MTRA-FSP Installation & Operation Manual 

 

 
 

 
00242600-MTRA-FSP_Manual.doc 

Page 7 of 16 

4.2 

DIP Switch Settings 

The MTRA-FSP is configured using the DIP switches located on the front of the 
relay enclosure. 

DIP # 

Setting 

Mode Description 

See Section: 

OFF 

Empty (Discharge) Mode 

5.1 

ON 

Fill (Charge) Mode 

5.2 

OFF 

High Level Alarm 

6.1 

ON 

Low Level Alarm 

6.1 

OFF 

0.5 sec Pump Activation and Deactivation 
Delay 

8.2 

ON 

10 sec Pump Activation and Deactivation 
Delay 

8.2 

OFF 

Constant Alarm Output 

6.1 

ON 

Flash Alarm Output (1Hz) 

6.1 

OFF 

0.5 sec Alarm Activation Delay 

8.2 

ON 

10 sec Alarm Activation Delay 

8.2 

OFF 

NC Alarm Output 

6.1 

ON 

NO Alarm Output 

6.1 

Probe Sensitivity 

8.1 

OFF 

OFF 

1kohm 

 

ON 

OFF 

4kohm 

 

OFF 

ON 

20kohm 

 

ON 

ON 

80kohm 

 

Содержание MTRA-FSP

Страница 1: ...MTRA FSP Level Control Relay Installation Operation Manual...

Страница 2: ...Ltd in Australia USA and many countries worldwide PUMPVIEW is a registered trademark of MultiTrode Pty Ltd in Australia Design registration is pending for the MultiSmart Pump Controller Remote and Ba...

Страница 3: ...troduction 5 3 Specifications 5 4 Installation 6 4 1 Power Supply 6 4 2 DIP Switch Settings 7 5 Operation Modes 8 5 1 Empty Discharge Mode 8 5 2 Fill Charge Mode 10 6 Alarms 12 6 1 Level Alarms AL Pro...

Страница 4: ...ds DANGER This symbol is used where non compliance could result in injury or death WARNING This symbol is used where non compliance could result in incorrect operation damage to or failure of the equi...

Страница 5: ...rent status including Pump On Off Thermal Fault Probe Fault and Level Alarm The MTRA FSP level control relay is designed to be easy to install and configure All connections are clearly labelled on the...

Страница 6: ...nd an overcurrent protection device must be included in the installation The disconnection device must be in close proximity to the equipment and within easy reach of the operator and be marked as the...

Страница 7: ...de 5 1 1 ON Fill Charge Mode 5 2 OFF High Level Alarm 6 1 2 ON Low Level Alarm 6 1 OFF 0 5 sec Pump Activation and Deactivation Delay 8 2 3 ON 10 sec Pump Activation and Deactivation Delay 8 2 OFF Con...

Страница 8: ...ay and also the Pump Relay in case the high level probe has failed The pump will continue to operate until the liquid level drops below the low level probe and the pump deactivation period expires A t...

Страница 9: ...MTRA FSP Installation Operation Manual 00242600 MTRA FSP_Manual doc Page 9 of 16...

Страница 10: ...The pump will continue to operate until the liquid level rises to the high level probe and the pump deactivation period expires A thermal fault will deactivate the pump regardless of liquid level A Pr...

Страница 11: ...MTRA FSP Installation Operation Manual 00242600 MTRA FSP_Manual doc Page 11 of 16...

Страница 12: ...he Alarm contacts can be used to operate an alarm device such as a light or siren The alarm output can be set to Normally Open NO or Normally Closed NC using DIP Switch 6 NC alarm output DIP Switch OF...

Страница 13: ...occurs the Probe LED flashes and the Failsafe Alarm output contacts are activated Also the pump contacts will be deactivated so the pump cannot run until the fault condition is removed NOTE If a non f...

Страница 14: ...buttons wired into the Manual Hand input and the Off input 7 1 Manual Operation of Pump Hand Manual pump operation works as follows Pushing the Manual Hand button will start the pump The pump will con...

Страница 15: ...vity can be changed using dip switches 7 and 8 if the sensitivity needs adjustment to allow for different types of liquid DIP Switch 7 8 Sensitivity OFF OFF 1 kohm ON OFF 4 kohm OFF ON 20 kohm ON ON 8...

Страница 16: ...Steady Thermal Thermal fault active Flashing Assumed probe fault Steady Probe Failsafe alarm active Flashing MultiTrode Pty Ltd Head Office Brisbane Technology Park 18 Brandl Street PO Box 4633 Eight...

Отзывы: