame Signal – The boiler will
lock out if it senses a flame signal
when there should be none present.

1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or replace the gas valve.
5. Turn the gas on at the service valve after corrective action is taken.
6. Check for condensate back up. Condensate back up can damage the refractory wall, and if the wall falls against the rectifier probe, it may

conduct the signal to ground, giving a false reading.

„

F13

Combustion Fan Speed Low – The
boiler will lock out if it senses that
the fan speed is less than 70% of
expected rate for more than 60
seconds.

1. Check the combustion air fan wiring.
1a. Check the quality of the 24 VAC signal by measuring from any connected safety to ground. A low voltage situation may cause a “false”

error code

2. Replace the combustion air fan.
3. Replace the control board.

„

F14

Combustion Fan Speed High – The
boiler will lock out if the fan speed is
more than 130% of expected rate for
more than 60 seconds.

1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.

„

F18

Gas Valve Error

1. Make sure the connector is correctly connected to the gas valve.
2. Check the electrical wiring from the valve to the control board.
2a. Voltage readings will be from 18-22 VDC on the outlet of the gas valve plug from any pin to ground, the connector must remain in contact

with the pins.

2b. On the 399M only, check the 24 VAC relay block.
3. Replace the low voltage wiring harness assembly.
4. Replace control board.

„

F19

Supply voltage frequency out of range. (92-132 VAC 60 Hz)

„

F30

Watchdog

Call factory for further assistance. Watchdog

„

F31

Parameter Memory

Call factory for further assistance. Parameter memory error, reprogramming needed

„

F32

Parameter Memory Write Error

Call factory for further assistance. Parameter memory write error

„

F33

Programming Error

Call factory for further assistance. Parameter memory error, reprogramming needed

„

PP

Parameters Programmed

Press S4 reset

„

Nc

Internal processor error, due to incoming voltage problems. (92-132 VAC 60 Hz). May also occur if neutral wire has been broken or damaged.

„

F

Internal error

Содержание Gas-Fired Hot Water Boiler

Страница 1: ...nstaller service technician Read all instructions in this manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial proper...

Страница 2: ...ff D Backflow Preventer E System Water Piping Methods F Circulators G Hydronic Piping with Circulators Zone Valves and Multiple Boilers H Circulator Sizing WARNING If the information in this manual is...

Страница 3: ...Exhaust Vent and Intake Air Vent Pipe Location E Exhaust Vent and Intake Air Vent Sizing G Exhaust Vent and Intake Air Pipe Installation H Heater Removal from a Common Vent System I Condensate Remova...

Страница 4: ...ption 57 60 A Programming the Vision I Option B Vision I Program Access C Vision I Program Navigation Part 14 Trouble Shooting 61 63 A Munchkin Error Code B Boiler Error C Boiler Fault Part 15 Mainten...

Страница 5: ...symbol indicates a potentially hazardous situation which if not avoided may result in property damage DEFINITIONS NOTICE Heat Transfer Products Inc reserves the right to make product changes or update...

Страница 6: ...at exchanger reduces heat transfer overheats the stainless steel heat exchanger and causes failure Addition of oxygen carried in by make up water can cause internal corrosion in system components Leak...

Страница 7: ...savings 3 Gas Valve The gas valve senses suction from the blower allowing gas to flow only if the gas valve is powered and combustion air is flowing 4 Supply water temperature sensor This sensor monit...

Страница 8: ...eezing temperatures or any other type of blockage Plastic tubing must be the only material used for the condensate line Steel brass copper or others will be subject to corrosion or deterioration A sec...

Страница 9: ...the condensate to flow to the location of the condensate hose the boiler must be slightly pitched back to assure proper flow direction The Munchkin Boiler comes equipped with leveling feet Should you...

Страница 10: ...1 4 NPT 3 4 2 4250 1200 58 lbs 80M 27 000 80 000 74 000 64 000 95 1 0 8 gal 1 1 4 NPT 3 4 3 3700 1600 75 lbs 140M 46 000 140 000 129 000 112 000 95 1 1 4 gal 1 1 4 NPT 3 4 3 3550 1400 101 lbs 199M 66...

Страница 11: ...10 GAS FIRED BOILER Boiler Manual DIMENSIONS 80M 140M 199M Figure 2 2 Figure 2 3...

Страница 12: ...ordinances National Fuel Gas Code ANSI Z223 1 latest edition Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 when required National Electrical Code For Canada...

Страница 13: ...VENT The Munchkin Boiler requires a special vent sys tem designed for pressurized venting Munchkin Boilers are rated ANSI Z21 13 Category IV pressurized vent likely to con dense in the vent You must...

Страница 14: ...nce will operate continuously e Test for spillage at draft hood opening after 5 PART 3 PREPARE BOILER LOCATION CONTINUED DANGER Do not install the Munchkin Boiler into a common vent with any other app...

Страница 15: ...lief valve to operate resulting in possibility of severe personal injury death or substantial property damage minutes of main burner operation Use the flame of a match or candle or smoke from a cigare...

Страница 16: ...nsion tank 1 Always install an automatic air vent on top of the air separator to remove residual air from the system F CIRCULATORS Sizing space heat system piping 1 See Piping Details in this manual P...

Страница 17: ...the cooling cycle Chilled Water Medium must be piped in parallel with the heater Freeze Protection for new or existing systems must use glycol that is specifically formulated for this purpose It will...

Страница 18: ...14 16 18 20 22 24 26 28 30 32 5 10 15 20 25 30 35 37 5 40 Flow in Gallons per Minute Friction in Feet of Head MUNCHKIN 399M NOTE The recommended circulators are based on 1 gpm per 10 000 btu hr with...

Страница 19: ...in volume for a temperature increase from 32 F to 180 F while water expands 3 with the same temperature rise Allowances must be made for this expansion in the system design 4 A 30 mixture of glycol w...

Страница 20: ...supply only the boiler loop 2 Install a separate circulator for each zone 3 Connect DHW domestic hot water piping to indirect storage water heater as shown L MULTIPLE BOILERS 1 Connect multiple boile...

Страница 21: ...way valve zone valve air separator backflow preventer diaphragm type expansion tank pressure reducing valve diff pressure bypass anti scald rated mixing valve pressure gauge 4 way motorized mixing va...

Страница 22: ...ze for connecting a Munchkin boiler is 1 25 inches and 2 inches for the 399M 5 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 6 The anti scal...

Страница 23: ...lf 3 The minimum pipe size for connecting a Super Stor water heater is 1 inch 4 The minimum pipe size for connecting a Munchkin boiler is 1 25 inches and 2 inches for the 399M 5 All pumps are shown wi...

Страница 24: ...pipe size for connecting a Munchkin boiler shall be 1 25 inches and 2 inches for the 399M 6 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 7...

Страница 25: ...installed upstream and downstream of all closely spaced tees 4 The minimum pipe size for connecting a Super Stor water heater is 1 inch 5 The minimum pipe size for connecting a Munchkin boiler shall...

Страница 26: ...e size for connecting a Munchkin boiler shall be 1 25 inches and 2 inches for the 399M 6 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 7 The...

Страница 27: ...pipe size for connecting a Munchkin boiler shall be 1 25 inches and 2 inches for the 399M 6 All pumps are shown with isolation flanges The alternative is standard flanges with full port ball valves 7...

Страница 28: ...n tained B ZONING WITH ZONE VALVES USING VISION I 1 Connect the boiler to the system as shown in piping details 3A through 3C 2 Connect the DHW circulator P2 directly to the boiler as shown as shown i...

Страница 29: ...99M 6 All pumps are shown with isolation flanges and integral flow check valves The alternative is standard flanges with full port ball valves and a separate flow check valve 7 The anti scald mixing v...

Страница 30: ...own with isolation flanges and integral flow check valves The alternative is standard flanges with full port ball valves and a separate flow check valve 7 The anti scald mixing valve is recommended if...

Страница 31: ...es with full port ball valves and a separate flow check valve 7 The anti scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F 8 Install a minimum of 12 di...

Страница 32: ...r shall be 1 25 inches and 2 inches for the 399M 6 All pumps are shown with isolation flanges and integral flow check valves The alternative is standard flanges with full port ball valves and a separa...

Страница 33: ...boiler shall be 1 25 inches and 2 inches for the 399M 6 All pumps are shown with isolation flanges and integral flow check valves The alternative is standard flanges with full port ball valves and a...

Страница 34: ...n with isolation flanges and integral flow check valves The alternative is standard flanges with full port ball valves and a separate flow check valve 7 The anti scald mixing valve is recommended if t...

Страница 35: ...n flanges and integral flow check valves The alternative is standard flanges with full port ball valves and a separate flow check valve 7 The anti scald mixing valve is recommended if the DHW temperat...

Страница 36: ...ral flow check valves The alternative is standard flanges with full port ball valves and a separate flow check valve 7 The anti scald mixing valve is recommended if the DHW temperature is set above th...

Страница 37: ...pipe size for connecting a Super Stor water heater is 1 inch 5 The minimum pipe size for connecting a Munchkin boiler shall be 1 25 inches and 2 inches for the 399M 6 All pumps are shown with isolatio...

Страница 38: ...alternative is standard flanges with full port ball valves and a separate flow check valve 7 The anti scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F...

Страница 39: ...art 7 Ensure the exhaust and intake piping comply with these instructions regarding vent system Inspect finished combustion air intake and exhaust piping thoroughly to ensure all joints are well secur...

Страница 40: ...ance or hazard h When adjacent to a public walkway locate exit terminal at least 7 feet above grade i Do not locate the exhaust directly under roof overhangs to prevent icicles from forming j Provide...

Страница 41: ...and direct vent venting systems Reference National Fuel Gas Code ANSI Z223 1 NFPA 54 2002 Fig 7 3 Multiple Vent Spacing Note Exhaust must extend out 1 foot Figure 7 5 Multiple Boiler Installations Fig...

Страница 42: ...bined equivalent length is 16 equivalent feet F LONGER VENT RUNS 1 The maximum combined equivalent length can be extended by increasing the diameter of both exhaust vent and intake air vent pipe equal...

Страница 43: ...between the space in which the appliance remains connected to the common venting system located and other spaces in the building Turn on clothes dryers and any appliances not connected to the common...

Страница 44: ...he condensation line may be necessary to avoid blockage of the conden sate flow CAUTION The condensate line must remain unobstructed allowing free flow of condensate If condensate is allowed to freeze...

Страница 45: ...IDEWALL VENTING WITH TEE INTAKE AND COUPLING EXHAUST COUPLING EXHAUST INTAKE AIR VENT 12 MIN EXTERIOR WALL TEE ALL HORIZONTAL TOP VIEW STRAIGHT AND VERTICAL PIPING COUPLING SUPPORT BRACKETS MUST BE US...

Страница 46: ...PIPING ALL HORIZONTAL EXTERIOR WALL VENT EXHAUST RIGHT SIDE VIEW MUST BE FACING UP NOTE INTAKE LEG SUPPORT BRACKETS MUST BE USED ON INTAKE AIR VENT 1 MIN AND VERTICAL PIPING FRONT VIEW EXTERIOR WALL M...

Страница 47: ...R 12 OVER MAXIMUM SNOW LEVEL OR 24 10 0 MIN RIGHT SIDE VIEW EXTERIOR WALL INTAKE AIR VENT ROOF VENT WITH CONCENTRIC VENT KIT AND VERTICAL PIPING ALL HORIZONTAL SUPPORT BRACKETS MUST BE USED ON EXHAUST...

Страница 48: ...esent The gas piping must be sized for the proper flow and length of pipe to avoid pressure drop Both the gas meter and the gas regulator must be properly sized for the total gas load If you experienc...

Страница 49: ...12 FIGURE 12 1 Fig 8 2 service to an area to provide maintenance to their lines This gas valve must not be replaced with a conventional gas valve under any circumstances As an additional safety featur...

Страница 50: ...1 Connect room thermostat or end switch 2 Install thermostat on inside wall away from influences of drafts hot or cold water pipes lighting fixtures television sunrays or fireplaces 3 Thermostat antic...

Страница 51: ...50 GAS FIRED BOILER Boiler Manual PART 9 FIELD WIRING CONTINUED Fig 9 4 Fig 9 3 Fig 9 1 Fig 9 2...

Страница 52: ...51 GAS FIRED BOILER Boiler Manual PART 9 FIELD WIRING CONTINUED Fig 9 5...

Страница 53: ...ll allow the installer to con trol the temperature of the indirect water heater from the Munchkin Boiler and give the water heater priority over the Central Heating Circuit Once the Water Heater is sa...

Страница 54: ...ufacturer s instructions B FREEZE PROTECTION WHEN USED 1 Determine freeze protection fluid quantity using total system water content following fluid manufacturer s instructions Remember to include exp...

Страница 55: ...CUIT S 1 Disconnect the two external wires connected to the boiler thermostat terminals low voltage terminal strip terminals 5 and 6 2 Connect a voltmeter across these two incoming wires Close each th...

Страница 56: ...t you support the condensation line to assure proper drainage H FINAL CHECKS BEFORE STARTING BOILER 1 Read Startup Procedures within this manual for proper steps to start boiler See Startup Report to...

Страница 57: ...em perature setting of the Munchkin The burner will not start until the outlet water temperature reaches a temperature that is equal to the tem perature setting for the Munchkin Boiler minus the diffe...

Страница 58: ...es not take place when the controller is in Test mode only temperature limitation based on the Munchkin Boiler Central Heating set point The user will be allowed to increase or decrease the fan speed...

Страница 59: ...se or decrease a value you will need to press either the S 1 key or S 2 key to change the default values If there is no key action for 1 minute the display returns to normal operation Changes are effe...

Страница 60: ...stalled 17 0 Interface Board Function 0 Building Management 1 Enables Tekmar Modulating control Consult with Tekmar to assure the Tekmar Control is compati ble Default Function Function Value Descript...

Страница 61: ...URVE CENTRAL HEATING CURVE Factory Default 50 OUTSIDE TEMPERATURE F 59 32 41 41 24 27 9 9 0 81 45 63 99 Plot your Curve CENTRAL HEATING CURVE SUPPLY OUTLET TEMPERATURE F 167 104 77 59 68 86 95 131 113...

Страница 62: ...supply to the boiler at the gas service valve Table 14 1 925 Control Board ERROR Codes WARNING When servicing or replacing any components of this boiler be certain that The gas is off All electrical...

Страница 63: ...5 If there is a flame check the flame sensor 6 Check any flue blockage or condensate blocks F10 Loss of Flame Signal The boiler will relight 4 times before the control goes into this lockout condition...

Страница 64: ...130 41 28600 50 22800 59 18300 68 14770 77 12000 86 9804 95 8054 104 6652 113 5522 Boiler Sensor 7250P 667 Indirect Sensor 7250P 320 Boiler and Indirect Temperature F Resistance ohms 32 32550 41 25340...

Страница 65: ...thing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh air Munchkin Boiler side so the flow can be observed c Disconnect connections from the gas valve s...

Страница 66: ...Blower 7250P 144 31 Burner Door 7250P 169 12 Combustion Blower 7250P 085 32 Burner Door Ceramic Refractory 7250P 161 13 Gas Valve Adapter Plate w Screws 7250P 644 33 Gasket Burner 7250P 070 14 Screws...

Страница 67: ...play w Ribbon Cable 7250P 332 22 S S Hex Nut 10 32 Blocked Vent Pressure Switch 7250P 153 7 Blocked Vent Pressure Switch 7250P 150 23 S S Hex Nuts 7250P 559 8 Screws 8 x 1 2 Blocked Vent Pressure Swit...

Страница 68: ...s Valve 7250P 718 140M 199M 7250P 117 199M 9 Swirl Plate 7500P 092 80M 26 Nut M6 Burner Door 7500P 067 7500P 093 140M 199M 27 Burner Door 7250P 684 10 Gas Valve Adapter Plate w Screws 7250P 644 28 Bur...

Страница 69: ...PVC Tee Sch 40 3 4 NPT Condensate Assy 7250P 646 7 Screw 1 4 20 x 1 2 Control Board Mounting Panel 7250P 184 22 Cable Clamp Condensate Assy 7250P 649 8 Control Board Hold Down Clips 7250P 352 23 Screw...

Страница 70: ...e Electrode 7250P 069 9 Screws M4 x 30MM Allen Head N A 27 Flame Rectification Probe w Gasket 7250P 049 10 Right Angle Connector 7250P 723 28 Screws Torx M5 x 22MM Air Gas Channel to Burner Door 7250P...

Страница 71: ...lamp Exhaust Assembly 7250P 549 8 Fuse Control Board 7250P 378 24 PVC Pipe Sch 40 4 Exhaust Assembly 7250P 524 9 Control Board Display w Ribbon Cable 7250P 332 25 S S Hex Nut 10 32 Blocked Vent Pressu...

Страница 72: ..._ppm CO Low Fire 4 Verify System Operation Turn up thermostat to verify wiring connections 5 Record Ionization Current Check A reading at d7 on the status menu see start up section ____ A High Fire __...

Страница 73: ...heating curve See Part 13 Electrical Connections Check wire connections make sure they are tight Circuit breakers Check to see that the circuit breaker is clearly labeled exercise circuit breaker Swit...

Страница 74: ...ECO replace if corroded Water Pressure Switch Check operation check for signs of leakage replace if corroded Thermistors Check wiring verify through ohms reading see chart part 14 Fig 14 3 Final Inspe...

Страница 75: ...f installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back up is...

Страница 76: ...manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instructions provided by the manufact...

Страница 77: ...76 MAINTENANCE NOTES...

Страница 78: ...77 MAINTENANCE NOTES...

Страница 79: ...78 MAINTENANCE NOTES...

Страница 80: ...2007 Heat Transfer Products Inc www HTproducts com LP 185 REV 12 10 07...

Отзывы: