Multitel SDTA-02 Скачать руководство пользователя страница 1

 

 

 

 
 

 
 
 
 
 

 

SDTA-02 

Step Down Transformer Adapter

 

 
 

User’s Manual 

Содержание SDTA-02

Страница 1: ...SDTA 02 Step Down Transformer Adapter User s Manual...

Страница 2: ...t shall 1 Keep all information contained herein confidential and shall protect same in whole or in part from disclosure and dissemination to all third parties and 2 Use the same for operating and main...

Страница 3: ...2...

Страница 4: ...ENT 10 4 2 MOUNTING THE SYSTEM 10 4 3 WIRING AND CONNECTING 11 4 3 1 GENERAL INFORMATION 12 4 4 ALERNATIVE VOLTAGE MEASUREMENTS 12 5 MAINTENANCE 16 5 1 CALIBRATION 16 5 2 TROUBLESHOOTING 16 5 2 1 Gene...

Страница 5: ...93 06 25 First English issue Pierre Poulin 1 01 94 10 12 1 02 97 05 08 Minor modifications and new formatting Fran ois Dionne 1 1 00 06 16 New certification information for CSA c and CSA US Gilles Bel...

Страница 6: ...onfigurations available for the SDTA 02 interface Table 1 SDTA 02 Models and Part Numbers DESCRIPTION MULTITEL PART SDTA 02 240 VAC 3 phases M 4173 SDTA 02 600 VAC 3 phases M 4178 These models are CSA...

Страница 7: ...SDTA 02 GENERAL INFORMATION www multitel com support multitel com 6 Figure 1 Physical Aspect...

Страница 8: ...put impedance Voltmeter 240 V 2400 600 V 6000 Ammeter 0 2 Output signal Voltmeter 17 VAC 2 nominal inputs max 28 VAC Ammeter 500 mVAC 2 2 ENVIRONMENTAL Temperature Operation 0 C to 50 C 32 F to 122 F...

Страница 9: ...analog input channels need to be programmed with the proper scaling factor according to the AC voltage or AC current input range see Table 2 Please refer to the user s manual of your MULTITEL monitor...

Страница 10: ...w multitel com support multitel com 9 Table 3 SDTA 02 Setup PHASE JUMPER MXP2 MIRADOR RPM 1000 C Phase A JP5 OFF ON JP6 ON OFF JP9 ON OFF Phase B JP3 OFF ON JP4 ON OFF JP8 ON OFF Phase C JP1 OFF ON JP...

Страница 11: ...S multimeter with clamp on meter Bx cable 14 2 Belden cable 9305 or 20 AWG stranded NOTE Unpack and verify with the Material list that all the material is received and in good condition 4 2 MOUNTING T...

Страница 12: ...on of the SDTA 02 4 3 WIRING AND CONNECTING IMPORTANT This Cabling and connecting section provides the general installation procedures and describes how to interconnect and put into service a SDTA 02...

Страница 13: ...low the manufacturer s instruction supplied with the CTs Make sure that polarity dots on CTs is respected 4 4 ALERNATIVE VOLTAGE MEASUREMENTS Connect each breaker output max 15 Amp for each phase A B...

Страница 14: ...SDTA 02 INSTALLATION www multitel com support multitel com 13 Figure 3 AC Current and Voltage Measurements...

Страница 15: ...USE TYPE PIN NAME USE TYP E 1 VOUTC2 Voltmeter phase C common output lead OUT 5 VOUTB1 Voltmeter phase B output lead OUT 2 VOUTC1 Voltmeter phase C output lead OUT 6 N C Not connected N A 3 N C Not co...

Страница 16: ...TYPE PIN NAME USE TYPE 1 VINA1 Phase A VAC input lead IN 5 VINB2 Phase B VAC common input lead IN 2 VINA2 Phase A VAC common input lead IN 6 N C Non connected N A 3 N C Not connected N A 7 VINC1 Phase...

Страница 17: ...er to calibrate the erratic measurement 1 Configure the MULTITEL monitoring system s analog channel according to specifications 2 Read the source value with an RMS multimeter or RMS clamp on meter 3 A...

Страница 18: ...le 2 5 The wiring is compliant with specifications in the SDTA 02 connector definition 6 If all of these possible causes are not true your SDTA 02 may be defective refer to Multitel s Customer Service...

Отзывы: